Skip to content
Boilers.caby ROMA Heating & Cooling

Camus Hydronics · Dynaforce Series

Camus Dynaforce DR400

The Camus Dynaforce DR400 is the 399 MBH hydronic-heating size of Camus' fully condensing watertube line: 399 MBTU/hr input, 375 MBTU/hr output, up to 99% thermal efficiency and 5:1 turndown on the Honeywell SOLA control.

Status unknownSold in Canada

Key figures

Max input
399 MBTU/hr
Max CSA output
375 MBTU/hr
AFUE
Min input
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Camus Dynaforce DR400 in practice

Per the official Dynaforce hydronic-heating submittal (99-0129 Rev. 06), the DR400 is rated at 399 MBTU/hr input and 375 MBTU/hr output with a 6.3 US-gallon heat-exchanger water content and a 500 lb shipping weight. It connects on 1 1/2" NPT water lines with a 1" NPT gas connection, and 120 vac, 60 hz — 20 a max (boiler only).

The DR400 uses the Dynaforce's all-welded 439 stainless 12-pass watertube heat exchanger with 316L waterways, rated to 160 psig with constant 40°F returns, fired by a radial knitted-stainless premix burner through Pulse-width modulation (DR300–DR1000). direct igniter, 3 ignition tries then lockout, with light-off at no more than 50% input.

Because Camus is a Mississauga, Ontario manufacturer, the Dynaforce is a Canadian-made condensing watertube option; Boilers.ca reproduces the manufacturer's printed figures here and leaves sizing of a boiler plant to a heat-loss and load calculation by a licensed contractor.

Best suited to

  • Hydronic heating plants whose design load lands near 399 MBTU/hr input (375 MBTU/hr output)
  • Projects wanting a condensing watertube boiler with a Canadian-built heat exchanger and 40°F return capability
  • Multiple-boiler plants: the SOLA control cascades up to eight units

Applicability and support

Model number
DR(H) 400
Canadian availability
available
Production status
unknown
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Camus Hydronics. Units are shown with every value; notes flag conflicting sources or missing figures.

Camus Dynaforce DR400 specifications
SpecificationValueNote
Input
Input, maximum399 MBTU/hrAs printed in the Dynaforce hydronic-heating submittal (99-0129 Rev. 06); 5:1 turndown gives a 20% minimum firing rate.
Output
Output, maximum375 MBTU/hrHydronic heating output as printed in the submittal.
Efficiency
Efficiency99 %Up to 99% thermal efficiency; NOx 9 ppm corrected to 3% O2 (submittal 99-0129 Rev. 06).
Venting and air
VentingCategory II or IV (SS / AL29-4C, PPE / polypropylene; PVC and CPVC for select systems — consult factory)
Physical and connections
Heat-exchanger water content6.3 US gal
Weight500 lb
Water connections1 1/2" NPT
Gas connection1" NPT
Heat exchanger439 SS welded 12-pass watertube, 316L waterways
Electrical
Electrical requirement120 VAC, 60 Hz — 20 A max (boiler only)
Operating limits and other
IgnitionDirect igniter, 3 ignition tries then lockout
Modulation drivePulse-width modulation (DR300–DR1000)
Turndown ratio5:1Minimum 20% firing rate with light-off at no more than 50% input.
Max. working pressure160 psig1100 kPa; ASME Section IV heat-exchanger testing.
System return temperature40 °FConstant allowable return temperatures for fully condensing operation.
ControlHoneywell SOLA touchscreen; Modbus RTU; cascade up to 8
CertificationCSA (ANSI Z21.13 / CSA 4.9); ASHRAE 90.1

Manuals

    Alerts documented for this model

    None documented yet.

    Services

    Frequently asked questions

    Is the Dynaforce DR400 condensing?

    Yes. Every Dynaforce is fully condensing with a welded 439 stainless watertube heat exchanger rated for constant 40°F system returns, up to 99% thermal efficiency and 9 ppm NOx.

    How big is the DR400?

    The submittal prints 399 MBTU/hr maximum input and 375 MBTU/hr hydronic-heating output, with a 500 lb weight and 1 1/2" NPT water connections.

    What fuel can a Dynaforce burn?

    Natural gas or propane, with hydrogen blend up to 25% (UL Verified) also listed by Camus. Fuel type and conversion are decided and performed by a licensed contractor.

    Questions about the Camus Dynaforce DR400?

    Describe what the boiler is doing and get a straight answer about the next step.

    On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

    Sources and verification

    Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

    CallEmailEstimate