HTP EFW-285WBN

The HTP EFW-285WBN is the 285 MBH class wall-mount model of the current EFW (Elite Firetube Wall Mount) line: 28.5 to 285 MBH input, 263 MBH heating capacity, a 228 MBH net AHRI water rating at 95% AFUE, a 3" vent connection and a 180 lb wall package with the Honeywell Sola control.

CurrentCanadian status unknown

Key figures

Max input
285 MBH
Max CSA output
—
AFUE
95 %
Min input
28.5 MBH
Natural gasPropaneHeating-onlyresidential

Input is gas energy consumed; output is heat delivered. Never size from input alone.

HTP EFW-285WBN in practice

The EFW-285WBN is a wall-mount, condensing, stainless-steel fire-tube boiler in HTP's current EFW Series. The official rating table prints 28.5–285 MBH input, 263 MBH heating capacity, a 228 MBH net AHRI water rating and 95% AFUE on the ASME 'H' SA240-S43932 down-fired fire-tube heat exchanger; the 3" vent/air connection runs to the page's 3" up to 150 ft limit in PVC, CPVC, polypropylene or stainless steel.

The unit carries a 10:1 modulating burner with direct-spark ignition, a built-in ECM circulation arrangement on the primary loop, an integrated low-water cut-off with test switch, and the advanced Honeywell Sola boiler controller with a backlit screen, 2 central-heat inputs (high and low temperature), DHW priority, outdoor reset with the supplied 10k outdoor sensor, warm-weather shutdown, Modbus RTU and lead-lag cascade of up to eight EFW boilers. It mounts on the wall as standard (floor kit optional, HTP P/N 6000084630), weighs 180 lb with water and holds 4.9 gal; power is 120 V / 1 Ph / 60 Hz at less than 12 A.

The EFW ships factory-set for natural gas and converts to propane with the documented conversion kits; capacity is derated 4% per 1,000 ft above 2,000 ft. HTP backs the line with the 15-year limited warranty document shared with the ELU/EFTU (registered installations extend pressure-vessel coverage through year 15), and the product page advertises a free 5-year parts warranty when registered upon installation. Boilers.ca found no official statement of Canadian sales, so canadianStatus stays 'unknown'; gas, combustion and venting work belongs with a licensed contractor against the EFW I&O manual (420011327000).

Best suited to

  • Homes or light-commercial loads whose heat-loss calculation fits inside 285 MBH of input
  • Wall-mounted installations with long vent runs (the page allows up to 150 ft on the 285)
  • Owners wanting the Honeywell Sola control with Modbus RTU and 8-boiler cascade capability

Applicability and support

Model number
EFW-285WBN
Canadian availability
unknown
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Series terms

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by HTP. Units are shown with every value; notes flag conflicting sources or missing figures.

HTP EFW-285WBN specifications
SpecificationValueNote
Input
Input rate, minimum28.5 MBH28,500 Btu/hr, as printed on the official EFW rating table and in I&O Table 2-1.
Input rate, maximum285 MBH285,000 Btu/hr, as printed on the official EFW rating table and in I&O Table 2-1.
Output
Heating capacity263 MBHHeating capacity as printed on the official EFW rating table (ratings certified by AHRI to U.S. DOE test procedures).
Net AHRI rating, water228 MBHNet AHRI water rating as printed on the official EFW rating table.
Efficiency
DOE AFUE95 %AFUE as printed for this size on the official EFW rating table; the 340/399 rows print thermal efficiency instead.
Venting and air
Vent/air intake pipe diameter3"The official page states vent runs of up to 3" up to 150 ft; approved materials are PVC, CPVC, polypropylene or stainless steel, with five vent termination options and 2" optional venting on some models.
Physical and connections
Water connections1-1/4" NPT maleAs printed on the official EFW rating table.
Gas connection3/4" NPT maleAs printed on the official EFW rating table.
Cabinet (H x W x D)33-3/8" x 21-1/4" x 18-5/8"As printed on the official page rating table; the I&O Table 2-1 prints the 285 cabinet depth as 18-7/8 in (both figures as printed).
Approximate boiler weight with water180 lbAs printed on the official EFW rating table.
Boiler water content4.9 galAs printed on the official EFW rating table.
Water pressureMaximum operating pressure 80 psi; 30 psi ASME pressure relief valve factory suppliedThe EFW submittals print a maximum operating pressure of 80 psi and a factory-supplied 30 psi ASME relief valve; the boiler is ASME 'H' stamped to Section IV.
Heat exchangerSA240-S43932 stainless steel, down-fired fire tube, ASME 'H' stampedThe page describes an ASME certified down-fired fire-tube exchanger with dimpled tubes; the submittal prints SA240-S43932 stainless steel.
MountingWall mount standard; floor mounting with optional kit (HTP P/N 6000084630)The submittal prints wall (standard) or floor mounting with the optional kit; zero clearance to combustibles with service clearances.
Electrical
Power supply120 V / 1 Ph / 60 Hz, less than 12 A
Operating limits and other
FuelNatural gas (factory) or propane with documented conversion kitsThe EFW I&O states the boilers are factory set for natural gas and must be converted with the listed Natural Gas to LP Conversion Kit; the conversion-kit table prints kit part numbers 560000283500 (285) and 560000283000 (340/399).
TurndownUp to 10:1The official page and the submittal sheets print a fully modulating burner with 10:1 turndown.
ControlAdvanced Honeywell Sola boiler controller with backlit screenThe I&O lists the Honeywell Sola Controller R7910B1015/B; features include auto-diagnostics, 2 central-heat inputs (high and low temperature), DHW priority, outdoor reset with the factory 10k outdoor sensor, warm-weather shutdown, Modbus RTU and lead-lag cascade up to 8 EFW boilers.
Altitude operationMaximum listed capacity at 0–2,000 ft; derate 4% per 1,000 ft above 2,000 ftAs printed on the official page table footnotes and the I&O high-altitude table (USA de-rate: 10% at 3,000 ft, 16% at 4,000 ft, 18% at 4,500 ft, 20% at 5,000 ft per the page).
Warranty15-year limited warranty (5-year basic all components; registered installations extend pressure-vessel coverage through year 15)The ELU/EFTU/EFW limited warranty (420030066700, 07-07-23) prints basic coverage years 1–5 at 100% and registered extended coverage years 6–10 at 100% and years 11–15 at 20% on the pressure vessel; the product page states a free 5-year parts warranty when registered upon installation.

Frequently asked questions

What are the EFW-285WBN ratings?

28.5–285 MBH input, 263 MBH heating capacity, a 228 MBH net AHRI water rating and 95% AFUE per the official EFW rating table.

What size vent does the EFW-285WBN use?

The 3" vent/air connection, with the official page stating runs up to 3" up to 150 ft in PVC, CPVC, polypropylene or stainless steel.

How is the EFW-285WBN controlled?

By the advanced Honeywell Sola boiler controller with backlit display, outdoor reset (10k sensor supplied), DHW priority, Modbus RTU and cascade of up to eight EFW boilers.

Questions about the HTP EFW-285WBN?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.