Skip to content
Boilers.caby ROMA Heating & Cooling

Navien · NFB700-C Commercial Boiler

Navien NFB700-600C

The Navien NFB700-600C steps the floor-standing NFB700-C line to 40 to 599 MBH of input with a 584 MBH heating capacity and a 508 MBH net AHRI water rating at 97.5% thermal efficiency, in the same 622 lb cabinet as the 500C.

CurrentSold in Canada

Key figures

Max input
599 MBH
Max CSA output
AFUE
Min input
40 MBH
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Navien NFB700-600C in practice

The NFB700-600C fires from 40 to 599 MBH at a printed 97.5% thermal efficiency, with the product page listing a 584 MBH heating capacity and a 508 MBH net AHRI water rating (net figures are based on a piping and pickup allowance of 1.15). Physically it is identical to the NFB700-500C, so the 100 MBH of extra ceiling comes at no change to the installation footprint.

The boiler weighs 622 lb dry and 843 lb with its 26.5 gallons of water, measures 23.8 x 72.1 x 31.0 in, and connects on 2" NPT water and 1" NPT gas fittings. Venting is 4" PVC, CPVC, approved polypropylene or approved stainless steel (or 4" special gas vent Type BH, Class III A/B/C) in a forced-draft direct-vent arrangement, with the series page stating venting up to 150 ft; the product pages print a 12–160 PSI water pressure range, and the stainless fire-tube heat exchanger sits in a cold-rolled carbon steel casing.

Best suited to

  • Commercial hydronic plants whose load calculation lands between 40 and 599 MBH
  • Projects that want the NFB700-500C's footprint and minimum fire with 100 MBH more ceiling
  • Floor-standing installations that will later be cascaded (up to 8 units per the series page)

Applicability and support

Model number
NFB700-600C
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Navien. Units are shown with every value; notes flag conflicting sources or missing figures.

Navien NFB700-600C specifications
SpecificationValueNote
Input
Input, minimum40 MBHPer the product page.
Input, maximum599 MBHPer the product page.
Output
Heating capacity584 MBHPer the product page.
Net AHRI water rating508 MBHNet AHRI based on a piping and pickup allowance of 1.15, per the product page.
Efficiency
Thermal efficiency97.5 %As printed on the product page (DOE test basis); the page labels the row "Thermal Efficiency", not AFUE.
Venting and air
Venting4" PVC, CPVC, approved polypropylene or approved stainless steel, or 4" special gas vent Type BH (Class III A/B/C)Forced-draft direct vent per the product page; the series page states venting up to 150 ft.
Physical and connections
Weight622 lb622 lb dry; 843 lb with water, per the product page.
Width23.8 in
Height72.1 in
Depth31 in
Water content26.5 galPer the product page.
Heating water connections2" NPTPer the product page.
Gas connection1" NPTPer the product page.
Operating limits and other
FuelNatural gas or propaneRatings are the same for natural-gas models converted to propane use, per the product page; the series ships with a propane conversion kit.
Water pressure rating12 – 160 psi12–160 PSI water pressure range printed on the NFB700-C product pages.
Altitude rating10,100 ftPer the NFB700-C series page.

Manuals

    Alerts documented for this model

    None documented yet.

    Services

    Frequently asked questions

    What is the input range of the NFB700-600C?

    40 to 599 MBH, per the product page, with a 584 MBH heating capacity and a 508 MBH net AHRI water rating at 97.5% thermal efficiency.

    Is the NFB700-600C bigger than the NFB700-500C?

    No. Both models weigh 622 lb dry (843 lb with water), measure 23.8 x 72.1 x 31.0 in and hold 26.5 gallons; only the firing ceiling, capacity and net AHRI ratings differ.

    What venting does the NFB700-600C use?

    4" PVC, CPVC, approved polypropylene or approved stainless steel, or 4" special gas vent Type BH (Class III A/B/C), per the product page; the series page states venting up to 150 ft.

    Questions about the Navien NFB700-600C?

    Describe what the boiler is doing and get a straight answer about the next step.

    On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

    Sources and verification

    Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

    CallEmailEstimate