Navien NFB700-C Commercial Boiler

The NFB700-C is Navien's floor-standing commercial condensing fire-tube boiler series for Canada — its first floor-standing line — with the NFB700-500C, 600C, 800C and 1000C firing from 40 to 999 MBH at a printed 97.5% thermal efficiency, up to 15:1 turndown and a 160 PSI working pressure rating.

Current seriesSold in CanadaNatural gasPropanecommercial

Series facts

Type
condensing
Efficiency
97.5% thermal-efficiency
Fuel
Natural gas or propane; each NFB700-C unit ships with a propane conversion kit per the series page.
Venting
Venting up to 150 ft in PVC, CPVC, approved polypropylene or approved stainless steel per the series page, with 4" (NFB700-500C/600C) or 6" (NFB700-800C/1000C) sizes and special gas vent Type BH (Class III A/B/C) options; common venting for up to 4 units.
Models documented
4
Warranty
Not verified

97.5% thermal efficiency per the NFB700-C series and product pages, which print a "Thermal Efficiency" row (DOE test basis), not AFUE.

About the NFB700-C Commercial Boiler

The NFB700-C is Navien's first floor-standing boiler series, sold for commercial work and marked "New NFB700-C Series" on the Canadian site: four models from the NFB700-500C to the NFB700-1000C fire 40 to 999 MBH at a printed 97.5% thermal efficiency, with the series page claiming turndown ratios up to 15:1, cascades of up to 8 units and common venting of up to 4 units.

The series page rates the line at 160 PSI maximum allowable working pressure with ASME "H"-stamped construction, states CSA, AHRI and SCAQMD certification plus Energy Star certification, and claims low-NOx combustion below 20 ppm under SCAQMD Rule 1146.2. The stainless fire-tube heat exchangers sit in cold-rolled carbon steel casings, and each unit ships with a propane conversion kit and a high-elevation kit, per the series page.

Controls are a 10.1" colour touch display with Wi-Fi and a mobile app, a Startup Wizard, and low-water cutoff, flame rod, ignition detector, water and exhaust high-limit sensors and high and low gas pressure switches per the series copy. The series runs on 120 VAC/60 Hz drawing under 12 A, is rated to 10,100 ft altitude, and the Canadian products grid lists the NFB700-C under Commercial → Boilers; model-page badges print "Residential/Commercial".

Highlights

  • Floor-standing commercial fire-tube condensing line: NFB700-500C through NFB700-1000C
  • 97.5% thermal efficiency printed on the pages
  • 40 to 999 MBH input; turndown up to 15:1 per the series page
  • 160 PSI maximum allowable working pressure; ASME "H"-stamped
  • Low NOx below 20 ppm (SCAQMD Rule 1146.2 claim); Energy Star certified
  • Cascade up to 8 units; common vent up to 4 units; venting to 150 ft

Models

NFB700-C Commercial Boiler models

One canonical page per model with input, output and efficiency kept separate.

CurrentSold in Canada
Input
40–499 MBH
Output (max)
—
AFUE
—

The Navien NFB700-500C is the entry model of the floor-standing NFB700-C commercial boiler series: 40 to 499 MBH of input with a 487 MBH heating capacity and a 423 MBH net AHRI water rating at 97.5% thermal efficiency.

Natural gasPropaneHeating-only
CurrentSold in Canada
Input
40–599 MBH
Output (max)
—
AFUE
—

The Navien NFB700-600C steps the floor-standing NFB700-C line to 40 to 599 MBH of input with a 584 MBH heating capacity and a 508 MBH net AHRI water rating at 97.5% thermal efficiency, in the same 622 lb cabinet as the 500C.

Natural gasPropaneHeating-only
CurrentSold in Canada
Input
66–799 MBH
Output (max)
—
AFUE
—

The Navien NFB700-800C is the third size of the floor-standing NFB700-C commercial boiler series: 66 to 799 MBH of input with a 779 MBH heating capacity and a 677 MBH net AHRI water rating at 97.5% thermal efficiency, in the larger 750 lb cabinet.

Natural gasPropaneHeating-only
CurrentSold in Canada
Input
66–999 MBH
Output (max)
—
AFUE
—

The Navien NFB700-1000C is the top model of the floor-standing NFB700-C commercial boiler series: 66 to 999 MBH of input with a 974 MBH heating capacity at 97.5% thermal efficiency, in the same 750 lb cabinet as the 800C.

Natural gasPropaneHeating-only

Compare models in this series

Comparison of Navien NFB700-500C and Navien NFB700-600C and Navien NFB700-800C and Navien NFB700-1000C
SpecificationNavien NFB700-500CNavien NFB700-600CNavien NFB700-800CNavien NFB700-1000C
Input, minimum40 MBH40 MBH66 MBH66 MBH
Input, maximum499 MBH599 MBH799 MBH999 MBH
output-max————
afue————
turndown————
vent-max-3————
vent-max-2————
Weight622 lb622 lb750 lb750 lb

Read the full comparison: Navien NFB700-500C vs NFB700-600C →

Read the full comparison: Navien NFB700-600C vs NFB700-800C →

Read the full comparison: Navien NFB700-800C vs NFB700-1000C →

Read the full comparison: Navien NFB700-500C vs Navien NFB700-800C →

Error codes and alerts

NFB700-C Commercial Boiler alerts

No alerts documented for this series yet.

Manuals

Official documents

    Where ROMA provides on-site service

    On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

    See all service areas

    Frequently asked questions

    Which models make up the NFB700-C series?

    Four floor-standing models: the NFB700-500C (40–499 MBH), NFB700-600C (40–599 MBH), NFB700-800C (66–799 MBH) and NFB700-1000C (66–999 MBH), all printed at 97.5% thermal efficiency.

    What is the maximum working pressure of the NFB700-C?

    The series page rates the NFB700-C at 160 PSI maximum allowable working pressure, with ASME "H"-stamped construction and stainless fire-tube heat exchangers.

    Does the NFB700-C ship ready for propane?

    The series page states each unit ships with a propane conversion kit and a high-elevation kit, and the product pages note ratings are the same for natural-gas models converted to propane use.

    Talk to a boiler technician

    Describe what the boiler is doing and get a straight answer about the next step.

    On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

    Sources and verification