Navien · NFC-H Fire-Tube Combi
Navien NFC-250/200H
The Navien NFC-250/200H is the top NFC-H fire-tube combi: 13.3 to 199.9 MBH heating input with DHW input to 210,000 BTU/h, 95.0% AFUE and 7.9 GPM DHW flow at a 45°F rise, in the same 141 lb cabinet as the 175H.
Key figures
- Max input
- 199.9 MBH
- Max CSA output
- —
- AFUE
- 95 %
- Min input
- 13.3 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Navien NFC-250/200H in practice
The NFC-250/200H is the only Navien residential fire-tube combi whose heating input reaches the 199,900 BTU/h ceiling of the Canadian H-series line, firing from the same 13,300 BTU/h minimum as the NFC-250/175H. For a large home or a small multi-suite building whose heat-loss calculation crosses 175 MBH, this is the NFC-H size that adds the headroom.
The DHW side matches the 175H — up to 210,000 BTU/h with 7.9 GPM of flow published at a 45°F rise — and the cabinet, weight and venting are identical at 17.3 x 17.3 x 33.5 in, 141 lb and 2" or 3" pipe to 65 or 150 equivalent feet. Rated 95.0% AFUE with 6 to 80 psi system pressure, it is physically the same appliance as the 175H with a higher firing ceiling.
Best suited to
- Large homes and small multi-suite buildings needing heating input beyond 175 MBH
- Households wanting fire-tube combi DHW reach with 200-class heating headroom
- Projects where one wall-hung appliance must cover a heavy heating load and on-demand hot water
Applicability and support
- Model number
- NFC-250/200H
- Canadian availability
- available
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Not verified
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Navien. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Heating input, minimum | 13.3 MBH | Space-heating input. |
| Heating input, maximum | 199.9 MBH | Space-heating input. |
| Efficiency | ||
| Efficiency (AFUE) | 95 % | 95.0% AFUE per the installation manual. |
| Domestic hot water | ||
| DHW input, maximum | 210 MBH | 210,000 BTU/h |
| DHW flow at 45°F rise | 7.9 GPM | Both NFC-H models, per the installation manual. |
| Domestic hot water | Integrated in the combi heat exchanger | |
| Venting and air | ||
| Venting | PVC, CPVC or approved polypropylene; 2" or 3" | Canada: plastic venting must meet ULC S636 where required. |
| Max. equivalent vent length, 2" | 65 ft | |
| Max. equivalent vent length, 3" | 150 ft | |
| Physical and connections | ||
| Weight | 141 lb | 64 kg; 170 lb (77 kg) with water. |
| Width | 17.3 in | |
| Height | 33.5 in | |
| Depth | 17.3 in | |
| Gas connection | 3/4" NPT | |
| Heating water connections | 1" NPT | |
| Operating limits and other | ||
| Fuel | Natural gas or propane | Separate Navien ratings per fuel. |
| Altitude rating | 10,100 ft | Per installation manual. |
| System water pressure | 6 – 80 psi | |
Manuals
Alerts documented for this model
Frequently asked questions
What is the input range of the NFC-250/200H?
13,300 to 199,900 BTU/h for space heating and up to 210,000 BTU/h for DHW, per the installation manual, at 95.0% AFUE.
How does the NFC-250/200H differ from the NFC-250/175H?
Only the heating ceiling differs: 199.9 MBH against 175 MBH. Both models weigh 141 lb, share the 17.3 x 17.3 x 33.5 in cabinet, fire down to 13.3 MBH and draw up to 210,000 BTU/h for DHW.
Is the NFC-250/200H available in Canada?
Yes. Navien Canada lists the NFC-250/200H on its NFC-H series page. Whether it is supplied for your project is confirmed at consultation.
Questions about the Navien NFC-250/200H?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Sources and verification
- Navien Canada — NFC-H series · accessed September 7, 2026
- NFC-H Series Installation Manual (EN) · accessed September 7, 2026
- NFC-H Service Manual, Ver 1.0 (Jan 2021) · Ver 1.0 · accessed September 7, 2026
Facts checked September 7, 2026. Last updated September 7, 2026. Technical reviewer: not yet assigned.