Skip to content
Boilers.caby ROMA Heating & Cooling

Raypak · XTherm

Raypak XTherm H7-1005A

The Raypak XTherm H7-1005A is a vertical modulating condensing commercial hydronic boiler rated 999 MBTUH input and 959 MBTUH output at 96% thermal efficiency, with 7:1 turndown, Category IV venting and a 6 in flue.

CurrentCanadian status unknown

Key figures

Max input
999 MBH
Max CSA output
959 MBH
AFUE
Min input
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Raypak XTherm H7-1005A in practice

The H7-1005A is the 999 MBTUH size of Raypak's XTherm vertical modulating condensing line, which pairs a finned copper tube primary heat exchanger with a stainless steel condensing section. The official submittal prints 999 MBTUH input, 959 MBTUH output and 96% thermal efficiency at full rate, with 7:1 turndown, a 6 in flue, a 6 in combustion-air intake, a 1-1/4" NPT gas connection and 1,065 lb approximate shipping weight.

The XTherm line is documented by I&O manual 241513 for the 1005A-2005A sizes and 241549 for the 3005-4005 sizes, each with a French edition, and the ratings above come from submittals 241869 and 241868. The units run the VERSA IC modulating controller with a 7 in colour touchscreen, Raymote connectivity and cascade up to eight heaters, and vent as Category IV condensing appliances.

Best suited to

  • Commercial hydronic loads near 999 MBTUH input
  • Plants wanting a vertical modulating condensing boiler with copper-fin primary and stainless condensing sections
  • Cascade installations up to eight heaters on the VERSA IC control

Applicability and support

Model number
H7-1005A
Canadian availability
unknown
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Raypak. Units are shown with every value; notes flag conflicting sources or missing figures.

Raypak XTherm H7-1005A specifications
SpecificationValueNote
Input
Input999 MBHRated input 999 MBTUH printed in the 241869 product submittal.
Output
Output959 MBHRated output 959 MBTUH printed in the same submittal.
Efficiency
AHRI thermal efficiency96 %96% thermal efficiency at full rate per the XTherm product page and the 241869/241868 submittals.
Venting and air
Venting categoryCategory IVCondensing Category IV venting per the product page model data.
Flue outlet6 inFlue diameter per the submittal.
Combustion air intake6 inCombustion-air intake diameter per the submittal.
Physical and connections
Gas connection1-1/4" NPTGas connection (natural gas) per the 241869 submittal; the submittal notes propane models use a 1 in NPT connection.
Weight1,065 lbApproximate shipping weight 1,065 lb printed in the submittal.
Electrical
Electrical120 VAC, 1-phaseOperating voltage from the product page model data.
Operating limits and other
Turndown7:1Turndown printed for H7-1005A in the submittal and product page model data.
Maximum water flow70 GPMMaximum water flow from the product page model data.
CascadeUp to 8 boilersVERSA IC control with cascade up to 8 heaters, no external sequencer, per the submittal.
FuelNatural gas or propaneNatural gas or propane; the 241869/241868 submittals print propane connection sizes separately.

Frequently asked questions

What are the XTherm H7-1005A ratings?

The official submittal prints 999 MBTUH input, 959 MBTUH output and 96% thermal efficiency at 7:1 turndown.

Which XTherm manual covers the H7-1005A?

Raypak publishes I&O 241513 for this size group, in English and French, with the matching product submittal for the rating table.

Is the XTherm condensing?

Yes. Raypak lists the XTherm under its condensing hydronic boilers; the submittal describes a finned copper tube exchanger combined with a stainless steel condensing exchanger.

Questions about the Raypak XTherm H7-1005A?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate