Raypak XTherm H7-3505

The Raypak XTherm H7-3505 is a vertical modulating condensing commercial hydronic boiler rated 3,500 MBTUH input and 3,360 MBTUH output at 96% thermal efficiency, with 10:1 turndown, Category IV venting and a 10 in flue.

CurrentCanadian status unknown

Key figures

Max input
3,500 MBH
Max CSA output
3,360 MBH
AFUE
—
Min input
—
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Raypak XTherm H7-3505 in practice

The H7-3505 is the 3,500 MBTUH size of Raypak's XTherm vertical modulating condensing line, which pairs a finned copper tube primary heat exchanger with a stainless steel condensing section. The official submittal prints 3,500 MBTUH input, 3,360 MBTUH output and 96% thermal efficiency at full rate, with 10:1 turndown, a 10 in flue, a 12 in combustion-air intake and 2,925 lb approximate shipping weight.

The XTherm line is documented by I&O manual 241513 for the 1005A-2005A sizes and 241549 for the 3005-4005 sizes, each with a French edition, and the ratings above come from submittals 241869 and 241868. The units run the VERSA IC modulating controller with a 7 in colour touchscreen, Raymote connectivity and cascade up to eight heaters, and vent as Category IV condensing appliances.

Best suited to

  • Commercial hydronic loads near 3,500 MBTUH input
  • Plants wanting a vertical modulating condensing boiler with copper-fin primary and stainless condensing sections
  • Cascade installations up to eight heaters on the VERSA IC control

Applicability and support

Model number
H7-3505
Canadian availability
unknown
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Raypak. Units are shown with every value; notes flag conflicting sources or missing figures.

Raypak XTherm H7-3505 specifications
SpecificationValueNote
Input
Input3,500 MBHRated input 3,500 MBTUH printed in the 241868 product submittal.
Output
Output3,360 MBHRated output 3,360 MBTUH printed in the same submittal.
Efficiency
AHRI thermal efficiency96 %96% thermal efficiency at full rate per the XTherm product page and the 241869/241868 submittals.
Venting and air
Venting categoryCategory IVCondensing Category IV venting per the product page model data.
Flue outlet10 inFlue diameter per the submittal.
Combustion air intake12 inCombustion-air intake diameter per the submittal.
Physical and connections
Weight2,925 lbApproximate shipping weight 2,925 lb printed in the submittal.
Water content26.9 galWater content 26.9 gal printed in the 241868 submittal.
Heat transfer surface399 sq ftPrimary heat transfer surface printed in the 241868 submittal.
Electrical
Electrical208-240 VAC, 1-phaseOperating voltage from the product page model data.
Operating limits and other
Turndown10:1Turndown printed for H7-3505 in the submittal and product page model data.
Maximum water flow208 GPMMaximum water flow from the product page model data.
CascadeUp to 8 boilersVERSA IC control with cascade up to 8 heaters, no external sequencer, per the submittal.
FuelNatural gas or propaneNatural gas or propane; the 241869/241868 submittals print propane connection sizes separately.

Frequently asked questions

What are the XTherm H7-3505 ratings?

The official submittal prints 3,500 MBTUH input, 3,360 MBTUH output and 96% thermal efficiency at 10:1 turndown.

Which XTherm manual covers the H7-3505?

Raypak publishes I&O 241549 for this size group, in English and French, with the matching product submittal for the rating table.

Is the XTherm condensing?

Yes. Raypak lists the XTherm under its condensing hydronic boilers; the submittal describes a finned copper tube exchanger combined with a stainless steel condensing exchanger.

Questions about the Raypak XTherm H7-3505?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate