Burnham Alpine ALP105B vs ALP150B

Verdict in brief

The ALP105B and ALP150B are both 95.0% AFUE Alpines, but the 150B steps input from 105 to 150 MBH maximum (DOE capacity 96 to 136 MBH, net AHRI 83 to 118 MBH), loses the 2" vent option — 3" only, vent side limited to 100 ft against the 105B's 135 ft — and gains 27 lb of shipping weight.

Side by side

Published manufacturer figures. Input and output are kept separate; blanks mean the manufacturer did not publish that value.

Comparison of Burnham Alpine ALP105B and Burnham Alpine ALP150B
SpecificationBurnham Alpine ALP105BBurnham Alpine ALP150B
Input, minimum21 MBH30 MBH
Input, maximum105 MBH150 MBH
DOE heating capacity96 MBH136 MBH
Net AHRI water rating83 MBH118 MBH
Efficiency (AFUE)95 %95 %
Vent connection3" CPVC/PVC (optional 2" reduced-length build)3" CPVC/PVC
Shipping weight155 lb182 lb
Gas connection1/2" FPT1/2" FPT
Supply/return connections1" FPT1" FPT
Domestic hot waterHeating-only boiler — domestic hot water comes from a separate indirect tank or water heaterHeating-only boiler — domestic hot water comes from a separate indirect tank or water heater

What actually separates them

Both are 95.0% AFUE condensing Alpines with the stainless steel coil heat exchanger, Sage2.X outdoor-reset control, 5:1 modulation and identical NG/LP inputs; both connect on 1/2" FPT gas and 1" FPT supply/return.

The 150B lifts the maximum input from 105 to 150 MBH (minimum rises 21 to 30 MBH), and the ratings table prints 136 MBH DOE heating capacity and a 118 MBH net AHRI rating against the 105B's 96 and 83 MBH.

Venting separates them in the mechanical room: the 150B is 3" only — 135 ft maximum equivalent intake but 100 ft vent — while the 105B keeps the reduced 2" option to 60 ft alongside 135 ft in 3". Weight rises from 155 to 182 lb shipping.

CurrentCanadian status unknown
Input
21–105 MBH
Output (max)
—
AFUE
95 %

The Burnham Alpine ALP105B fires 21 to 105 MBH input at 95.0% AFUE — 96 MBH DOE heating capacity and an 83 MBH net AHRI rating — in the wall-hung or floor-standing Alpine chassis, with the same 3" venting (2" option) as the ALP080B.

Natural gasPropaneHeating-only
CurrentCanadian status unknown
Input
30–150 MBH
Output (max)
—
AFUE
95 %

The Burnham Alpine ALP150B is the mid-size Alpine: 30 to 150 MBH input at 95.0% AFUE with 136 MBH DOE heating capacity and a 118 MBH net AHRI rating, wall-hung or floor-standing at 182 lb, vented in 3" pipe to 135 ft intake / 100 ft vent.

Natural gasPropaneHeating-only

Frequently asked questions

Can the ALP150B vent in 2" pipe?

No. The 150B vents in 3" only, to 135 ft maximum equivalent intake and 100 ft maximum equivalent vent; the 2" reduced option exists only on the 080B and 105B.

What does the ALP150B add over the ALP105B?

Maximum input rises from 105 to 150 MBH, DOE heating capacity from 96 to 136 MBH and net AHRI from 83 to 118 MBH, at 182 lb shipping weight versus 155 lb.

Are both rated 95% AFUE?

Yes — 95.0% AFUE for both, per the Alpine I&O ratings table.

Not sure which one fits your home?

A consultation includes a heat-loss review so the size is right the first time.