Skip to content
Boilers.caby ROMA Heating & Cooling

Comparison

IBC SL 26-260 G3 vs SL 40-399 G3

Verdict in brief

The SL 26-260 G3 and SL 40-399 G3 are IBC's two commercial SL G3 boilers. The 399 roughly doubles the output ceiling (383 vs 239 MBH), raises operating pressure from 30 to 80 psig and moves to a 4" flue, but the 260 is rated by AFUE at 95% while the 399 carries 96% combustion and 96% thermal efficiency.

Side by side

Published manufacturer figures. Input and output are kept separate; blanks mean the manufacturer did not publish that value.

Comparison of IBC SL 26-260 G3 and IBC SL 40-399 G3
SpecificationIBC SL 26-260 G3IBC SL 40-399 G3
CSA input, minimum26 MBH40 MBH
CSA input, maximum260 MBH399 MBH
CSA output, minimum24.9 MBH38.4 MBH
CSA output, maximum239 MBH383 MBH
Efficiency (AFUE)95 %—
Thermal efficiency (ANSI/AHRI-1500)—96 %
Power use at full fire (less pumps)127 W190 W
Weight (empty)162 lb240 lb
Max. operating water pressure30 psig80 psig
Max. equivalent vent length, each side200 ft200 ft
Water connections1 1/2" NPT-M1 1/2" NPT-M
Domestic hot waterHeating boiler; IBC lists DHW opt-out priority for multi-boiler systemsHeating boiler; IBC lists DHW opt-out priority for multi-boiler systems

What actually separates them

Both models are wall-hung condensing boilers on the V-10 controller with BACnet, up to four zone pumps, DDC 0-10 VDC / 4-20 mA, the same 1 1/2" NPT-M water connections and the same 200 equivalent feet of vent per side. The difference is scale: the 260 covers 26–260 MBH input and 24.9–239 MBH output, while the 399 covers 40–399 MBH input and 38.4–383 MBH output.

Efficiency is published on different bases. IBC rates the 26-260 G3 at 95% AFUE and the 40-399 G3 at 96% combustion and 96% thermal efficiency to ANSI/AHRI-1500, with no AFUE for the larger model. The 399's higher 80 psig operating-pressure rating (against 30 psig on the 260) also suits taller or higher-pressure systems.

Installation differences follow the size: the 260 vents 3" and weighs 162 lb (74 kg), the 399 vents 4" and weighs 240 lb (110 kg), and the 399 offers an optional 316Ti titanium heat exchanger. In a multi-boiler plant, IBC states up to 24 units and 9.5 MMBtu/h with 240:1 turndown at 24 x 399.

IBC Technologies

IBC SL 26-260 G3

CurrentSold in Canada
Input
26–260 MBH
Output (max)
239 MBH
AFUE
95 %

The IBC SL 26-260 G3 is the smaller of IBC's two commercial SL G3 boilers: 26 to 260 MBH CSA input, 24.9 to 239 MBH CSA output, 95% AFUE, 3" venting to 200 equivalent feet per side and 1 1/2" NPT-M water connections.

Natural gasPropaneHeating-only

IBC Technologies

IBC SL 40-399 G3

CurrentSold in Canada
Input
40–399 MBH
Output (max)
383 MBH
AFUE
—

The IBC SL 40-399 G3 is the larger commercial SL G3 boiler: 40 to 399 MBH CSA input, 38.4 to 383 MBH output, 96% combustion and 96% thermal efficiency, 4" venting to 200 equivalent feet and an optional 316Ti titanium heat exchanger.

Natural gasPropaneHeating-only

Frequently asked questions

Which SL G3 commercial model is more efficient?

The 40-399 G3 is rated 96% combustion and 96% thermal efficiency; the 26-260 G3 is rated 95% AFUE. The two figures use different test bases, so IBC publishes them separately.

Do both models vent the same?

No. The 260 uses 3" venting and the 399 uses 4", each allowed 200 equivalent feet per side with direct-vent or indoor air supply.

Does the 399 have any options the 260 does not?

Yes. IBC lists an optional 316Ti titanium-enhanced heat exchanger for the SL 40-399 G3.

Not sure which one fits your home?

A consultation includes a heat-loss review so the size is right the first time.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate