IBC Technologies · SL Series G3 Commercial

IBC SL 26-260 G3

The IBC SL 26-260 G3 is the smaller of IBC's two commercial SL G3 boilers: 26 to 260 MBH CSA input, 24.9 to 239 MBH CSA output, 95% AFUE, 3" venting to 200 equivalent feet per side and 1 1/2" NPT-M water connections.

CurrentSold in Canada

Key figures

Max input
260 MBH
Max CSA output
239 MBH
AFUE
95 %
Min input
26 MBH
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

IBC SL 26-260 G3 in practice

The SL 26-260 G3 is a wall-hung condensing boiler rated 26–260 MBH CSA input (7.6–76.2 kW) with 24.9–239 MBH output (7.31–70.0 kW) at 95% AFUE. It shares the commercial SL G3 chassis, V-10 touchscreen controller and BACnet connectivity with the larger SL 40-399 G3, and IBC covers both in the commercial I&O manual 120-270E12.

At 162 lb (74 kg) and with 1 1/2" NPT-M water connections, the 260 is the lighter of the two commercial models and vents in 3" Schedule 40 or rigid PPs to 200 equivalent feet per side, with direct-vent or indoor air supply. Its pressure vessel holds 4.64 USG (17.6 L), the maximum boiler flow is 25 USgpm (95 Lpm) and it is rated 30 psig maximum operating pressure with a 30 psig relief valve supplied.

IBC's commercial feature set applies: up to 24-boiler networks and 9.5 MMBtu/h without additional controls, up to four zone pumps, DDC 0-10 VDC or 4-20 mA, MFZ moisture management, reverse-flow detection and an up-to-10-year commercial heat-exchanger warranty. The 260 is heating-only; IBC lists DHW opt-out priority for multi-boiler systems rather than an integrated DHW coil.

Best suited to

  • Light-commercial buildings and large homes whose load fits 24.9–239 MBH output
  • Multi-boiler plants starting with one SL 26-260 G3 and expanding up to a 24-boiler network
  • Mechanical rooms where 3" venting to 200 equivalent feet per side is available

Applicability and support

Model number
SL 26-260G3
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Series terms

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by IBC Technologies. Units are shown with every value; notes flag conflicting sources or missing figures.

IBC SL 26-260 G3 specifications
SpecificationValueNote
Input
CSA input, minimum26 MBH7.6 kW
CSA input, maximum260 MBH76.2 kW
Output
CSA output, minimum24.9 MBH7.31 kW
CSA output, maximum239 MBH70.0 kW
Efficiency
Efficiency (AFUE)95 %95% AFUE per IBC's commercial specification table.
Domestic hot water
Domestic hot waterHeating boiler; IBC lists DHW opt-out priority for multi-boiler systems
Venting and air
Flue material3" Schedule 40 / rigid PPsIBC's page also lists PVC/CPVC/PPs approval.
Max. equivalent vent length, each side200 ft
Air intakeDirect vent or indoor supply
Physical and connections
Weight (empty)162 lb74 kg
Heating surface area22.71 ft² / 2.11 m²
Pressure vessel water content4.64 USG / 17.6 L
Water connections1 1/2" NPT-M
Gas connection3/4" NPT-F
Relief valve & air vent3/4" NPT-F
Condensate connection3/4" hose
Electrical
Power use at full fire (less pumps)127 W120 V / 60 Hz.
Operating limits and other
Maximum boiler flow rate25 USgpm / 95 Lpm
Minimum boiler flow rate6 USgpm / 23 Lpm
Max. operating water pressure30 psig206 kPa; ships with a 30 psig pressure relief valve.
Minimum water pressure8 psig55 kPa.
FuelNatural gas or propaneCSA input is rated for natural gas or propane on IBC's commercial specification table.
Gas supply pressure4 – 14 in. w.c.
Ambient temperature32 – 122 °F0 – 50°C.
Minimum water temperature34 °F1°C.
Max. water temperature (electronic hi-limit)190 °F88°C; lockout limit 201°F / 94°C.
Max. ΔT supply/return40 °F22°C electronic fence.
Altitude rating0 – 12,000 ft3,658 m ASL.

Frequently asked questions

What input and output does the SL 26-260 G3 cover?

26–260 MBH CSA input (7.6–76.2 kW) and 24.9–239 MBH CSA output (7.31–70.0 kW) per IBC's commercial specification table.

Does the SL 26-260 G3 make domestic hot water?

It is a heating boiler. IBC lists DHW opt-out priority for multi-boiler systems, and the captured commercial pages do not document an integrated DHW coil.

What venting does the 260 use?

3" Schedule 40 or rigid PPs, 200 equivalent feet per side, with direct-vent or indoor air supply; IBC's page also lists PVC/CPVC/PPs approval.

Questions about the IBC SL 26-260 G3?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate