IBC Technologies · SL Series G3 Commercial

IBC SL 40-399 G3

The IBC SL 40-399 G3 is the larger commercial SL G3 boiler: 40 to 399 MBH CSA input, 38.4 to 383 MBH output, 96% combustion and 96% thermal efficiency, 4" venting to 200 equivalent feet and an optional 316Ti titanium heat exchanger.

CurrentSold in Canada

Key figures

Max input
399 MBH
Max CSA output
383 MBH
AFUE
Min input
40 MBH
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

IBC SL 40-399 G3 in practice

The SL 40-399 G3 covers 40–399 MBH CSA input (11.7–117 kW) and 38.4–383 MBH output (11.2–112 kW). IBC rates it at 96% combustion efficiency and 96% thermal efficiency to ANSI/AHRI-1500; no AFUE is published for this size. It is documented with the SL 26-260 G3 in the commercial I&O manual 120-270E12.

The 399 carries a 4" flue and 4" combustion-air connection, both Schedule 40, with 200 equivalent feet per side and direct-vent or indoor air supply. It weighs 240 lb (110 kg) empty, holds 6.66 USG (25.2 L) and accepts up to 45 USgpm (170 Lpm) with a 20 USgpm (76 Lpm) minimum. Maximum operating pressure is 80 psig (551 kPa), and IBC supplies a 30 psig relief valve.

An optional 316Ti titanium-enhanced heat exchanger is available on this model; the commercial specification table covers the standard and Ti versions in one column. Network features match the rest of the commercial SL G3 line: up to 24 boilers and 9.5 MMBtu/h, 240:1 turndown at 24 x 399, four zone pumps, DDC 0-10 VDC or 4-20 mA and an up-to-10-year commercial heat-exchanger warranty.

Best suited to

  • Commercial buildings needing up to 383 MBH output from one wall-hung boiler
  • Plants planning a 24-boiler, 9.5 MMBtu/h network
  • Projects specifying the optional titanium heat exchanger for the 399

Applicability and support

Model number
SL 40-399G3
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Series terms

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by IBC Technologies. Units are shown with every value; notes flag conflicting sources or missing figures.

IBC SL 40-399 G3 specifications
SpecificationValueNote
Input
CSA input, minimum40 MBH11.7 kW
CSA input, maximum399 MBH117 kW
Output
CSA output, minimum38.4 MBH11.2 kW
CSA output, maximum383 MBH112 kW
Efficiency
Combustion efficiency96 %No AFUE is published for this model.
Thermal efficiency (ANSI/AHRI-1500)96 %
Domestic hot water
Domestic hot waterHeating boiler; IBC lists DHW opt-out priority for multi-boiler systems
Venting and air
Flue material4" Schedule 40 / rigid PPsIBC's page also lists PVC/CPVC/PPs approval.
Max. equivalent vent length, each side200 ft
Air intakeDirect vent or indoor supply
Physical and connections
Weight (empty)240 lb110 kg
Heating surface area36.56 ft² / 3.40 m²
Pressure vessel water content6.66 USG / 25.2 L
Water connections1 1/2" NPT-M
Gas connection3/4" NPT-F
Relief valve & air vent3/4" NPT-F
Condensate connection3/4" hose
Electrical
Power use at full fire (less pumps)190 W120 V / 60 Hz.
Operating limits and other
Heat exchanger optionOptional 316Ti titanium-enhanced heat exchangerIBC lists the SL 40-399 G3 Ti as an option in the same specification-table column as the standard 40-399.
Maximum boiler flow rate45 USgpm / 170 Lpm
Minimum boiler flow rate20 USgpm / 76 Lpm
Max. operating water pressure80 psig551 kPa; ships with a 30 psig pressure relief valve.
Minimum water pressure8 psig55 kPa.
FuelNatural gas or propaneCSA input is rated for natural gas or propane on IBC's commercial specification table.
Gas supply pressure4 – 14 in. w.c.
Ambient temperature32 – 122 °F0 – 50°C.
Minimum water temperature34 °F1°C.
Max. water temperature (electronic hi-limit)190 °F88°C; lockout limit 201°F / 94°C.
Max. ΔT supply/return40 °F22°C electronic fence.
Altitude rating0 – 12,000 ft3,658 m ASL.

Frequently asked questions

Is the SL 40-399 G3 rated by AFUE?

No. IBC publishes 96% combustion and 96% thermal efficiency (ANSI/AHRI-1500) for this model; 95% AFUE is published for the smaller SL 26-260 G3.

What is the titanium option?

IBC lists an optional 316Ti titanium-enhanced heat exchanger for the SL 40-399 G3. The commercial specification table presents the standard and Ti versions in the same column.

How much vent can the 399 use?

200 equivalent feet of 4" Schedule 40 or rigid PPs per side, with direct-vent or indoor air supply.

Questions about the IBC SL 40-399 G3?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.