Lochinvar Crest FCB1000
- Input
- 50–999 MBH
- Output (max)
- —
- AFUE
- —
The Crest with Hellcat FCB1000 opens the FCB line at 50 to 999 MBH input with 961 MBH gross output and an 834 MBH AHRI net rating, on 3" pipe with 6" air and vent.
Canada-wide gas boiler information · On-site service in Greater Vancouver, BC
Boilers.ca is a brand of ROMA Heating & Cooling · Licensed gas contractor LGA0202903
Comparison
Verdict in brief
The Crest with Hellcat FCB1000 and FCB1500 are the two smallest Hellcat boilers: the 1500 fires 60 to 1500 MBH with 1443 MBH gross output, stepping the pipe to 4" with 1-1/2" gas and 8" air/vent, against the 1000's 3" pipe, 1-1/4" gas and 6" openings.
Published manufacturer figures. Input and output are kept separate; blanks mean the manufacturer did not publish that value.
| Specification | Lochinvar Crest FCB1000 | Lochinvar Crest FCB1500 |
|---|---|---|
| Heating input, minimum | 50 MBH | 60 MBH |
| Heating input, maximum | 999 MBH | 1,500 MBH |
| Gross output | 961 MBH | 1,443 MBH |
| Net AHRI water rating | 834 MBH | 1,252 MBH |
| Water content | 77 gal | 94 gal |
| Pipe outlet connection | 3" | 4" |
| Pipe inlet connection | 3" | 4" |
| Gas connection | 1-1/4" | 1-1/2" |
| Air size | 6" | 8" |
| Vent size | 6" | 8" |
| Weight with water | 1,838 lb | 2,307 lb |
Both are Crest wave fire-tube boilers with the Hellcat combustion system — RealTime O2 Trim combustion and the full-color 10" capacitive touchscreen — vented as room air/direct vent or common vent to 150 equivalent feet.
The 1500 is the first FCB size on 4" pipe: against the 1000's 3" outlet/inlet and 1-1/4" gas, it uses 4" pipe with a 1-1/2" gas inlet, and air and vent step from 6" to 8". Minimum fires are close (50 and 60 MBH).
Capacity rises from 999 to 1500 MBH of input with gross output from 961 to 1443 MBH and the AHRI net rating from 834 to 1252 MBH. Water content grows from 77 to 94 gallons and weight with water from 1,838 to 2,307 lb per the ratings table.
Lochinvar
The Crest with Hellcat FCB1000 opens the FCB line at 50 to 999 MBH input with 961 MBH gross output and an 834 MBH AHRI net rating, on 3" pipe with 6" air and vent.
Lochinvar
The Crest with Hellcat FCB1500 fires 60 to 1500 MBH with 1443 MBH gross output and a 1252 MBH AHRI net rating, stepping the Hellcat line to 4" pipe and 8" air and vent.
The pipe connections step from 3" to 4", the gas inlet from 1-1/4" to 1-1/2" and air and vent from 6" to 8"; minimum fire rises only from 50 to 60 MBH.
The Hellcat combustion system with RealTime O2 Trim, the 10" touchscreen control, and venting to 150 equivalent feet in stainless steel, polypropylene, PVC or CPVC.
A consultation includes a heat-loss review so the size is right the first time.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Sources and verification
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.