Lochinvar Crest FCB1000 vs FCB1500

Verdict in brief

The Crest with Hellcat FCB1000 and FCB1500 are the two smallest Hellcat boilers: the 1500 fires 60 to 1500 MBH with 1443 MBH gross output, stepping the pipe to 4" with 1-1/2" gas and 8" air/vent, against the 1000's 3" pipe, 1-1/4" gas and 6" openings.

Side by side

Published manufacturer figures. Input and output are kept separate; blanks mean the manufacturer did not publish that value.

Comparison of Lochinvar Crest FCB1000 and Lochinvar Crest FCB1500
SpecificationLochinvar Crest FCB1000Lochinvar Crest FCB1500
Heating input, minimum50 MBH60 MBH
Heating input, maximum999 MBH1,500 MBH
Gross output961 MBH1,443 MBH
Net AHRI water rating834 MBH1,252 MBH
Water content77 gal94 gal
Pipe outlet connection3"4"
Pipe inlet connection3"4"
Gas connection1-1/4"1-1/2"
Air size6"8"
Vent size6"8"
Weight with water1,838 lb2,307 lb

What actually separates them

Both are Crest wave fire-tube boilers with the Hellcat combustion system — RealTime O2 Trim combustion and the full-color 10" capacitive touchscreen — vented as room air/direct vent or common vent to 150 equivalent feet.

The 1500 is the first FCB size on 4" pipe: against the 1000's 3" outlet/inlet and 1-1/4" gas, it uses 4" pipe with a 1-1/2" gas inlet, and air and vent step from 6" to 8". Minimum fires are close (50 and 60 MBH).

Capacity rises from 999 to 1500 MBH of input with gross output from 961 to 1443 MBH and the AHRI net rating from 834 to 1252 MBH. Water content grows from 77 to 94 gallons and weight with water from 1,838 to 2,307 lb per the ratings table.

CurrentSold in Canada
Input
50–999 MBH
Output (max)
—
AFUE
—

The Crest with Hellcat FCB1000 opens the FCB line at 50 to 999 MBH input with 961 MBH gross output and an 834 MBH AHRI net rating, on 3" pipe with 6" air and vent.

Natural gasPropaneHeating-only
CurrentSold in Canada
Input
60–1500 MBH
Output (max)
—
AFUE
—

The Crest with Hellcat FCB1500 fires 60 to 1500 MBH with 1443 MBH gross output and a 1252 MBH AHRI net rating, stepping the Hellcat line to 4" pipe and 8" air and vent.

Natural gasPropaneHeating-only

Frequently asked questions

What changes in the plant at the FCB1500?

The pipe connections step from 3" to 4", the gas inlet from 1-1/4" to 1-1/2" and air and vent from 6" to 8"; minimum fire rises only from 50 to 60 MBH.

What do the two FCB sizes share?

The Hellcat combustion system with RealTime O2 Trim, the 10" touchscreen control, and venting to 150 equivalent feet in stainless steel, polypropylene, PVC or CPVC.

Not sure which one fits your home?

A consultation includes a heat-loss review so the size is right the first time.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate