Lochinvar · Crest (FB / Hellcat FCB)
Lochinvar Crest FCB1000
The Crest with Hellcat FCB1000 opens the FCB line at 50 to 999 MBH input with 961 MBH gross output and an 834 MBH AHRI net rating, on 3" pipe with 6" air and vent.
Key figures
- Max input
- 999 MBH
- Max CSA output
- —
- AFUE
- —
- Min input
- 50 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Lochinvar Crest FCB1000 in practice
The FCB1000 is the entry of the Crest with Hellcat FCB1000-6000 range: the I&O ratings table (Models 1000-6000, Series 100) lists 50 to 999 MBH input with 961 MBH gross output and an 834 MBH AHRI net water rating — the same ratings row the Crest FB1001 carries. The Hellcat combustion system with RealTime O2 Trim distinguishes it from the FB-generation boiler, per Lochinvar's page copy.
Connections follow the smallest FCB envelope: 3" pipe outlet and inlet, a 1-1/4" gas inlet and 6" air and vent, with a 77-gallon water content and 1,838 lb weight with water per the ratings table. Venting is room air/direct vent or common vent in stainless steel, polypropylene, PVC or CPVC to 150 equivalent feet per the Hellcat page feature list.
Best suited to
- Commercial projects entering the Hellcat range at the 999,000 BTU/hr size
- Plants that want RealTime O2 Trim combustion at the smallest FCB size
- Systems with a 50 MBH minimum fire and 3" piping
Applicability and support
- Model number
- FCB1000
- Canadian availability
- available
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Series terms
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Lochinvar. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Heating input, minimum | 50 MBH | Per the I&O ratings table. |
| Heating input, maximum | 999 MBH | Per the I&O ratings table. |
| Output | ||
| Gross output | 961 MBH | Per the I&O ratings table. |
| Net AHRI water rating | 834 MBH | Per the I&O ratings table. |
| Venting and air | ||
| Air size | 6" | Per the I&O ratings table. |
| Vent size | 6" | Per the I&O ratings table. |
| Venting | Category IV sealed combustion; room air/direct vent/common vent in stainless steel, polypropylene, PVC or CPVC | Up to 150 equivalent feet per the Crest with Hellcat product-page feature list. |
| Physical and connections | ||
| Water content | 77 gal | Per the I&O ratings table. |
| Pipe outlet connection | 3" | Per the I&O ratings table. |
| Pipe inlet connection | 3" | Per the I&O ratings table. |
| Gas connection | 1-1/4" | Per the I&O ratings table. |
| Weight with water | 1,838 lb | Per the I&O ratings table. |
Manuals
Alerts documented for this model
- Gas Pressure SW Open
- Low Water Cutoff Open
- Blocked Drain SW Open
- APS Open
- Anti-cycling
- Flame Failure
- Flame Fail Running
- Gas Valve / Relay Failure
- Auto Reset High Limit
- Manual Reset High Limit Open
- Fan Speed Low
- Fan Speed High
- Louver Proving Sw Open
- Flue Temp High
- Delta T High
- Outlet Temp High
- Parameter Programming Complete
- Sensor Open
- Sensor Shorted
- Flue Sensor Open
- Flue Sensor Shorted
- Too Many Resets - Try Later
- Internal Fault
- Flue Temp Shutdown
- Delta T Shutdown
- Outlet Temp Shutdown
- Writing/Programming EEProm Error
- CRC Parameter Error
- Wrong Error Code
- Flame Sense Out of Sequence 1
- Flame Sense Out of Sequence 2
- Flue Damper Switch Open
- IO Expander Out Error
- Failure ADC Controller
- Outlet Sensor Differential
- Flue Sensor Differential
Frequently asked questions
What are the FCB1000's ratings?
50 to 999 MBH of input with 961 MBH gross output and an 834 MBH AHRI net water rating per the I&O ratings table.
How does the FCB1000 differ from the Crest FB1001?
The rating rows are the same (the FCB line shares the wave fire-tube boiler), but the FCB adds the Hellcat combustion system with RealTime O2 Trim, a 10" capacitive touchscreen and 150 equivalent feet of venting versus 100 on the FB line.
Questions about the Lochinvar Crest FCB1000?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Compare and explore
- Lochinvar Crest FCB1000 vs FCB1500Comparison
- Lochinvar Crest FBN0751Same series
- Lochinvar Crest FBN1001Same series
- Lochinvar Crest FBN1251Same series
- Lochinvar Crest FBN1501Same series
- Lochinvar Crest FBN1751Same series
- Lochinvar Crest FBN2001Same series
- Lochinvar Crest FBN2501Same series
- Lochinvar Crest FBN3001Same series
- Lochinvar Crest FBN3501Same series
- Lochinvar Crest FBN4001Same series
- Lochinvar Crest FBN5001Same series
- Lochinvar Crest FBN6001Same series
- Lochinvar Crest FCB1500Same series
- Lochinvar Crest FCB2000Same series
- Lochinvar Crest FCB2500Same series
- Lochinvar Crest FCB3000Same series
- Lochinvar Crest FCB4000Same series
- Lochinvar Crest FCB5000Same series
- Lochinvar Crest FCB6000Same series
- Crest (FB / Hellcat FCB) series hub
- Buying guide
Sources and verification
- Lochinvar — Crest with Hellcat (FCB4000N) model page · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.