Skip to content
Boilers.caby ROMA Heating & Cooling

AERCO (Watts) · Series

AERCO (Watts) Benchmark

The AERCO Benchmark is the company's condensing gas-fired firetube boiler line from 750 to 6000 MBH — a 439 stainless-steel heat exchanger with 'only two moving parts', up to 20:1 turndown depending on capacity, 87%–98% efficiency range and boiler sequencing for up to 16 boilers, documented here in nine BMK rating-table sizes.

Current seriesunknownNatural gasPropanecommercial

Series facts

Type
condensing
Efficiency
Unknown
Fuel
The TDS specifications table lists natural gas, propane or dual fuel.
Venting
Vent materials AL29-4C, polypropylene, PVC or CPVC (model dependent), per the TDS feature list.
Models documented
9

About the Benchmark

AERCO positions the Benchmark as its flagship condensing boiler: the published 750–6000 TDS ratings table prints nine standard BMK sizes — 750, 1000, 1500, 2000, 2500, 3000, 4000, 5000 and 6000 MBH — with minimum inputs from 50 to 400 MBH, thermal efficiencies from 93.5% to 96.8% at 80º–180ºF and an 87%–98% efficiency range for every row. The TDS also prints a BMK 5000N low-gas-pressure variant.

The heat exchanger is 439 stainless-steel firetube construction, the TDS lists natural gas, propane or dual fuel, NOx capability of 9 ppm or less at all firing rates depending on capacity, and the specifications table prints gas connections from 1" to 2"/3", water connections from 3" to 6" and dry weights from 669 lb to 3,000 lb. The Edge controller adds on-board Boiler Sequencing Technology for plants of 2–16 boilers, BACnet and Modbus communications, and integrated O2 monitoring with TComp air-temperature compensation.

The published warranty is a 10-year heat exchanger, lifetime thermal shock and 18-month parts. The BMK TDS, the Benchmark brochure and the 750–3000 / 6000 installation guides are linked from the live official document system (verified 2026-09-09); aerco.com HTML pages were Cloudflare-blocked to the research network, so no manual URLs are invented and all facts come from the official PDFs.

Highlights

  • Condensing gas boiler in nine standard BMK sizes: 750 – 6000 MBH
  • 439 stainless-steel firetube heat exchanger
  • Thermal efficiency 93.5% – 96.8% by size; 87%–98% range printed for every row
  • Up to 20:1 turndown depending on capacity (12:1 on the BMK 5000)
  • On-board Boiler Sequencing Technology for 2–16 boilers; BACnet/Modbus
  • 10-year heat exchanger / lifetime thermal shock / 18-month parts warranty (page)
  • No official Canadian statement found — canadianStatus unknown

AERCO's Benchmark page prints a 10-year heat-exchanger warranty, lifetime thermal-shock protection and an 18-month parts warranty.

Models

Benchmark models

One canonical page per model with input, output and efficiency kept separate.

AERCO (Watts)

AERCO Benchmark 750

CurrentCanadian status unknown
Input
50–750 MBH
Output (max)
720 MBH
AFUE

The AERCO Benchmark 750 (BMK 750) is a condensing gas-fired firetube commercial boiler rated 750 MBH maximum input and a 653–720 MBH output range in AERCO's published ratings table, at 95.6% thermal efficiency (87%–98% range), with 15:1 (7%) turndown and a 669 lb dry weight.

Natural gasPropaneHeating-only
CurrentCanadian status unknown
Input
50–1000 MBH
Output (max)
960 MBH
AFUE

The AERCO Benchmark 1000 (BMK 1000) is a condensing gas-fired firetube commercial boiler rated 1000 MBH maximum input and a 870–960 MBH output range in AERCO's published ratings table, at 96.8% thermal efficiency (87%–98% range), with 20:1 (5%) turndown and a 700 lb dry weight.

Natural gasPropaneHeating-only
CurrentCanadian status unknown
Input
75–1500 MBH
Output (max)
1,440 MBH
AFUE

The AERCO Benchmark 1500 (BMK 1500) is a condensing gas-fired firetube commercial boiler rated 1500 MBH maximum input and a 1305–1440 MBH output range in AERCO's published ratings table, at 94.6% thermal efficiency (87%–98% range), with 20:1 (5%) turndown and a 1406 lb dry weight.

Natural gasPropaneHeating-only
CurrentCanadian status unknown
Input
100–2000 MBH
Output (max)
1,920 MBH
AFUE

The AERCO Benchmark 2000 (BMK 2000) is a condensing gas-fired firetube commercial boiler rated 2000 MBH maximum input and a 1740–1920 MBH output range in AERCO's published ratings table, at 94.6% thermal efficiency (87%–98% range), with 20:1 (5%) turndown and a 1500 lb dry weight.

Natural gasPropaneHeating-only
CurrentCanadian status unknown
Input
167–2500 MBH
Output (max)
2,400 MBH
AFUE

The AERCO Benchmark 2500 (BMK 2500) is a condensing gas-fired firetube commercial boiler rated 2500 MBH maximum input and a 2175–2400 MBH output range in AERCO's published ratings table, at 93.5% thermal efficiency (87%–98% range), with 15:1 (7%) turndown and a 2000 lb dry weight.

Natural gasPropaneHeating-only
CurrentCanadian status unknown
Input
200–3000 MBH
Output (max)
2,880 MBH
AFUE

The AERCO Benchmark 3000 (BMK 3000) is a condensing gas-fired firetube commercial boiler rated 3000 MBH maximum input and a 2610–2880 MBH output range in AERCO's published ratings table, at 94.6% thermal efficiency (87%–98% range), with 15:1 (7%) turndown and a 2170 lb dry weight.

Natural gasPropaneHeating-only
CurrentCanadian status unknown
Input
267–4000 MBH
Output (max)
3,840 MBH
AFUE

The AERCO Benchmark 4000 (BMK 4000) is a condensing gas-fired firetube commercial boiler rated 4000 MBH maximum input and a 3480–3840 MBH output range in AERCO's published ratings table, at 94.1% thermal efficiency (87%–98% range), with 15:1 (7%) turndown and a 2200 lb dry weight.

Natural gasPropaneHeating-only
CurrentCanadian status unknown
Input
400–5000 MBH
Output (max)
4,800 MBH
AFUE

The AERCO Benchmark 5000 (BMK 5000) is a condensing gas-fired firetube commercial boiler rated 5000 MBH maximum input and a 4350–4800 MBH output range in AERCO's published ratings table, at 94.8% thermal efficiency (87%–98% range), with 12:1 (8%) turndown and a 3000 lb dry weight.

Natural gasPropaneHeating-only
CurrentCanadian status unknown
Input
400–6000 MBH
Output (max)
5,760 MBH
AFUE

The AERCO Benchmark 6000 (BMK 6000) is a condensing gas-fired firetube commercial boiler rated 6000 MBH maximum input and a 5220–5760 MBH output range in AERCO's published ratings table, at 94.5% thermal efficiency (87%–98% range), with 15:1 (7%) turndown and a 3000 lb dry weight.

Natural gasPropaneHeating-only

Compare models in this series

Comparison of AERCO Benchmark 750 and AERCO Benchmark 1000 and AERCO Benchmark 1500 and AERCO Benchmark 2000 and AERCO Benchmark 2500 and AERCO Benchmark 3000 and AERCO Benchmark 4000 and AERCO Benchmark 5000 and AERCO Benchmark 6000
SpecificationAERCO Benchmark 750AERCO Benchmark 1000AERCO Benchmark 1500AERCO Benchmark 2000AERCO Benchmark 2500AERCO Benchmark 3000AERCO Benchmark 4000AERCO Benchmark 5000AERCO Benchmark 6000
Min. input50 MBH50 MBH75 MBH100 MBH167 MBH200 MBH267 MBH400 MBH400 MBH
Max. input750 MBH1,000 MBH1,500 MBH2,000 MBH2,500 MBH3,000 MBH4,000 MBH5,000 MBH6,000 MBH
Max. output720 MBH960 MBH1,440 MBH1,920 MBH2,400 MBH2,880 MBH3,840 MBH4,800 MBH5,760 MBH
afue
Turndown ratio15:1 (7%)20:1 (5%)20:1 (5%)20:1 (5%)15:1 (7%)15:1 (7%)15:1 (7%)12:1 (8%)15:1 (7%)
vent-max-3
vent-max-2
Weight, dry669 lb700 lb1,406 lb1,500 lb2,000 lb2,170 lb2,200 lb3,000 lb3,000 lb

Read the full comparison: AERCO Benchmark 750 vs Benchmark 1000

Read the full comparison: AERCO Benchmark 1000 vs Benchmark 1500

Read the full comparison: AERCO Benchmark 2500 vs Benchmark 3000

Read the full comparison: AERCO Benchmark 5000 vs Benchmark 6000

Error codes and alerts

Benchmark alerts

Manuals

Official documents

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Frequently asked questions

Is the AERCO Benchmark a condensing boiler?

Yes. AERCO lists the Benchmark under Condensing Boilers with a 439 stainless-steel firetube heat exchanger and lifetime thermal-shock protection.

What sizes does the Benchmark come in?

The published TDS prints nine standard BMK sizes — 750, 1000, 1500, 2000, 2500, 3000, 4000, 5000 and 6000 MBH — plus a BMK 5000N low-gas-pressure variant.

Is the Benchmark available in Canada?

No official Canadian statement was found on the captured pages. AERCO's site provides rep and service locators; confirm supply through an authorized AERCO representative.

Talk to a boiler technician

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate