Skip to content
Boilers.caby ROMA Heating & Cooling

Bradford White · Brute

Bradford White Brute FT BFTHW-399

The Bradford White Brute FT BFTHW-399 is the top Brute FT boiler for Canada: a wall-hung condensing, heating-only hydronic boiler (floor stand optional) rated at 399,000 Btu/h maximum input with 10:1 turndown, printing 95.9% combustion and 95.4% thermal efficiency.

CurrentSold in Canada

Key figures

Max input
399 MBH
Max CSA output
—
AFUE
—
Min input
39.9 MBH
Natural gasPropaneHeating-onlyresidentialcommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Bradford White Brute FT BFTHW-399 in practice

The BFTHW-399 is the larger of the two Brute FT boiler-type condensing units Bradford White lists for Canada (model number printed on the official Canada and US catalogues as BFTHW-399). It shares the BFTHW-301's wall-hung chassis with a floor-stand accessory option but fires to 399,000 Btu/h from the same 39,900 Btu/h minimum — a printed 10:1 turndown — with AHRI certified combustion and thermal efficiencies of 95.9% and 95.4%.

The official sizing data prints a gross output of 379 MBH and a Net AHRI water rating of 330 MBH, with an 80 psig MAWP (ASME "H" stamp) and a 30 psi ASME pressure relief valve. Venting is sealed-combustion Category IV in 3" to 65 equivalent ft or 4" to 150 equivalent ft, with 1½" NPT system supply/return and 1" NPT gas connections, on the NGTB-1000C control with outdoor reset and cascade to four units.

Like the BFTHW-301, the Brute FT is heating-only, not a combi — domestic hot water comes from a separate tank supported through the boiler's DHW sensor logic. With the other Brute lines marked 'No Longer Available in Canada' on the official Canada catalogue, the BFTHW-399 is the top-input Brute size a Canadian buyer can currently specify; its extra 98 MBH of ceiling over the 301 earns its place only when a heat-loss calculation genuinely needs it.

Best suited to

  • Larger homes and light-commercial plants whose heat-loss calculation approaches the 399 MBH input ceiling
  • Heating-only hydronic systems feeding radiators or in-floor loops with a separate indirect tank
  • Projects wanting the full Brute FT modulation depth (10:1) at the top Canadian-listed input

Applicability and support

Model number
BFTHW-399
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Series terms

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Bradford White. Units are shown with every value; notes flag conflicting sources or missing figures.

Bradford White Brute FT BFTHW-399 specifications
SpecificationValueNote
Input
Maximum input399 MBH399,000 Btu/h (117 kW), as printed in the sizing data (Submittal 1540; I&O Section 2.3).
Minimum input39.9 MBH39,900 Btu/h as printed — the same minimum fire rate is printed for the BFTHW-301.
Output
Gross output379 MBH379 MBH (111 kW) as printed in the sizing data.
Net AHRI water rating330 MBH330 MBH (97 kW) as printed in the sizing data.
Efficiency
Combustion efficiency (AHRI)95.9 %AHRI certified combustion efficiency as printed (95.9%); product-page copy states 95%+ AHRI certified.
Thermal efficiency (AHRI)95.4 %AHRI certified thermal efficiency as printed (95.4%).
Domestic hot water
Domestic hot waterNone built in — heating-only hydronic boiler; indirect tank supported through DHW sensor logicNot a combi: rated for hydronic heating with indirect DHW via tank sensor logic, as printed.
Venting and air
Max. equivalent vent length, 3"65 ft3" venting to 65 equivalent ft as printed.
Max. equivalent vent length, 4"150 ft4" venting to 150 equivalent ft as printed.
VentingSealed combustion, Category IV — single, concentric or direct vent3" venting to 65 equivalent ft or 4" venting to 150 equivalent ft; CPVC, polypropylene (incl. flexible), PVC and stainless flue; air intake in ABS, PVC, CPVC, PP or galvanized material.
Physical and connections
Product weight250 lb250 lb (114 kg); shipping weight 275 lb (125 kg). With the floor-stand accessory: 285 lb product and 320 lb shipping, as printed.
Height32.7 inH × W × D as printed; the BFTHW-301 and BFTHW-399 share the same chassis dimensions.
Width25.4 in
Depth20.7 in
Water capacity10 gal10.0 gal (80 lb), as printed.
Water connections1½" NPTSystem supply and return, top and bottom (as printed).
Gas connection1" NPT
Condensate line½" OD
Electrical
Electrical120 V / 60 Hz on a 15 A circuit (<4 A draw); 24 VAC controls
Operating limits and other
Turndown ratio10:110:1 as printed in the sizing data (399 ÷ 39.9 = 10:1).
FuelNatural gas or propaneNatural gas is the factory configuration; the propane conversion kit is included with the unit (field conversion, as printed).
Gas supply pressureNG 3.5–10.5 / LP 8.0–13.0 in. w.c.Natural-gas inlet 3.5–10.5" w.c.; propane inlet 8.0–13.0" w.c., as printed.
Maximum allowable working pressure (MAWP)80 psig80 psi (551 kPa); ASME "H" stamp with National Board listing, as printed.
Pressure relief valve30 psig30 psi (207 kPa) ASME PRV, as printed on the product page feature list.
Controls & cascadeNGTB-1000C main controller with P-953EH display; PID modulation; outdoor reset sensor included; cascade up to 4 units (mixed sizes allowed); 0–10 VDC; Modbus via gateway
BurnerSingle-orifice premix burner, ceramic fiber; direct spark ignition
Heat exchangerStainless steel heat exchanger with finned-aluminum-core fire tubes10-year limited heat exchanger warranty, as printed.

Frequently asked questions

How does the BFTHW-399 differ from the BFTHW-301?

Both are the same wall-hung condensing Brute FT chassis with the same 39,900 Btu/h minimum fire, but the 399 fires to 399,000 Btu/h (10:1 turndown) against the 301's 301,000 Btu/h (7.5:1), prints 95.9%/95.4% combustion/thermal efficiency and is about 10 lb heavier.

Is the BFTHW-399 a combi boiler?

No. The Brute FT line is heating-only — the BFTHW-399 produces no domestic hot water itself. It pairs with a separate indirect tank through the control's DHW sensor logic.

What venting does the BFTHW-399 need?

Sealed-combustion Category IV venting: 3" to 65 equivalent ft or 4" to 150 equivalent ft, single, concentric or direct, as printed. Canadian plastic venting must comply with the applicable codes (ULC S636 where required).

Questions about the Bradford White Brute FT BFTHW-399?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 8, 2026. Last updated September 8, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate