Skip to content
Boilers.caby ROMA Heating & Cooling

Bryan Boilers · BFIT

Bryan BFIT 1000

The Bryan BFIT 1000 is a commercial condensing stainless-steel boiler rated 999,000 BTU/hr input and 969,000 BTU/hr output at 97% thermal/combustion efficiency, 29 BHP, with 10:1 turndown and <10 ppm NOx in Bryan's published submittal.

CurrentCanadian status unknown

Key figures

Max input
999,000 BTU/HR
Max CSA output
969,000 BTU/HR
AFUE
Min input
100,000 BTU/HR
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Bryan BFIT 1000 in practice

Bryan's BFIT 1000 submittal prints 100,000 BTU/hr low fire, 999,000 BTU/hr high fire and 969,000 BTU/hr high-fire output at 29 BHP, with 97% thermal/combustion efficiency, 75 sq ft of heating surface, 8 gallons of water volume and a recovery rate of 1,187 GPH at a 100°F temperature rise.

The unit fires Natural Gas or LP with full modulation and 10:1 burner turndown at <10 ppm NOx. The dimensions table prints 38 1/2" high × 25 5/8" wide × 52 3/8" long with 2" FNPT water outlet, 2" MNPT water inlet, 6" vent and air intake, 1" gas inlet and a 600 lb approximate shipping weight; electrical is 120 VAC single phase at 8 A maximum draw.

The BFIT pressure vessel is ASME Section IV certified with an 'H' stamp at 160 PSIG and 210°F maximum, backed by a ten-year limited pressure vessel warranty, and controlled by the Concert control with EMS communications. Bryan publishes the BFIT/W combined literature, I&O manuals, parts manual and Concert control manual as public downloads. No official Canadian-sales statement was found.

Best suited to

  • Commercial condensing plants documenting an installed BFIT 1000 against Bryan's submittal
  • Tight boiler rooms — BFIT models 400–2000 are documented as fitting through standard doorways
  • Variable-flow or primary/secondary hydronic systems in the 29 BHP class

Applicability and support

Model number
BFIT-1000 C
Canadian availability
unknown
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Series terms

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Bryan Boilers. Units are shown with every value; notes flag conflicting sources or missing figures.

Bryan BFIT 1000 specifications
SpecificationValueNote
Input
Input, low fire100,000 BTU/HRAs printed in the BFIT submittal ratings table.
Input, high fire999,000 BTU/HRAs printed in the BFIT submittal ratings table.
Output
Output, high fire969,000 BTU/HRAs printed in the BFIT submittal ratings table.
Efficiency
Thermal / combustion efficiency97 %As printed in the BFIT submittal ratings table.
Domestic hot water
Recovery rate (100°F rise)1,187 GPHAs printed in the BFIT submittal ratings table.
Venting and air
Vent and air intake6"As printed in the BFIT submittal dimensions/connections table; Category II or IV venting.
Physical and connections
Heating surface75 Sq.Ft.As printed in the BFIT submittal ratings table.
Water volume8 galAs printed in the BFIT submittal ratings table.
Approx. shipping weight600 lbAs printed in the BFIT submittal ratings table.
Width25 5/8"As printed in the BFIT submittal dimensions table.
Length52 3/8"As printed in the BFIT submittal dimensions table.
Height38 1/2"As printed in the BFIT submittal dimensions table.
Water connections (out / in)2" FNPT / 2" MNPTAs printed in the BFIT submittal dimensions/connections table.
Gas inlet connection1"As printed in the BFIT submittal dimensions/connections table.
Electrical
Electrical (appliance only)120 VAC, 1 phase, 60 Hz, 8 A max drawAs printed in the BFIT submittal electrical table.
Operating limits and other
Boiler horsepower29 BHPAs printed in the BFIT submittal ratings table.
FuelNatural Gas or LPAs printed in the BFIT submittal ratings table.
Burner turndown10:1As printed in the BFIT submittal ratings table.
Low NOx emissions<10 ppmAs printed in the BFIT submittal ratings table.
ASME Section IV rating160 PSIG / 210°FASME Section IV (Max 160 PSIG / 210°F) as printed on the BFIT submittal.

Frequently asked questions

What are the BFIT 1000 ratings?

Bryan's submittal prints 100,000 BTU/hr low fire, 999,000 BTU/hr high fire, 969,000 BTU/hr output, 29 BHP and 97% thermal/combustion efficiency.

What fuel does the BFIT 1000 use?

The submittal prints Natural Gas or LP.

What efficiency is the BFIT 1000?

The submittal prints 97% thermal/combustion efficiency; Bryan's BFIT page states all models are 97% thermal efficient.

Questions about the Bryan BFIT 1000?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate