Skip to content
Boilers.caby ROMA Heating & Cooling

Crown Boiler Co. · Raptor

Crown Raptor RPTR085HB

The Crown Raptor RPTR085HB fires 8.5 to 85 MBH input at 96% AFUE with 79 MBH DOE heating capacity and a 69 MBH net AHRI rating, on the stainless-steel fire-tube condensing platform.

CurrentCanadian status unknown

Key figures

Max input
85 MBH
Max CSA output
AFUE
96 %
Min input
8.5 MBH
Natural gasPropaneHeating-onlyresidentialcommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Crown Raptor RPTR085HB in practice

The Raptor RPTR085HB is a heat-only Raptor size: a stainless-steel, gas-fired, direct-vent condensing boiler rated 8.5–85 MBH input with 79 MBH DOE heating capacity and a 69 MBH net AHRI water rating (1.15 allowance) at 96% AFUE per the ratings table (I&O manual Table 2.3; product page). It is designed for installation on a wall with a pre-installed hanging bracket and wall-mount kit (literature PN 980778).

The specifications table lists 2.6 US gallons of water volume, a 30 psig maximum allowable working pressure, 1" copper sweat water connections, a 1/2" NPT gas connection and approximately 110 lb net weight. Venting is direct vent at 2" or 3" with a 30 ft minimum and a 60 ft (2") or 135 ft (3") maximum equivalent length; the boiler measures 33-5/16" high, 19-13/16" wide and 20" deep. The touchscreen Sola-family control includes outdoor reset, domestic hot water priority, three circulator outputs and a built-in sequencer for up to 8 boilers.

Boilers.ca documents this model at model level; boilers ship set for natural gas with LP conversion by optional kit. No official Canadian-sales statement was found, so canadianStatus stays 'unknown'; installation, gas and venting work belongs with a licensed contractor.

Best suited to

  • 85-MBH-class residential and light-commercial loads
  • Projects wanting 10:1-modulating stainless condensing heat with an outdoor reset sensor
  • Cascaded multi-boiler plants using the built-in sequencer (up to 8 boilers)

Applicability and support

Model number
RPTR085HB
Canadian availability
unknown
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Crown Boiler Co.. Units are shown with every value; notes flag conflicting sources or missing figures.

Crown Raptor RPTR085HB specifications
SpecificationValueNote
Input
Input, maximum85 MBHMaximum input per the Raptor ratings table (I&O manual Table 2.3; product page).
Input, minimum8.5 MBHMinimum input per the Raptor ratings table (I&O manual Table 2.3).
Output
DOE heating capacity79 MBHDOE heating capacity per the Raptor ratings table (I&O manual Table 2.3).
Net AHRI water rating69 MBHNet AHRI water rating based on a piping and pickup allowance of 1.15 per the ratings table.
Efficiency
Efficiency (AFUE)96 %AFUE per the ratings table; the RPTR085HB and RPTR110HB are ENERGY STAR certified (literature PN 980778).
Domestic hot water
Domestic hot waterHeating-only boiler — domestic hot water comes from a separate indirect tank or water heater
Venting and air
VentingDirect vent, 2" or 3"Vent/intake size per the ratings and vent-length tables; minimum vent length 30 ft, maximum 60 ft in 2" or 135 ft in 3" equivalent length with derate at maximum length (I&O manual Tables 2.3/2.4).
Physical and connections
Water volume2.6 galWater volume per the Raptor specifications table (I&O manual Table 2.3).
Water connection1" copper sweatWater connection size (copper sweat) per the specifications table; versatile top and bottom supply and return connections per the literature.
Gas connection1/2" NPTGas connection size (NPT) per the specifications table (I&O manual Table 2.3).
Approx. net weight110 lbApproximate net weight per the specifications table (I&O manual Table 2.3).
Dimensions (H × W × D)33-5/16" × 19-13/16" × 20"Boiler height and width per the literature drawing; depth per the product dimensions table.
Operating limits and other
Maximum allowable working pressure (MAWP)30 psigMAWP per the ratings table (I&O manual Table 2.3).
FuelNatural gas or LP gasBoilers ship set for natural gas; field convertible to LP gas with an optional kit (literature; product page).
ControlSola control system with LCD touch screen displayBuilt-in self diagnostics, domestic hot water priority, warm weather shutdown, three circulator outputs, password security and built-in sequencer for up to 8 boilers (literature PN 980778).

Frequently asked questions

What are the RPTR085HB's ratings?

8.5–85 MBH input, 79 MBH DOE heating capacity and a 69 MBH net AHRI water rating at 96% AFUE per the ratings table.

Is the RPTR085HB ENERGY STAR certified?

Yes — the RPTR085HB and RPTR110HB are ENERGY STAR certified products per the literature sheet.

Does the Raptor need a chimney?

No — it is a direct-vent condensing boiler that vents horizontally or vertically in 2" or 3" approved pipe up to 135 equivalent feet (60 ft in 2").

Questions about the Crown Raptor RPTR085HB?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 8, 2026. Last updated September 8, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate