Crown Raptor RPTR155CB (Combi)
The Crown Raptor RPTR155CB Combi fires 15.5 to 155 MBH input at 95% AFUE with 145 MBH DOE heating capacity and a 126 MBH net AHRI rating, adding tankless domestic hot water through a thermostatic mixing valve and brazed plate heat exchanger, on the stainless-steel fire-tube condensing platform.
Key figures
- Max input
- 155 MBH
- Max CSA output
- —
- AFUE
- 95 %
- Min input
- 15.5 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Crown Raptor RPTR155CB (Combi) in practice
The Raptor RPTR155CB is the combi version of the Raptor line: a stainless-steel, gas-fired, direct-vent condensing boiler rated 15.5–155 MBH input with 145 MBH DOE heating capacity and a 126 MBH net AHRI water rating (1.15 allowance) at 95% AFUE per the ratings table (I&O manual Table 2.3; product page). It is designed for installation on a wall with a pre-installed hanging bracket and wall-mount kit (literature PN 980778).
The specifications table lists 3 US gallons of water volume, a 30 psig maximum allowable working pressure, 1" copper sweat water connections, a 1/2" NPT gas connection and approximately 140 lb net weight. Venting is direct vent at 3" with a 30 ft minimum and a 60 ft (2") or 135 ft (3") maximum equivalent length; the boiler stands 33-5/16" high by 19-13/16" wide. The touchscreen Sola-family control includes outdoor reset, domestic hot water priority, three circulator outputs and a built-in sequencer for up to 8 boilers.
Note: the product page prints the combi rating row as RPTRC155CB with a 170 lb approximate shipping weight, while the I&O manual ratings table (Table 2.3) prints RPTR155CB at a 140 lb approximate net weight — the manual's model number and weight are used here, and the difference is flagged. Boilers.ca documents this model at model level; boilers ship set for natural gas with LP conversion by optional kit. No official Canadian-sales statement was found, so canadianStatus stays 'unknown'; installation, gas and venting work belongs with a licensed contractor.
Best suited to
- Homes wanting the Raptor's 155 MBH-class heat plus tankless domestic hot water in one wall-hung unit
- Projects wanting 10:1-modulating stainless condensing heat with an outdoor reset sensor
- Cascaded multi-boiler plants using the built-in sequencer (up to 8 boilers)
Applicability and support
- Model number
- RPTR155CB
- Canadian availability
- unknown
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Not verified
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Crown Boiler Co.. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Input, maximum | 155 MBH | Maximum input per the Raptor ratings table (I&O manual Table 2.3; product page). |
| Input, minimum | 15.5 MBH | Minimum input per the Raptor ratings table (I&O manual Table 2.3). |
| Output | ||
| DOE heating capacity | 145 MBH | DOE heating capacity per the Raptor ratings table (I&O manual Table 2.3). |
| Net AHRI water rating | 126 MBH | Net AHRI water rating based on a piping and pickup allowance of 1.15 per the ratings table. |
| Efficiency | ||
| Efficiency (AFUE) | 95 % | AFUE per the ratings table; the RPTR085HB and RPTR110HB are ENERGY STAR certified (literature PN 980778). |
| Domestic hot water | ||
| Domestic hot water | Integrated combi boiler: space heating plus tankless domestic hot water | Combi model featuring a thermostatic mixing valve and brazed plate heat exchanger (product page); tankless domestic hot water per the I&O manual product description. |
| Venting and air | ||
| Venting | Direct vent, 3" | Vent/intake size per the ratings and vent-length tables; minimum vent length 30 ft, maximum 60 ft in 2" or 135 ft in 3" equivalent length with derate at maximum length (I&O manual Tables 2.3/2.4). |
| Physical and connections | ||
| Water volume | 3 gal | Water volume per the Raptor specifications table (I&O manual Table 2.3). |
| Water connection | 1" copper sweat | Water connection size (copper sweat) per the specifications table; versatile top and bottom supply and return connections per the literature. |
| Gas connection | 1/2" NPT | Gas connection size (NPT) per the specifications table (I&O manual Table 2.3). |
| Approx. net weight | 140 lb | Approximate net weight per the specifications table (I&O manual Table 2.3). |
| Operating limits and other | ||
| Maximum allowable working pressure (MAWP) | 30 psig | MAWP per the ratings table (I&O manual Table 2.3). |
| Fuel | Natural gas or LP gas | Boilers ship set for natural gas; field convertible to LP gas with an optional kit (literature; product page). |
| Control | Sola control system with LCD touch screen display | Built-in self diagnostics, domestic hot water priority, warm weather shutdown, three circulator outputs, password security and built-in sequencer for up to 8 boilers (literature PN 980778). |
Frequently asked questions
What are the RPTR155CB's ratings?
15.5–155 MBH input, 145 MBH DOE heating capacity and a 126 MBH net AHRI water rating at 95% AFUE per the ratings table.
Why does the product page print RPTRC155CB?
The current product page prints the combi row as RPTRC155CB (170 lb approximate shipping weight), while the I&O manual ratings table prints RPTR155CB with a 140 lb approximate net weight — Boilers.ca uses the manual's model number and net weight and notes the page spelling.
Does the Raptor need a chimney?
No — it is a direct-vent condensing boiler that vents horizontally or vertically in 2" or 3" approved pipe up to 135 equivalent feet (60 ft in 2").
Questions about the Crown Raptor RPTR155CB (Combi)?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Compare and explore
- Crown Raptor RPTR110HB vs RPTR155CB (Combi)Comparison
- Crown Raptor RPTR155CB (Combi) vs RPTR155HBComparison
- Crown Raptor RPTR085HBSame series
- Crown Raptor RPTR110HBSame series
- Crown Raptor RPTR155HBSame series
- Crown Raptor RPTR205HBSame series
- Crown Raptor RPTR270HBSame series
- Raptor series hub
- Buying guide
Sources and verification
- Velocity Boiler Works — Raptor product page · accessed September 9, 2026
- Raptor Installation and Operating Manual, PN 107363-02 (11/17) (PDF) · 107363-02 · accessed September 9, 2026
Facts checked September 8, 2026. Last updated September 8, 2026. Technical reviewer: not yet assigned.