Skip to content
Boilers.caby ROMA Heating & Cooling

HTP · Error codes

HTP Pioneer LOU — 24 Volt Low

LOU

Needs attentionHTP Pioneer boilers (926 SIT control, manual LP-325)

24 volt low. Check line voltage (must be 100-128 volts); with HTP service software check the 24 V supply display (must be greater than 128, should be greater than 250); remove the 10-pin Molex from the customer connection board - if LOU clears the problem is external sensor wiring (examine for shorts to ground); if still present disconnect the high gas pressure switch, then low gas pressure switch, then UL 353 low water cut-off one at a time and replace the faulty part; check the low-voltage wire harness for shorts to ground; check the gas valve for excessive current draw when the burner tries to light; if LOU is present with the low-voltage harness disconnected from the 926 control board, replace the 926 control board. The table classifies it as Error (Auto Reset).

Applies to

This gas-train fault code is displayed by the 926 SIT control on Pioneer models (PHR100-55 through PHR199-55), as documented in Pioneer Installation Manual, LP-325 Rev. 010 Rel. 001 (12.8.21), Table 18 (LP-325). Codes can differ between controller generations, so always check the manual that matches your unit.

Controller: 926 SIT control. Source manual: LP-325.

Why a code is not a diagnosis

A gas-train code involves the gas valve or its electrical circuit. It does not mean there is a leak; the circuit, coils and wiring must be measured by a licensed technician.

Safe things to observe

  • If you smell gas, stop, go outside and call your gas utility's emergency line or 911 before anything else.
  • Note the exact code and what the appliance was doing when it appeared.
  • Check whether other gas appliances in the building are working.

Do not

  • Do not reset or run the appliance while the gas valve circuit is suspect.
  • Do not touch the gas valve.

How professional service helps

  1. A technician verifies harness connections and coil resistances against the manual before replacing parts.
  2. Combustion and safety devices are verified with an analyser and the manufacturer's procedure after any repair.

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Parts and service

Parts commonly involved

These parts appear in the documented text for this alert. A code reports a condition, not a failed part — a technician confirms the cause by testing before anything is replaced.

Service for this alert

  • Gas Boiler Repair

    Licensed gas technicians from ROMA Heating & Cooling diagnose and repair residential and light-commercial gas boilers across…

Every boiler part explained — what it does, how it fails and what a technician checks.

Documented for HTP Pioneer (discontinued).

Frequently asked questions

Does this code mean I have a gas leak?

Not by itself. If you smell gas, stop, leave the building and call your gas utility's emergency line or 911 from outside before anything else. Otherwise the code points to a fault a technician confirms on site.

Can I clear this code myself?

Clearing a code without fixing its cause usually just brings it back. Note the code, check the safe items on this page, then call a licensed technician. If your appliance manual describes a user reset for this exact code and it stays away, no call may be needed.

Boiler locked out? Call with the alert text ready.

The brand, model and this alert are passed along when you request service online, so the technician arrives prepared.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 8, 2026. Last updated September 8, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate