Skip to content
Boilers.caby ROMA Heating & Cooling

HTP · Error codes

HTP Ultra Er:80 — Low Water Level Sensor (low Water Level Detected Four Consecutive Times)

Er:80

LockoutHTP UFT (Universal Fire Tube) boilers (Er:## codes, manual lp-542)

Low Water Level Sensor (Low Water Level Detected Four Consecutive Times). Low water level was detected four consecutive times. Ensure all valves are open to the boiler and there are no leaks, purge all air from the system, check the low water level sensor wiring connections and sensor resistance (replace if zero). The table classifies it as Soft lockout (auto reset when condition remedied).

Applies to

This low-water or pressure protection code is displayed by the UFT control (Er:## codes) on UFT models (UFT-080W through UFT-199W), as documented in UFT Boiler Installation Start-Up Maintenance Parts Warranty, lp-542 Rev.002 (6.9.20) (lp-542 Rev.002). Codes can differ between controller generations, so always check the manual that matches your unit.

Controller: UFT control (Er:## codes). Source manual: lp-542 Rev.002 (2020-06).

Why a code is not a diagnosis

A water-pressure or low-water code can mean a genuine leak or empty system, a failed expansion tank, a faulty fill valve, or a sensor problem. The appliance does not distinguish these.

Safe things to observe

  • Read the pressure gauge and compare it with the normal cold-system pressure your installer set.
  • Look for drips or wet spots near the appliance, pipes and the relief-valve discharge.

Do not

  • Do not keep re-pressurizing a system that keeps losing water.
  • Do not cap a relief-valve discharge pipe.

How professional service helps

  1. A technician finds and repairs the leak, checks the expansion tank and fill assembly, and verifies the sensor circuit.

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Parts and service

Parts commonly involved

These parts appear in the documented text for this alert. A code reports a condition, not a failed part — a technician confirms the cause by testing before anything is replaced.

Service for this alert

  • Gas Boiler Repair

    Licensed gas technicians from ROMA Heating & Cooling diagnose and repair residential and light-commercial gas boilers across…

  • Emergency Boiler Repair

    Priority gas boiler repair for homes and buildings in Greater Vancouver with no heat, no hot water, a locked-out boiler or a leak.

Every boiler part explained — what it does, how it fails and what a technician checks.

Documented for HTP Ultra (UFT & EFTU).

Frequently asked questions

Can I clear this code myself?

Clearing a code without fixing its cause usually just brings it back. Note the code, check the safe items on this page, then call a licensed technician. If your appliance manual describes a user reset for this exact code and it stays away, no call may be needed.

Boiler locked out? Call with the alert text ready.

The brand, model and this alert are passed along when you request service online, so the technician arrives prepared.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 8, 2026. Last updated September 8, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate