NTI Boilers Green Furnace (GF200 / GF150)

The Green Furnace line merges an NTI condensing combi boiler with a high-efficiency air handler for forced-air heating, hydronic heating and domestic hot water in one cabinet: the GF200 at 19,900-199,000 BTU/hr DHW input and 97% AFUE, and the GF150 at 13,200-150,000 BTU/hr DHW input and 95% AFUE.

Current seriesSold in CanadaNatural gasPropaneresidential

Series facts

Type
combi
Efficiency
Unknown
Fuel
The GF200 submittal prints "Field Convertible to LP Gas" and the GF150 spec table prints NG 3.5-10.5" W.C. and LP 8-13" W.C. gas pressures.
Venting
Forced-draft direct vent: the GF200 takes 2" or 3" venting and the GF150 prints 2" (0-100 ft intake / 6-100 ft exhaust) or 3" (0-150 ft intake / 6-150 ft exhaust) runs.
Models documented
2
Warranty
Not verified

About the Green Furnace (GF200 / GF150)

The Green Furnace is NTI's all-in-one combi-furnace: a condensing boiler section paired with an ECM air handler that provides forced-air heating, hydronic heating and domestic hot water from a single unit. The GF200 submittal prints space-heating input of 19,900-80,000 BTU/hr and DHW input of 19,900-199,000 BTU/hr with 97% AFUE, a 0.97 energy factor on domestic water and flow rates from 7.8 gpm at a 50°F rise down to 4.8 gpm at an 80°F rise; the GF150 spec table prints 13,200-120,000 BTU/hr space heating, 13,200-150,000 BTU/hr DHW, 95% AFUE and 3.6 gpm at a 77°F rise.

Both models include internal recirculation and a buffer tank to eliminate the cold-water sandwich, stainless steel heat exchangers, a built-in condensate trap and a built-in DHW flow switch with a serviceable filter. The GF200 ships at 248 lb in a 17.75" x 38" x 38" cabinet with 2" or 3" venting; the GF150 adds cooling capability up to 3 tons with 300-1200 CFM heating airflow and 360-1200 CFM cooling airflow. Both are field-convertible to LP gas, and the GF200 submittal notes its AFUE is based on NTI lab testing sent to AHRI.

Highlights

  • Combi-furnace: forced-air heating, hydronic heating and DHW in one cabinet
  • GF200: 19,900-199,000 BTU/hr DHW input, 97% AFUE, 0.97 energy factor
  • GF150: 13,200-150,000 BTU/hr DHW input, 95% AFUE, up to 3 tons cooling
  • Internal recirculation and buffer tank; stainless steel heat exchangers
  • 2" or 3" direct venting; field-convertible to LP gas
  • Built-in DHW flow switch with serviceable filter and condensate trap

Models

Green Furnace (GF200 / GF150) models

One canonical page per model with input, output and efficiency kept separate.

NTI Boilers

NTI GF 200

CurrentSold in Canada
Input
19.9–80 MBH
Output (max)
AFUE
97 %

The NTI GF 200 is a combi-furnace with 19,900-80,000 BTU/hr space-heating input, 19,900-199,000 BTU/hr DHW input, 97% AFUE and a 0.97 DHW energy factor, delivering up to 7.8 gpm at a 50°F rise from an internal recirculation and buffer tank.

Natural gasPropaneCombi

NTI Boilers

NTI GF150

CurrentSold in Canada
Input
13.2–80 MBH
Output (max)
AFUE
95 %

The NTI GF150 is a combi-furnace with 13,200-120,000 BTU/hr space-heating capacity, 13,200-150,000 BTU/hr DHW capacity, 95% AFUE, up to 3 tons of cooling and 3.6 gpm of domestic hot water at a 77°F rise.

Natural gasPropaneCombi

Compare models in this series

Comparison of NTI GF 200 and NTI GF150
SpecificationNTI GF 200NTI GF150
Space heating input, minimum19.9 MBH13.2 MBH
Space heating input, maximum80 MBH80 MBH
output-max
Efficiency (AFUE)97 %95 %
turndown
vent-max-3
vent-max-2
Weight248 lb

Read the full comparison: NTI GF 200 vs GF150

Error codes and alerts

Green Furnace (GF200 / GF150) alerts

No alerts documented for this series yet.

Manuals

Official documents

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Frequently asked questions

What is a Green Furnace?

It is NTI's all-in-one unit that merges a condensing combi boiler with an ECM air handler, providing forced-air heating, hydronic heating and domestic hot water from one appliance rather than a separate furnace and water heater.

What is the difference between the GF200 and GF150?

Capacity: the GF200 spans 19,900-199,000 BTU/hr DHW input at 97% AFUE, while the GF150 spans 13,200-150,000 BTU/hr DHW input at 95% AFUE with up to 3 tons of cooling and 360-1200 CFM cooling airflow.

Can a Green Furnace run on propane?

Yes. The GF200 submittal states it is field convertible to LP gas, and the GF150 spec table prints LP gas pressures of 8-13" W.C. against 3.5-10.5" W.C. for natural gas.

Talk to a boiler technician

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.