Peerless Cast 92-4
The Peerless Cast 92-4 is the legacy commercial or large-residential gas-fired condensing cast-iron boiler: a single-model line with an 80–399 MBH CSA input range whose 399 MBH rating row prints 370 MBH output and a 322 MBH net rating at 92.7% thermal efficiency (87.7% combustion efficiency), sealed-combustion direct vent with a 4" flue, 7.125 gallons of water and a cascade-ready HeatNet control.
Key figures
- Max input
- —
- Max CSA output
- —
- AFUE
- —
- Min input
- —
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Peerless Cast 92-4 in practice
The Cast 92-4 is the commercial or large-residential member of Peerless' legacy Cast 92 condensing cast-iron family, published under 'Out of Circulation – Gas Boilers' on the official site. The page describes a gas-fired condensing cast-iron boiler with a thermal efficiency of 92.7%, a cast-iron heat exchanger that 'retains heat longer for extreme durability', low CO2 and NOx emissions, quiet operation and a compact space-saving design; the product is described as cascade ready.
The rating table prints 399 MBtu/hr input, 370 MBH output, a 322 MBtu/hr net rating, 92.7% thermal efficiency and 87.7% combustion efficiency (no AFUE row is printed), with a 2"–14" W.C. gas pressure range, 4–72 GPM flow (4 GPM at 100% input), 20–100°F temperature rise, 0–100 equivalent feet of vent and air-inlet piping, 7.125 gallons of water, a 4" flue, 5 A current FLA and 10.6 boiler horsepower. Combustion is direct spark and venting is sealed-combustion direct vent.
The Cast 92-4 shares the HeatNet text-display control with the Cast 92-2 (cascade-capable with one master and up to 15 members, Modbus RS485 per the I&O manual). The official site groups the product under 'Out of Circulation', so productStatus is 'discontinued'; Boilers.ca documents the printed model row from the product page and the C928000 R1 I&O manual. No official Canadian-sales statement was found, so canadianStatus stays 'unknown'.
Best suited to
- Owners documenting an installed Cast 92-4 against the official rating table
- Service planning for cascade HeatNet installations and sealed-combustion venting
- Legacy replacement research in the 399-MBH-input condensing class
Applicability and support
- Model number
- 92-4
- Canadian availability
- unknown
- Production status
- discontinued
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Not verified
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Peerless Boilers. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Input | 80–399 MBH | CSA input range 80,000–399,000 Btuh per the Cast 92 catalog; the product-page rating table prints the 399 MBH maximum row. |
| Output | ||
| Output | 370 MBH | Output per the rating table on the Cast 92-4 product page. |
| Net rating | 322 MBH | Net rating per the rating table on the Cast 92-4 product page. |
| Efficiency | ||
| Thermal efficiency | 92.7 % | 92.7% thermal efficiency and 87.7% combustion efficiency printed on the Cast 92-4 rating table (no AFUE row is printed). |
| Domestic hot water | ||
| Domestic hot water | Heating-only boiler — domestic hot water comes from a separate indirect tank or water heater | |
| Venting and air | ||
| Venting | Sealed combustion, direct vent — 4" flue | 4" flue diameter; up to 100 equivalent feet of vent and air inlet length per the rating table. |
| Physical and connections | ||
| Water volume | 7.125 gal | Water volume per the rating table on the Cast 92-4 product page. |
| Electrical | ||
| Electrical | 120VAC/60Hz/1PH, 5 A | Voltage and current FLA per the rating table on the Cast 92-4 product page. |
| Operating limits and other | ||
| Gas pressure (W.C.) | 2"–14" | Gas pressure range per the rating table on the Cast 92-4 product page. |
| Flow | 4–72 GPM | Flow range per the rating table; 4 GPM marked at 100% input. |
| Boiler H.P. | 10.6 | Boiler horsepower per the rating table on the Cast 92-4 product page. |
| Ignition | Direct spark | Direct-spark combustion per the product page product details; HeatNet text-display control; cascade ready. |
Manuals
- Cast 92 Gas Boilers Installation, Operation & Maintenance Manual (C928000 R1, 11/13)C928000 R1 · 2013-11
- Cast 92 User's Information Manual (C928001 R0, 5/10)C928001 R0 · 2010-05
- Catalog Literature — Cast 92 (CUT-C92 R2, 3/14)CUT-C92 R2 · 2014-03
Alerts documented for this model
Frequently asked questions
What are the Cast 92-4's ratings?
399 MBtu/hr input, 370 MBH output, a 322 MBtu/hr net rating, 92.7% thermal efficiency and 87.7% combustion efficiency per the rating table on the product page; no AFUE row is printed.
Does the Cast 92-4 need a chimney?
No — it is a sealed-combustion, direct-vent condensing boiler with a 4" flue and up to 100 equivalent feet of vent and air-inlet piping.
Can Cast 92-4 boilers be cascaded?
Yes — the product page describes the Cast 92-4 as cascade ready, and the I&O manual documents one master with up to 15 member boilers on the HeatNet control.
Questions about the Peerless Cast 92-4?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Sources and verification
- Peerless Boilers — Cast 92-4 product page (rating table) · accessed September 9, 2026
- Cast 92 Gas Boilers Installation, Operation & Maintenance Manual, C928000 R1 (11/13) (PDF) · C928000 R1 · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.