Bosch Thermotechnology · Buderus GB162

Buderus GB162-100 kW

The Buderus GB162-100 kW is the largest North American GB162: 72,000 to 333,000 BTU/hr natural-gas input and 295,000 BTU/hr CSA output, with BTS 2000 efficiency figures (96.1 part load) in place of an AFUE row, in the same 154 lb wall cabinet as the 80 kW.

CurrentSold in Canada

Key figures

Max input
333 MBH
Max CSA output
AFUE
Min input
72 MBH
Natural gasPropaneHeating-onlyresidentialcommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Buderus GB162-100 kW in practice

The GB162-100 kW is the top of the two-model North American GB162 range and the size a cascade plant is usually built from: natural-gas input runs 72,000 to 333,000 BTU/hr (62,000 to 315,000 on propane) with a 295,000 BTU/hr CSA output. Bosch's CA product page describes cascades linking typically two to four boilers, expandable to eight, and claims a four-boiler cascade delivering over 1,000 MBH can fit in less than 13 square feet of floor space.

Efficiency documentation differs from the 80 kW: the service-manual appendix prints no AFUE row for the 100 kW and instead lists BTS 2000 figures of 96.1 (part load) and 90.8 (full load) at 80/180 °F, alongside the family-level 'up to 93% AFUE' claim on the CA product page. Physical data matches the 80 kW: 50.4 x 20.5 x 18.3 in cabinet, 154 lb (70 kg) without the pump group, 4" flue connection (4"/4" parallel for room-air-independent runs).

The 100 kW runs the same UBA 3/BC10 control package as the 80 kW with its two-character-plus-sub-code fault display and LED state column. Like its sibling it is still a current CA catalog product while the US catalog lists the GB162 as discontinued — a cross-border status difference buyers should confirm with Bosch Thermotechnology Corp.

Best suited to

  • Large residences and light-commercial plants at the top of the GB162 range
  • Cascade designs needing the 100 kW unit as the building block
  • Installations where the same 154 lb wall cabinet must deliver up to 333 MBH input

Applicability and support

Model number
GB162-100 kW
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Bosch Thermotechnology. Units are shown with every value; notes flag conflicting sources or missing figures.

Buderus GB162-100 kW specifications
SpecificationValueNote
Input
Rated thermal load, minimum (NG)72 MBH72,000 BTU/hr natural gas; 62,000 BTU/hr propane.
Rated thermal load, maximum (NG)333 MBH333,000 BTU/hr natural gas; 315,000 BTU/hr propane.
Output
CSA output295 MBH295,000 BTU/hr (NG) per the service-manual appendix.
Efficiency
Efficiency (BTS 2000 at 80/180 °F)96.1 part load / 90.8 full loadThe 100 kW model carries BTS 2000 figures instead of an AFUE row in the service-manual appendix. CA product page states 'up to 93% AFUE' for the family.
Venting and air
Flue gas connection4" (100 mm); 4"/4" (100 mm) parallel for room-air-independentFree fan feed pressure 0.883 in w.c. (220 Pa) per the IOM.
Physical and connections
Weight (without packaging)154 lb154 lb (70 kg) without a pump group per the IOM and service manual. The CA product page copy says 'only 150 lbs each'.
Dimensions (W x H x D)50.4 × 20.5 × 18.3 in (1280 × 520 × 465 mm), height × width × depth, with pump groupPer the manual technical data table.
Maximum flow temperature180 °F180 °F (82 °C) per the IOM; the service-manual appendix prints 190 °F (88 °C) — a doc-vs-doc difference noted by Boilers.ca.
Maximum working pressure (boiler)50 psi50 psi (3.6 bar).
Heating circuit volume of heat exchanger1.3 gal1.3 gal (5.0 l).
Pump group pumpUP 26-99Per the IOM technical specifications.
Electrical
Electrical power consumption, full load156 WWithout a pump group.
Electrical power consumption, partial load29 WWithout a pump group.
Operating limits and other
FuelNatural gas or propaneSeparate NG and LPG ratings in the manual; LPG requires the gas conversion kit included with the appliance.
Derate above sea level2.1% per 1,000 ft (NG)NG 100 kW row per the service-manual appendix; propane 2.0%.

Frequently asked questions

What is the CSA output of the GB162-100 kW?

295,000 BTU/hr on natural gas per the service-manual appendix, with input from 72,000 to 333,000 BTU/hr (315,000 on propane).

Why does the 100 kW not have an AFUE number?

The service-manual appendix prints BTS 2000 figures for the 100 kW (96.1 part load, 90.8 full load at 80/180 °F) instead of an AFUE row, while the 80 kW gets AFUE 93.8/93.9. Bosch's CA page claims 'up to 93% AFUE' for the GB162 family.

Can the GB162-100 kW be cascaded?

Yes — cascading is the GB162's design focus per Bosch's CA page: typically two to four boilers, expandable up to eight, with common venting of up to four.

Questions about the Buderus GB162-100 kW?