Bosch Thermotechnology · Buderus GB162

Buderus GB162-80 kW

The Buderus GB162-80 kW is the smaller of the two North American GB162 sizes: 72,000 to 290,000 BTU/hr natural-gas input, 261,000 BTU/hr CSA output, 93.8/93.9 AFUE at 80/180 °F, in a 154 lb wall-hung Logamax plus cabinet with 4" flue connection.

CurrentSold in Canada

Key figures

Max input
290 MBH
Max CSA output
—
AFUE
93.8 %
Min input
72 MBH
Natural gasPropaneHeating-onlyresidentialcommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Buderus GB162-80 kW in practice

The GB162-80 kW is one of only two GB162 sizes sold in North America (the European catalog has more), and the CA catalog still lists the GB162 as current. It modulates 72,000 to 290,000 BTU/hr natural-gas input (62,000 to 270,000 on propane), carries a 261,000 BTU/hr CSA output and reaches 93.8/93.9 AFUE at 80/180 °F per the service-manual appendix — the figure behind Bosch's 'up to 93% AFUE' CA page copy.

The wall-hung cabinet measures 50.4 x 20.5 x 18.3 in with the pump group and weighs 154 lb (70 kg) without one — Bosch's CA page copy claims 'only 150 lbs each', a figure Boilers.ca flags against the manual's 154 lb. Gas connection is Rp 1", heating water is a G 1-1/2" union nut with female thread enclosed, and the condensate connection is 1-1/4" (32 mm).

Controls are the UBA 3 with the BC10 basic controller: two-character service codes with numeric sub-codes, a UBA 3 LED column and reset flags documented in the service instructions, whose chapter 6 carries the diagnosis structure diagrams. Flow temperature is set on the BC10; the IOM's 180 °F maximum and the service appendix's 190 °F maximum are a documented discrepancy to resolve per the edition in hand.

Best suited to

  • Residences and light-commercial plants whose load fits the 80 kW class
  • Cascade plants — the CA page describes cascades of two to four boilers expandable to eight
  • Projects that want the Buderus Logamax plus platform with UBA 3 controls

Applicability and support

Model number
GB162-80 kW
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Bosch Thermotechnology. Units are shown with every value; notes flag conflicting sources or missing figures.

Buderus GB162-80 kW specifications
SpecificationValueNote
Input
Rated thermal load, minimum (NG)72 MBH72,000 BTU/hr natural gas; 62,000 BTU/hr propane.
Rated thermal load, maximum (NG)290 MBH290,000 BTU/hr natural gas; 270,000 BTU/hr propane.
Output
CSA output261 MBH261,000 BTU/hr (NG) per the service-manual appendix.
Efficiency
Efficiency93.8 %AFUE at 80/180 °F: 93.8 (NG) / 93.9 (LP) per the service manual appendix. CA product page states 'up to 93% AFUE'.
Venting and air
Flue gas connection4" (100 mm); 4"/4" (100 mm) parallel for room-air-independentFree fan feed pressure 0.602 in w.c. (150 Pa) per the IOM.
Physical and connections
Weight (without packaging)154 lb154 lb (70 kg) without a pump group per the IOM and service manual. The CA product page copy says 'only 150 lbs each'.
Dimensions (W x H x D)50.4 × 20.5 × 18.3 in (1280 × 520 × 465 mm), height × width × depth, with pump groupPer the manual technical data table.
Maximum flow temperature180 °F180 °F (82 °C) per the IOM; the service-manual appendix prints 190 °F (88 °C) — a doc-vs-doc difference noted by Boilers.ca.
Maximum working pressure (boiler)50 psi50 psi (3.6 bar).
Heating circuit volume of heat exchanger1.3 gal1.3 gal (5.0 l).
Pump group pumpUP 26-99Per the IOM technical specifications.
Electrical
Electrical power consumption, full load104 WWithout a pump group.
Electrical power consumption, partial load29 WWithout a pump group.
Operating limits and other
FuelNatural gas or propaneSeparate NG and LPG ratings in the manual; LPG requires the gas conversion kit included with the appliance.
Derate above sea level2.3% per 1,000 ft (NG)NG 80 kW row per the service-manual appendix; propane 2.2%.

Frequently asked questions

How big is the GB162-80 kW?

72,000 to 290,000 BTU/hr natural-gas input with 261,000 BTU/hr CSA output, in a 50.4 x 20.5 x 18.3 in wall cabinet weighing 154 lb (70 kg) without the pump group.

Is the GB162-80 kW rated for propane?

Yes — the manuals print propane ratings (62,000 to 270,000 BTU/hr input) and describe conversion; the factory gas setting is natural gas.

Where does the 93% AFUE figure come from?

Bosch's CA product page states 'Efficiency up to 93% AFUE'; the service-manual appendix prints 93.8 (NG) / 93.9 (LP) AFUE at 80/180 °F for the 80 kW model.

Questions about the Buderus GB162-80 kW?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 7, 2026. Last updated September 7, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate