IBC EX 400
The IBC EX 400 is the smallest floor-standing EX Series commercial boiler: 40–399 MBH input, 388 MBH output, 97.9% thermal efficiency, 4" venting to 170 equivalent feet and 2" NPT-M water connections.
Key figures
- Max input
- 399 MBH
- Max CSA output
- 388 MBH
- AFUE
- —
- Min input
- 40 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
IBC EX 400 in practice
The EX 400 opens IBC's floor-standing EX Series at 40–399 MBH CSA input (11.7–117 kW) with 388 MBH CSA output (114 kW) and the line's highest thermal efficiency, 97.9% to ANSI/AHRI-1500. IBC markets the series with a touchscreen control, remote access, multi-boiler communication and 10:1 turndown.
It uses a 4" Schedule 40 flue and 4" combustion air, both with 170 equivalent feet of vent per side and direct-vent or indoor air supply, and 2" NPT-M water connections. At approximately 414 lb (188 kg) empty it is the lightest EX model, with 55.3 ft² (5.14 m²) of heating surface, 13.5 USG (51.1 L) of vessel water and a 10 USgpm minimum flow against the series' 100 USgpm maximum.
All EX models are rated 160 psig maximum operating pressure with a 50 psig relief valve supplied; alternative 30, 100, 125 and 150 psig relief valves are available, and installation is approved to 12,000 ft altitude. Documentation includes the EX I&O manual 120-327E10.
Best suited to
- Commercial buildings whose load fits 388 MBH output
- Plants wanting the EX line's highest 97.9% thermal efficiency
- Mechanical rooms with 4" flue and up to 170 equivalent feet of vent per side
Applicability and support
- Model number
- EX 400
- Canadian availability
- available
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Not verified
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by IBC Technologies. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| CSA input, minimum | 40 MBH | 11.7 kW |
| CSA input, maximum | 399 MBH | 117 kW |
| Output | ||
| CSA output | 388 MBH | 114 kW |
| Efficiency | ||
| Thermal efficiency (ANSI/AHRI-1500) | 97.9 % | |
| Venting and air | ||
| Max. equivalent vent length, each side | 170 ft | |
| Flue / combustion air | 4" Schedule 40 flue / 4" Schedule 40 combustion air | |
| Air intake | Direct vent or indoor supply | |
| Physical and connections | ||
| Weight (empty) | 414 lb | Approx. 188 kg |
| Heating surface area | 55.3 ft² / 5.14 m² | |
| Pressure vessel water content | 13.5 USG / 51.1 L | |
| Water connections | 2" NPT-M | |
| Gas connection | 1" NPT-F | |
| Condensate connection | 3/4" hose | |
| Electrical | ||
| Power use at full fire (less pumps) | 150 W | 120 V / 60 Hz. |
| Operating limits and other | ||
| Minimum boiler flow rate | 10 USgpm | |
| Fuel | Natural gas or propane | CSA input is rated for natural gas or propane on IBC's EX commercial specification table. |
| Gas supply pressure | 4 – 14 in. w.c. | |
| Ambient temperature | 32 – 122 °F | 0 – 50°C. |
| Minimum water temperature | 34 °F | 1°C. |
| Max. water temperature (electronic hi-limit) | 190 °F | 88°C; lockout limit 201°F / 94°C. |
| Max. ΔT supply/return | 80 °F | 44°C electronic fence. |
| Maximum boiler flow rate | 100 USgpm / 378 Lpm | |
| Max. operating water pressure | 160 psig | 1,103 kPa. |
| Minimum water pressure | 8 psig | 55 kPa. |
| Relief valve (supplied) | 50 psig | 345 kPa; alternative 30, 100, 125 and 150 psig relief valves are available. |
| Altitude rating | 0 – 12,000 ft | |
Manuals
Alerts documented for this model
- Ignition Trials Exceeded
- Water High Limit
- Low Water Cutoff
- Interlock 1 or 2 Open
- Vent High Limit
- Max. delta T Exceeded
- Fan Pressure
- High/Low Gas Press
- Module High Current
- Low Module Current
- Low Water Pressure
- Inlet Pres. Sensor
- See: Status > SIM menu > Status
- Roll Out Switch
- Controller Board
- No Boilernet Comm
- No MAC address
- [Vent High Pressure]
- Flame Signal / Vent Block
- Reversed Flow
- Temp. probe error
- Unhandled error code
- Blank – screen dark
- Service mode after update
- Water High Limit / Low Water Cutoff won't clear
- Outlet Limited
- Remote offline
- Unoccupied
- Summer
- Failsafe Setpoint
- Sensor
Frequently asked questions
What efficiency does the EX 400 reach?
97.9% thermal efficiency to ANSI/AHRI-1500, the highest in the EX Series.
What venting does the EX 400 use?
4" Schedule 40 flue and 4" Schedule 40 combustion air, with 170 equivalent feet per side and direct-vent or indoor supply.
What water connections does the EX 400 have?
2" NPT-M, per the EX commercial specification table.
Questions about the IBC EX 400?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Sources and verification
- IBC EX Series — series page (Canada) · accessed September 9, 2026
- IBC Technical Information Portal — EX commercial specification table · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.