IBC EX 700

The IBC EX 700 is a floor-standing commercial condensing boiler rated 70–700 MBH input and 679 MBH output at 97.0% thermal efficiency, with a 6" flue, 2½" NPT-M water connections and 120 equivalent feet of vent per side.

CurrentSold in Canada

Key figures

Max input
700 MBH
Max CSA output
679 MBH
AFUE
Min input
70 MBH
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

IBC EX 700 in practice

The EX 700 covers 70–700 MBH CSA input (20.5–205 kW) with 679 MBH CSA output (199 kW) at 97.0% thermal efficiency to ANSI/AHRI-1500. It is the first EX size to move to the larger connection group: a 6" Schedule 40 flue and 2½" NPT-M water connections, with combustion air supplied through a 4" collar that IBC requires to transition to 6" within three feet.

Vent length is capped at 120 equivalent feet per side — shorter than the EX 400/500's 170 feet — with direct-vent or indoor air supply. The unit weighs approximately 486 lb (220 kg) empty, has 84.6 ft² (7.86 m²) of heating surface and holds 17.5 USG (66.3 L) of water, the largest vessel in the line, with an 18 USgpm minimum flow against the series' 100 USgpm maximum.

The EX 700 shares the series' touchscreen control, remote access, multi-boiler communication and 10:1 turndown, and its 160 psig maximum operating pressure rating comes with a supplied 50 psig relief valve (30, 100, 125 and 150 psig alternatives are available). The EX I&O manual is 120-327E10.

Best suited to

  • Larger commercial buildings whose load fits 679 MBH output
  • Projects able to run 6" flue and within 120 equivalent feet per side
  • Plants that need 2½" NPT-M water connections

Applicability and support

Model number
EX 700
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by IBC Technologies. Units are shown with every value; notes flag conflicting sources or missing figures.

IBC EX 700 specifications
SpecificationValueNote
Input
CSA input, minimum70 MBH20.5 kW
CSA input, maximum700 MBH205 kW
Output
CSA output679 MBH199 kW
Efficiency
Thermal efficiency (ANSI/AHRI-1500)97 %
Venting and air
Max. equivalent vent length, each side120 ft
Flue / combustion air6" Schedule 40 flue / 4" Schedule 40 combustion airIBC requires the combustion air to transition to 6" within three feet of the 4" collar.
Air intakeDirect vent or indoor supply
Physical and connections
Weight (empty)486 lbApprox. 220 kg
Heating surface area84.6 ft² / 7.86 m²
Pressure vessel water content17.5 USG / 66.3 L
Water connections2½" NPT-M
Gas connection1" NPT-F
Condensate connection3/4" hose
Electrical
Power use at full fire (less pumps)195 W120 V / 60 Hz.
Operating limits and other
Minimum boiler flow rate18 USgpm
FuelNatural gas or propaneCSA input is rated for natural gas or propane on IBC's EX commercial specification table.
Gas supply pressure4 – 14 in. w.c.
Ambient temperature32 – 122 °F0 – 50°C.
Minimum water temperature34 °F1°C.
Max. water temperature (electronic hi-limit)190 °F88°C; lockout limit 201°F / 94°C.
Max. ΔT supply/return80 °F44°C electronic fence.
Maximum boiler flow rate100 USgpm / 378 Lpm
Max. operating water pressure160 psig1,103 kPa.
Minimum water pressure8 psig55 kPa.
Relief valve (supplied)50 psig345 kPa; alternative 30, 100, 125 and 150 psig relief valves are available.
Altitude rating0 – 12,000 ft

Frequently asked questions

What size flue does the EX 700 use?

A 6" Schedule 40 flue; combustion air enters through a 4" collar and IBC requires the transition to 6" within three feet.

How long can the EX 700 vent run?

120 equivalent feet per side, with direct-vent or indoor air supply.

What water connections does the EX 700 have?

2½" NPT-M, per the EX commercial specification table.

Questions about the IBC EX 700?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.