IBC EX 850

The IBC EX 850 is the largest EX Series boiler: 85–850 MBH input, 824.5 MBH output at 97.0% thermal efficiency, a 6" flue, 2½" NPT-M water connections and 120 equivalent feet of vent per side.

CurrentSold in Canada

Key figures

Max input
850 MBH
Max CSA output
824.5 MBH
AFUE
—
Min input
85 MBH
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

IBC EX 850 in practice

The EX 850 tops the EX Series at 85–850 MBH CSA input (24.9–249 kW) with 824.5 MBH CSA output (241.6 kW) at 97.0% thermal efficiency to ANSI/AHRI-1500, matching the EX 700's efficiency. It shares the 700's connection group: a 6" Schedule 40 flue, 4" combustion air that must transition to 6" within three feet, and 2½" NPT-M water connections.

Venting is limited to 120 equivalent feet per side, with direct-vent or indoor air supply. At approximately 510 lb (231 kg) empty it is the heaviest EX model, with 99.88 ft² (9.28 m²) of heating surface and 16.4 USG (62.0 L) of vessel water; the minimum flow is 21 USgpm against the series' 100 USgpm maximum.

Like every EX model it carries the touchscreen control, remote access, multi-boiler communication and 10:1 turndown, and is rated 160 psig maximum operating pressure with a supplied 50 psig relief valve (30, 100, 125 and 150 psig alternatives are available). The EX I&O manual is 120-327E10.

Best suited to

  • Large commercial buildings needing up to 824.5 MBH output
  • Projects planning multi-boiler EX plants with 10:1 turndown
  • Mechanical rooms able to run 6" flue within 120 equivalent feet per side

Applicability and support

Model number
EX 850
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by IBC Technologies. Units are shown with every value; notes flag conflicting sources or missing figures.

IBC EX 850 specifications
SpecificationValueNote
Input
CSA input, minimum85 MBH24.9 kW
CSA input, maximum850 MBH249 kW
Output
CSA output824.5 MBH241.6 kW
Efficiency
Thermal efficiency (ANSI/AHRI-1500)97 %
Venting and air
Max. equivalent vent length, each side120 ft
Flue / combustion air6" Schedule 40 flue / 4" Schedule 40 combustion airIBC requires the combustion air to transition to 6" within three feet of the 4" collar.
Air intakeDirect vent or indoor supply
Physical and connections
Weight (empty)510 lbApprox. 231 kg
Heating surface area99.88 ft² / 9.28 m²
Pressure vessel water content16.4 USG / 62.0 L
Water connections2½" NPT-M
Gas connection1" NPT-F
Condensate connection3/4" hose
Electrical
Power use at full fire (less pumps)228 W120 V / 60 Hz.
Operating limits and other
Minimum boiler flow rate21 USgpm
FuelNatural gas or propaneCSA input is rated for natural gas or propane on IBC's EX commercial specification table.
Gas supply pressure4 – 14 in. w.c.
Ambient temperature32 – 122 °F0 – 50°C.
Minimum water temperature34 °F1°C.
Max. water temperature (electronic hi-limit)190 °F88°C; lockout limit 201°F / 94°C.
Max. ΔT supply/return80 °F44°C electronic fence.
Maximum boiler flow rate100 USgpm / 378 Lpm
Max. operating water pressure160 psig1,103 kPa.
Minimum water pressure8 psig55 kPa.
Relief valve (supplied)50 psig345 kPa; alternative 30, 100, 125 and 150 psig relief valves are available.
Altitude rating0 – 12,000 ft

Frequently asked questions

How much output does the EX 850 deliver?

824.5 MBH CSA output (241.6 kW) from 85–850 MBH input (24.9–249 kW), per IBC's EX commercial specification table.

Is the EX 850 more efficient than the EX 700?

No. Both are rated 97.0% thermal efficiency to ANSI/AHRI-1500; the EX 400 (97.9%) and EX 500 (97.5%) are higher.

What is the EX 850's minimum flow?

21 USgpm, the highest minimum in the EX Series; the maximum is 100 USgpm for all four models.

Questions about the IBC EX 850?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.