Skip to content
Boilers.caby ROMA Heating & Cooling

IBC Technologies · Series

IBC Technologies SL Series G3 Commercial

The SL Series G3 Commercial is IBC's light-commercial condensing boiler line, sold in Canada as the SL 26-260 G3 and SL 40-399 G3 (with an optional 316Ti titanium heat exchanger on the 40-399). It is a separate documentation set from the residential SL G3: the commercial I&O manual is 120-270E12.

Current seriesSold in CanadaNatural gasPropanecommercial

Series facts

Type
condensing
Efficiency
96% thermal-efficiency
Fuel
The commercial specification table rates CSA input for natural gas or propane.
Venting
3" (SL 26-260 G3) or 4" (SL 40-399 G3) Schedule 40 / rigid PPs flue, 200 equivalent feet each side; direct vent or indoor air supply. IBC's model pages also list PVC, CPVC and PPs approval.
Models documented
2

The SL 26-260 G3 is rated 95% AFUE; the SL 40-399 G3 is rated 96% combustion and 96% thermal efficiency (ANSI/AHRI-1500) with no published AFUE.

About the SL Series G3 Commercial

The commercial SL G3 line covers the two largest SL G3 sizes: the SL 26-260 G3 and the SL 40-399 G3, rated 26–260 and 40–399 MBH CSA input. IBC describes them as suitable for large residential or light commercial applications, and they are documented in their own commercial I&O manual (120-270E12) rather than the residential SL G3 manual (120-276E13).

Both models use the V-10 touchscreen controller with true native BACnet, remote monitoring and diagnostics, USB programmability and a visible flame-current display. IBC states the boilers can network up to 24 units and 9.5 MMBtu/h without additional controls; with 24 SL 40-399 G3 boilers the published turndown is 240:1, from 40,000 Btu/h to 9.5 MMBtu/h in 1,000 Btu/h increments. Built-in control covers up to four zone pumps, and DDC 0-10 VDC or 4-20 mA is available without extra controls.

Efficiency is published per size: 95% AFUE on the SL 26-260 G3, and 96% combustion / 96% thermal efficiency (ANSI/AHRI-1500) on the SL 40-399 G3. Venting is 3" on the 260 and 4" on the 399, each allowed 200 equivalent feet per side with direct-vent or indoor air supply; IBC's marketing copy states PVC/CPVC/PPs approval and venting up to 400 feet (200 feet per side). An optional 316Ti titanium-enhanced heat exchanger is available on the SL 40-399 G3. IBC lists MFZ moisture management and reverse-flow detection among the series features.

Highlights

  • SL 26-260 G3 and SL 40-399 G3, 26–260 and 40–399 MBH CSA input
  • 95% AFUE on the 260; 96% combustion and thermal efficiency on the 399
  • V-10 touchscreen controller with true native BACnet and DDC 0-10 VDC / 4-20 mA
  • Network up to 24 boilers / 9.5 MMBtu/h without additional controls
  • 3" or 4" Schedule 40 / rigid PPs venting, 200 equivalent feet each side
  • Optional 316Ti titanium heat exchanger on the SL 40-399 G3
  • Up to 10-year commercial heat-exchanger warranty per IBC's feature list

IBC's SL G3 commercial feature list states up to a 10-year commercial heat-exchanger warranty on these models; the detailed terms are set out in IBC's warranty documents rather than the product pages captured for this record.

Models

SL Series G3 Commercial models

One canonical page per model with input, output and efficiency kept separate.

IBC Technologies

IBC SL 26-260 G3

CurrentSold in Canada
Input
26–260 MBH
Output (max)
239 MBH
AFUE
95 %

The IBC SL 26-260 G3 is the smaller of IBC's two commercial SL G3 boilers: 26 to 260 MBH CSA input, 24.9 to 239 MBH CSA output, 95% AFUE, 3" venting to 200 equivalent feet per side and 1 1/2" NPT-M water connections.

Natural gasPropaneHeating-only

IBC Technologies

IBC SL 40-399 G3

CurrentSold in Canada
Input
40–399 MBH
Output (max)
383 MBH
AFUE
—

The IBC SL 40-399 G3 is the larger commercial SL G3 boiler: 40 to 399 MBH CSA input, 38.4 to 383 MBH output, 96% combustion and 96% thermal efficiency, 4" venting to 200 equivalent feet and an optional 316Ti titanium heat exchanger.

Natural gasPropaneHeating-only

Compare models in this series

Comparison of IBC SL 26-260 G3 and IBC SL 40-399 G3
SpecificationIBC SL 26-260 G3IBC SL 40-399 G3
CSA input, minimum26 MBH40 MBH
CSA input, maximum260 MBH399 MBH
CSA output, maximum239 MBH383 MBH
Efficiency (AFUE)95 %—
turndown——
vent-max-3——
vent-max-2——
Weight (empty)162 lb240 lb

Read the full comparison: IBC SL 26-260 G3 vs SL 40-399 G3 →

Error codes and alerts

SL Series G3 Commercial alerts

Manuals

Official documents

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Frequently asked questions

What is the difference between the SL G3 commercial and residential models?

IBC publishes the SL 26-260 G3 and SL 40-399 G3 as the commercial models, with their own I&O manual (120-270E12); the residential SL G3 line covers 85–199 MBH and is documented in manual 120-276E13. The 260 and 399 are the two largest SL G3 sizes.

Is there a titanium heat-exchanger option?

Yes. IBC lists an optional 316Ti titanium-enhanced heat exchanger for the SL 40-399 G3; the commercial specification table covers it in the same column as the standard SL 40-399 G3.

How many SL G3 commercial boilers can be networked?

IBC's feature list states up to 24 boilers and 9.5 MMBtu/h without additional controls, with 240:1 turndown on a network of 24 SL 40-399 G3 boilers.

Talk to a boiler technician

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate