Skip to content
Boilers.caby ROMA Heating & Cooling

NTI Boilers · Trinity FTG

NTI Trinity FTG600

The NTI Trinity FTG600 is the smallest fire-tube boiler in the FTG family as the Installation and Operation Manual documents it: 80 to 600 MBH input at 96% thermal efficiency, with a 576 MBH heating capacity and a 500 MBH Net I=B=R rating.

CurrentSold in Canada

Key figures

Max input
600 MBH
Max CSA output
AFUE
Min input
80 MBH
Natural gasHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

NTI Trinity FTG600 in practice

The FTG I&O manual (99985422, V.2024-06-28) documents the FTG600 at 80 to 600 MBH input with 97% combustion efficiency and 96% thermal efficiency, a 576 MBH DOE heating capacity and a 500 MBH Net I=B=R rating. NTI's FTG product page omits the FTG600 and FTG800 rows, so these figures come from Table 2-2 of the manual, which covers the full FTG600-to-FTG2400 family.

Physically the FTG600 shares its 33-7/8 in width with the FTG800 but stands 68-1/2 in tall, 38-3/8 in deep and 930 lb with water (17 gallons), on a 1 in NPT gas connection with a 3 in grooved-joint water inlet and 2 in grooved-joint outlet. The 6 in air inlet and 6 in exhaust vent accept the FTG600-800 venting arrangement, whose last 6 ft of exhaust can be reduced to 4 or 5 in, and Canadian installations apply the manual's 10% input derate at 2,000–4,500 ft.

Best suited to

  • Commercial hydronic loads whose demand calculation sits between 80 and 600 MBH
  • Buildings wanting the FTG fire-tube platform's touchscreen control and cascade settings at its smallest documented size
  • Mechanical rooms that can take the 6 in air-inlet and exhaust connections

Applicability and support

Model number
FTG600
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Series terms

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by NTI Boilers. Units are shown with every value; notes flag conflicting sources or missing figures.

NTI Trinity FTG600 specifications
SpecificationValueNote
Input
Input, minimum80 MBHPer the FTG Installation and Operation Manual, Table 2-2.
Input, maximum600 MBHPer the FTG Installation and Operation Manual, Table 2-2.
Output
Heating capacity576 MBHPer the FTG I&O manual, Table 2-2.
Net AHRI rating500 MBHPer the FTG I&O manual, Table 2-2.
Efficiency
Combustion efficiency97 %Per the FTG I&O manual, Table 2-2.
Thermal efficiency96 %Per the FTG I&O manual, Table 2-2.
Domestic hot water
Domestic hot waterHeating-only; pair with an indirect tank or separate water heater
Venting and air
Air inlet size6 inDiameter per the FTG I&O manual, Table 2-1; runs up to 150 ft.
Flue size6 inDiameter per the FTG I&O manual, Table 2-1; runs up to 150 ft.
Physical and connections
Weight, with water930 lbPer the FTG I&O manual, Table 2-1; the NTI product page omits the FTG600 row entirely.
Water connections (inlet / outlet)3" grooved joint inlet / 2" grooved joint outletPer the FTG I&O manual, Table 2-1.
Gas connection1" NPTPer the FTG I&O manual, Table 2-1.
Operating limits and other
Canada altitude derate10% derate at 2,000–4,500 ftPer the FTG Installation and Operation Manual.
FuelNatural gasInput ratings per the NTI product page.

Manuals

Alerts documented for this model

Services

Frequently asked questions

Is the FTG600 on the NTI product page?

No. The product page's spec table begins at the FTG1200; the FTG600 and FTG800 are documented in the FTG Installation and Operation Manual (99985422), whose Table 2-2 covers both sizes.

What efficiency does the FTG600 have?

The FTG I&O manual prints 97% combustion efficiency and 96% thermal efficiency for the FTG600, with a 576 MBH heating capacity and a 500 MBH Net I=B=R rating.

What connections does the FTG600 use?

A 1 in NPT gas connection, a 3 in grooved-joint water inlet and a 2 in grooved-joint water outlet, with 6 in air-inlet and exhaust connections, per the FTG I&O manual's Table 2-1.

Questions about the NTI Trinity FTG600?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate