Skip to content
Boilers.caby ROMA Heating & Cooling

NTI Boilers · Trinity FTG

NTI Trinity FTG2000

The NTI Trinity FTG2000 is the entry of the 2,000 MBH-class FTG fire-tube boilers: 235 to 2000 MBH input at 96% thermal efficiency, with a 1,920 MBH heating capacity and a 1,670 MBH Net AHRI rating on a 1 1/2" NPT male gas connection.

CurrentSold in Canada

Key figures

Max input
2,000 MBH
Max CSA output
—
AFUE
—
Min input
235 MBH
Natural gasHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

NTI Trinity FTG2000 in practice

NTI lists the FTG2000 at 235 to 2000 MBH input with 96% thermal efficiency — matching the FTG1400's rating on the page table — a heating capacity of 1,920 MBH and a Net AHRI rating of 1,670 MBH. The model steps to the large FTG class: 1,710 lb on the page, 3 in grooved water connections, a 1 1/2 in NPT male gas connection, and 8 in air inlet and flue runs up to 150 ft.

The 2000 also crosses the page's weight line: the FTG Installation and Operation Manual (99985422) lists the 2,000 MBH class at 2,140 lb with water against the page's unqualified 1,710 lb, and the minimum fire jumps from the 1400's 140 MBH to 235 MBH. Canadian installations apply the manual's 10% altitude derate between 2,000 and 4,500 ft, and plant demand rather than spare capacity should drive the choice of this size.

Best suited to

  • Commercial hydronic plants whose demand calculation lands between 235 and 2000 MBH
  • Buildings wanting the 2,000 MBH class with the FTG's touchscreen cascade control
  • Mechanical rooms that can take the larger 1 1/2" NPT male gas connection

Applicability and support

Model number
FTG2000
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Series terms

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by NTI Boilers. Units are shown with every value; notes flag conflicting sources or missing figures.

NTI Trinity FTG2000 specifications
SpecificationValueNote
Input
Input, minimum235 MBHPer the NTI product page.
Input, maximum2,000 MBHPer the NTI product page.
Output
Heating capacity1,920 MBHPer the NTI product page.
Net AHRI rating1,670 MBHPer the NTI product page.
Efficiency
Thermal efficiency96 %Per the NTI product page.
Domestic hot water
Domestic hot waterHeating-only; pair with an indirect tank or separate water heater
Venting and air
Air inlet size8 inDiameter per the NTI product page; air-inlet runs up to 150 ft.
Flue size8 inDiameter per the NTI product page; flue runs up to 150 ft.
Physical and connections
Weight1,710 lbPer the NTI product page; the page row is not qualified as with water.
Weight, with water2,140 lbPer the FTG I&O manual's with-water figure for this size class; the product page prints 1,710 lb.
Water connections (inlet / outlet)3" grooved jointInlet and outlet per the NTI product page.
Gas connection1 1/2" NPT malePer the NTI product page.
Operating limits and other
Canada altitude derate10% derate at 2,000–4,500 ftPer the FTG Installation and Operation Manual.
FuelNatural gasInput ratings per the NTI product page.

Manuals

Alerts documented for this model

Services

Frequently asked questions

How does the FTG2000 differ from the FTG1400?

Input rises from 140–1400 to 235–2000 MBH, heating capacity from 1,344 to 1,920 MBH and the Net AHRI rating from 1,169 to 1,670 MBH; the gas connection steps from 1 1/4" NPT female to 1 1/2" NPT male and the page weight from 1,210 to 1,710 lb.

What is the FTG2000's efficiency?

96% thermal efficiency per the NTI product page — the same figure printed for the FTG1400, and above the 95.6% of the FTG2200.

How much does the FTG2000 weigh with water?

The FTG I&O manual lists the 2,000 MBH class at 2,140 lb with water; the NTI product page prints 1,710 lb without the with-water qualification.

Questions about the NTI Trinity FTG2000?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 8, 2026. Last updated September 8, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate