NTI Trinity FTG800

The NTI Trinity FTG800 is the second-smallest documented FTG fire-tube boiler: 80 to 800 MBH input at 95% thermal efficiency, with a 760 MBH heating capacity and a 660 MBH Net I=B=R rating.

CurrentSold in Canada

Key figures

Max input
800 MBH
Max CSA output
—
AFUE
—
Min input
80 MBH
Natural gasHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

NTI Trinity FTG800 in practice

The FTG I&O manual (99985422, V.2024-06-28) documents the FTG800 at 80 to 800 MBH input with 96% combustion efficiency and 95% thermal efficiency, a 760 MBH DOE heating capacity and a 660 MBH Net I=B=R rating. Together with the FTG600 it sits below the FTG1200 that opens NTI's product-page table, which is why the page's own "800 MBH to 2,350 MBH" headline reads oddly against the table.

The FTG800 shares the FTG600's physical package exactly — 33-7/8 in wide, 68-1/2 in tall and 38-3/8 in deep, 930 lb with water, 17 gallons water content — and the same 1 in NPT gas connection, 3 in inlet and 2 in outlet grooved-joint water connections and 6 in air-inlet/exhaust connections. The manual's 10% Canadian altitude derate for 2,000–4,500 ft and the 4-or-5-in exhaust reduction for the FTG600-800 vent run apply.

Best suited to

  • Commercial hydronic loads whose demand calculation sits between 80 and 800 MBH
  • Plants stepping up from the FTG600 without changing the connection or venting plan
  • Buildings wanting the FTG touchscreen control and cascade settings at the low end of the family

Applicability and support

Model number
FTG800
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Series terms

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by NTI Boilers. Units are shown with every value; notes flag conflicting sources or missing figures.

NTI Trinity FTG800 specifications
SpecificationValueNote
Input
Input, minimum80 MBHPer the FTG Installation and Operation Manual, Table 2-2.
Input, maximum800 MBHPer the FTG Installation and Operation Manual, Table 2-2.
Output
Heating capacity760 MBHPer the FTG I&O manual, Table 2-2.
Net AHRI rating660 MBHPer the FTG I&O manual, Table 2-2.
Efficiency
Combustion efficiency96 %Per the FTG I&O manual, Table 2-2.
Thermal efficiency95 %Per the FTG I&O manual, Table 2-2.
Domestic hot water
Domestic hot waterHeating-only; pair with an indirect tank or separate water heater
Venting and air
Air inlet size6 inDiameter per the FTG I&O manual, Table 2-1; runs up to 150 ft.
Flue size6 inDiameter per the FTG I&O manual, Table 2-1; runs up to 150 ft.
Physical and connections
Weight, with water930 lbPer the FTG I&O manual, Table 2-1; the NTI product page omits the FTG800 row entirely.
Water connections (inlet / outlet)3" grooved joint inlet / 2" grooved joint outletPer the FTG I&O manual, Table 2-1.
Gas connection1" NPTPer the FTG I&O manual, Table 2-1.
Operating limits and other
Canada altitude derate10% derate at 2,000–4,500 ftPer the FTG Installation and Operation Manual.
FuelNatural gasInput ratings per the NTI product page.

Manuals

Alerts documented for this model

Services

Frequently asked questions

How does the FTG800 differ from the FTG600?

Input rises from 80–600 to 80–800 MBH, heating capacity from 576 to 760 MBH and the Net I=B=R rating from 500 to 660 MBH, while thermal efficiency eases from 96% to 95%. The manual lists the same dimensions, 930 lb with water and the same connections for both.

Why is the FTG800 missing from NTI's product page?

The FTG product page's spec table begins at the FTG1200 even though the page headline says the line ranges from 800 MBH; the FTG800 is documented in the FTG Installation and Operation Manual's Table 2-2.

Does the FTG800 need altitude derating in Canada?

Yes. The FTG I&O manual calls for a 10% input derate at Canadian altitudes of 2,000 to 4,500 ft.

Questions about the NTI Trinity FTG800?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification