Peerless PureFire PF-300

The Peerless PureFire PF-300 fires 60 to 300 MBH input with 290 MBH gross output and a 252 MBH net rating at 96.5% thermal efficiency — the 300 MBH commercial-capable size — rated by gross output and thermal efficiency, and not ENERGY STAR certified per the product page — on the stainless-steel, sealed-combustion direct-vent condensing platform.

CurrentCanadian status unknown

Key figures

Max input
300 MBH
Max CSA output
—
AFUE
—
Min input
60 MBH
Natural gasPropaneHeating-onlyresidentialcommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Peerless PureFire PF-300 in practice

The PureFire PF-300 is a stainless-steel, condensing, sealed-combustion direct-vent gas boiler rated at 60–300 MBH input. Its rating row prints 290 MBH gross output and a 252 MBH net rating at 96.5% thermal efficiency (a commercial-section row of the shared residential cut sheet — not an AFUE figure; the PF-300 is not ENERGY STAR certified) in I&O manual Table 12.2 (PF8248-R9) and the residential cut sheet (CUT-PF R11).

The boiler ships in a 25" × 32" × 50" carton at about 255 lb, measures 28-1/8" × 17-3/16" × 40-1/2" (A × B × C) per the dimension table, connects on 1-1/2" NPT supply/return with 3/4" NPT gas, and runs on 120 VAC/60 Hz. Venting is 4" exhaust/air intake (PVC, CPVC, AL29-4C stainless or polypropylene) to a 200-equivalent-foot maximum combined length. The PureFire control shows status in plain English on an LCD, ignition is direct spark, and the product page claims ENERGY STAR certification (the PF-300 excepted) with a 12-year heat exchanger warranty.

Boilers.ca documents this size at model level for service planning and cross-referencing; installation, gas, electrical and venting work belongs with a licensed contractor. No official Canadian-sales statement was found, so canadianStatus stays 'unknown'.

Best suited to

  • 300-MBH-class light-commercial and large-residential loads
  • Plants wanting the PureFire family's 4" venting and 1-1/2" NPT water connections
  • Projects comparing PureFire PF sizes against the PFC commercial line

Applicability and support

Model number
PF-300
Canadian availability
unknown
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Peerless Boilers. Units are shown with every value; notes flag conflicting sources or missing figures.

Peerless PureFire PF-300 specifications
SpecificationValueNote
Input
Input, minimum60 MBHMinimum input per the PureFire ratings table (I&O manual Table 12.2; residential cut sheet).
Input, maximum300 MBHMaximum input per the PureFire ratings table (I&O manual Table 12.2; residential cut sheet). Above 2,000 ft the boiler de-rates 3.5% per additional 1,000 ft with no adjustment to the boiler.
Output
Gross output290 MBHGross output per the commercial-section row of the PureFire ratings table (I&O manual Table 12.2).
Net rating252 MBHNet rating per the PureFire ratings table (I&O manual Table 12.2).
Efficiency
Thermal efficiency96.5 %Thermal efficiency per the cut-sheet commercial row — not an AFUE figure, and the PF-300 is not ENERGY STAR certified (product page).
Domestic hot water
Domestic hot waterHeating-only boiler — domestic hot water comes from a separate indirect tank or water heater
Venting and air
Exhaust vent / air intake4"Exhaust vent and air intake size per I&O manual Table 3.2; total combined exhaust and air-intake length to 200 equivalent feet (Table 3.3/3.4 notes). The exhaust connection is a 3" CPVC female adapter on PF-50–PF-140, and 3" (PF-200/PF-210) or 4" (PF-300/PF-399) male CPVC pipe per Section 3.E.
Approved vent materialsPVC, CPVC, AL29-4C stainless or polypropylene (Category IV, positive pressure)Approved exhaust vent materials per I&O manual Table 3.1; Canadian installations require ULC S636 venting.
Physical and connections
Approx. shipping weight255 lbApproximate carton shipping weight per the cut-sheet table (carton dimensions 25" × 32" × 50").
Dimensions (A × B × C)28-1/8" × 17-3/16" × 40-1/2"Boiler dimensions A, B and C per the I&O manual dimension table (Table 12.1).
Supply/return connections1-1/2" NPTSupply and return connection size per the I&O manual parts/dimension data (brass field couplings sized 1-1/2" NPT).
Gas connection3/4" NPTGas connection per the I&O manual (1/2" NPT manual shut-off valve listed for PF-50–PF-140; 3/4" flexible gas line and 3/4" NPT full-port shut-off valve listed for PF-200–PF-399).
Electrical
Electrical120 VAC, 60 Hz; max total service current to boiler 22.79 ASupply 120 VAC (-15%, +10%), 60 Hz (±1.2 Hz) and maximum total service current to the boiler per I&O manual Table 12.5.
Operating limits and other
ControlPureFire control with plain-English LCD displayLCD control board shows operational status in plain English (product page); control diagnostics use blocking/locking/warning code tables in I&O manual Section 10.
FuelNatural gas or LP gasNatural gas or propane with sulfur content below the limits in I&O manual Section 5; conversion-kit instructions are published on the product page.

Frequently asked questions

What are the PF-300's ratings?

60–300 MBH input, 290 MBH gross output and a 252 MBH net rating at 96.5% thermal efficiency (not AFUE) per the ratings table.

Is the PF-300 a residential or a commercial boiler?

Its rating row prints on the commercial section of the residential PureFire cut sheet with gross output and thermal efficiency, and PB Heat publishes submittal data for it from both the residential and commercial product pages — Boilers.ca records applications as residential and commercial.

Why do the PF-300 and PF-399 print different efficiency figures?

Their rows print gross output and thermal efficiency (96.5% and 95.2%) instead of AFUE — the commercial rating convention used for the shared cut sheet's PF-300/PF-399/PFC-460 rows.

Questions about the Peerless PureFire PF-300?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate