Skip to content
Boilers.caby ROMA Heating & Cooling

Peerless Boilers · Series

Peerless Boilers PureFire

The Peerless PureFire is the brand's current stainless-steel, gas condensing boiler line, sold for residential/light-commercial use: modulating models PF-50 through PF-210 (50–210 MBH maximum input) at 95.0–95.1% AFUE, plus PF-300 and PF-399 sizes whose cut-sheet rows print 96.5%/95.2% thermal efficiency, on a direct-vent sealed-combustion system with a plain-English LCD control.

Current seriesunknownNatural gasPropaneresidentialcommercial

Series facts

Type
condensing
Efficiency
95.1% AFUE
Fuel
Natural or LP gas — the official site and the PF-50–PF-399 I&O manual (PF8248-R9) state the PureFire runs on natural gas or propane; the user- or installer-fitted conversion arrangements are covered in the conversion-kit literature on the product page.
Venting
Direct vent, sealed combustion (Category IV, positive pressure): exhaust and air intake 3" on PF-50 through PF-210 and 4" on PF-300/PF-399, to a maximum total combined length of 200 equivalent feet (I&O manual Tables 3.2–3.4). Approved pipe includes PVC, CPVC, AL29-4C stainless and polypropylene systems; Canadian installations require ULC S636 venting.
Models documented
8
Warranty
Not verified

Residential models print 95.0% AFUE (PF-50 through PF-200) and 95.1% AFUE (PF-210) in I&O manual Table 12.2 and the residential cut sheet. The PF-300 and PF-399 rows on the same cut sheet print gross output with thermal efficiency of 96.5% and 95.2% — thermal-efficiency figures, not AFUE — and the PF-300 is not ENERGY STAR certified.

About the PureFire

The PureFire is Peerless' current condensing gas boiler, published on the official site under Residential Boilers – Gas Boilers with copy positioning it for 'residential/light commercial applications'. It is a stainless-steel (316L heat exchanger), direct-vent sealed-combustion boiler with a fully modulating pre-mixed burner, direct spark ignition and a PureFire control with an LCD that shows operational status in plain English. The product page claims ENERGY STAR certification with one starred exception: the PF-300 model is not ENERGY STAR certified. PB Heat backs the line with a one-year parts-and-labour warranty upon product registration and a 12-year heat exchanger warranty per the product page.

Eight sizes carry PF model numbers in the PF-50–PF-399 I&O manual (PF8248-R9): PF-50, PF-80, PF-110, PF-140, PF-200, PF-210, PF-300 and PF-399. PF-50 through PF-210 are the residential rating rows (95.0% AFUE, with the PF-210 printing 95.1%); PF-300 and PF-399 rows print gross output and thermal efficiency (96.5% and 95.2%) on the same cut sheet, which also prints the commercial PFC-460 row. Inputs run 16–50 MBH on the PF-50 up to 80–399 MBH on the PF-399, venting is 3" (PF-50–PF-210) or 4" (PF-300/PF-399) to 200 equivalent feet, and the boilers can be wall mounted or floor standing per the I&O manual.

Ratings de-rate 3.5% per additional 1,000 ft above 2,000 ft elevation with no adjustment to the boiler (I&O manual Table 12.2 note). Boilers.ca documents all eight PF models at model level from the I&O manual and the residential cut sheet (CUT-PF R11, 8/25). No official Canadian-sales statement was found — the research reviewed US-site data only — so canadianStatus stays 'unknown'.

Highlights

  • Current Peerless gas condensing line: PF-50 to PF-399 (16–50 up to 80–399 MBH input)
  • Residential rows print 95.0–95.1% AFUE; PF-300/PF-399 rows print 96.5%/95.2% thermal efficiency
  • Stainless-steel (316L) heat exchanger; sealed-combustion direct vent, Category IV positive pressure
  • Direct vent 3" (PF-50–PF-210) or 4" (PF-300/PF-399), up to 200 equivalent feet
  • ENERGY STAR certified except the PF-300 model (product page); 12-year heat exchanger warranty claim
  • Wall-mountable or floor-standing installation; cascade capable; plain-English LCD control
  • Model-level pages published on Boilers.ca; I&O manual PF8248-R9 and cut sheet linked here

Models

PureFire models

One canonical page per model with input, output and efficiency kept separate.

Peerless Boilers

Peerless PureFire PF-50

CurrentCanadian status unknown
Input
16–50 MBH
Output (max)
—
AFUE
95 %

The Peerless PureFire PF-50 fires 16 to 50 MBH input with 47 MBH heating capacity and a 41 MBH net water rating at 95% AFUE — the smallest PureFire size and the entry point for the stainless condensing line — on the stainless-steel, sealed-combustion direct-vent condensing platform.

Natural gasPropaneHeating-only

Peerless Boilers

Peerless PureFire PF-80

CurrentCanadian status unknown
Input
20–80 MBH
Output (max)
—
AFUE
95 %

The Peerless PureFire PF-80 fires 20 to 80 MBH input with 75 MBH heating capacity and a 65 MBH net water rating at 95% AFUE — a mid-small size sharing the compact cabinet of the PF-50 — on the stainless-steel, sealed-combustion direct-vent condensing platform.

Natural gasPropaneHeating-only

Peerless Boilers

Peerless PureFire PF-110

CurrentCanadian status unknown
Input
27.5–110 MBH
Output (max)
—
AFUE
95 %

The Peerless PureFire PF-110 fires 27.5 to 110 MBH input with 103 MBH heating capacity and a 90 MBH net water rating at 95% AFUE — the first of the wider mid-range cabinets (21 × 23 × 36 inch carton) — on the stainless-steel, sealed-combustion direct-vent condensing platform.

Natural gasPropaneHeating-only

Peerless Boilers

Peerless PureFire PF-140

CurrentCanadian status unknown
Input
35–140 MBH
Output (max)
—
AFUE
95 %

The Peerless PureFire PF-140 fires 35 to 140 MBH input with 131 MBH heating capacity and a 114 MBH net water rating at 95% AFUE — the top size in the small-cabinet group (PF-50/PF-80/PF-110/PF-140) — on the stainless-steel, sealed-combustion direct-vent condensing platform.

Natural gasPropaneHeating-only

Peerless Boilers

Peerless PureFire PF-200

CurrentCanadian status unknown
Input
42–199 MBH
Output (max)
—
AFUE
95 %

The Peerless PureFire PF-200 fires 42 to 199 MBH input with 185 MBH heating capacity and a 161 MBH net water rating at 95% AFUE — the first of the two large cabinet sizes (21 × 24 × 48 inch carton) with a 199 MBH cap — on the stainless-steel, sealed-combustion direct-vent condensing platform.

Natural gasPropaneHeating-only

Peerless Boilers

Peerless PureFire PF-210

CurrentCanadian status unknown
Input
42–210 MBH
Output (max)
—
AFUE
95.1 %

The Peerless PureFire PF-210 fires 42 to 210 MBH input with 195 MBH heating capacity and a 170 MBH net water rating at 95.1% AFUE — the largest residential AFUE row — 42–210 MBH at 95.1% AFUE, alongside (not merged with) the PF-200 — on the stainless-steel, sealed-combustion direct-vent condensing platform.

Natural gasPropaneHeating-only

Peerless Boilers

Peerless PureFire PF-300

CurrentCanadian status unknown
Input
60–300 MBH
Output (max)
—
AFUE
—

The Peerless PureFire PF-300 fires 60 to 300 MBH input with 290 MBH gross output and a 252 MBH net rating at 96.5% thermal efficiency — the 300 MBH commercial-capable size — rated by gross output and thermal efficiency, and not ENERGY STAR certified per the product page — on the stainless-steel, sealed-combustion direct-vent condensing platform.

Natural gasPropaneHeating-only

Peerless Boilers

Peerless PureFire PF-399

CurrentCanadian status unknown
Input
80–399 MBH
Output (max)
—
AFUE
—

The Peerless PureFire PF-399 fires 80 to 399 MBH input with 380 MBH gross output and a 330 MBH net rating at 95.2% thermal efficiency — the largest PF model — 80–399 MBH input with a 380 MBH gross output row at 95.2% thermal efficiency — on the stainless-steel, sealed-combustion direct-vent condensing platform.

Natural gasPropaneHeating-only

Compare models in this series

Comparison of Peerless PureFire PF-50 and Peerless PureFire PF-80 and Peerless PureFire PF-110 and Peerless PureFire PF-140 and Peerless PureFire PF-200 and Peerless PureFire PF-210 and Peerless PureFire PF-300 and Peerless PureFire PF-399
SpecificationPeerless PureFire PF-50Peerless PureFire PF-80Peerless PureFire PF-110Peerless PureFire PF-140Peerless PureFire PF-200Peerless PureFire PF-210Peerless PureFire PF-300Peerless PureFire PF-399
Input, minimum16 MBH20 MBH27.5 MBH35 MBH42 MBH42 MBH60 MBH80 MBH
Input, maximum50 MBH80 MBH110 MBH140 MBH199 MBH210 MBH300 MBH399 MBH
output-max————————
Efficiency (AFUE)95 %95 %95 %95 %95 %95.1 %——
turndown————————
vent-max-3————————
vent-max-2————————
Approx. shipping weight88 lb88 lb108 lb118 lb165 lb165 lb255 lb255 lb

Read the full comparison: Peerless PureFire PF-50 vs PF-80 →

Read the full comparison: Peerless PureFire PF-80 vs PF-110 →

Read the full comparison: Peerless PureFire PF-110 vs PF-140 →

Read the full comparison: Peerless PureFire PF-140 vs PF-200 →

Error codes and alerts

PureFire alerts

  • E01PureFire control
  • E02PureFire control
  • E04PureFire control
  • E05PureFire control
  • E11PureFire control
  • E12PureFire control
  • E13PureFire control
  • E14PureFire control
  • E19PureFire control
  • E20PureFire control
  • E21PureFire control
  • E22PureFire control
  • E23PureFire control
  • E24PureFire control
  • E25PureFire control
  • E26PureFire control
  • E30PureFire control
  • E31PureFire control
  • E32PureFire control
  • E42PureFire control
  • E45PureFire control
  • E46PureFire control
  • E47PureFire control
  • E48PureFire control
  • E51PureFire control
  • A01PureFire control
  • A02PureFire control
  • A03PureFire control
  • A04PureFire control
  • A05PureFire control
  • A09PureFire control
  • A10PureFire control
  • A12PureFire control
  • A13PureFire control
  • A14PureFire control
  • A15PureFire control
  • A16PureFire control
  • A18PureFire control
  • A19PureFire control
  • A20PureFire control
  • A23PureFire control
  • A24PureFire control
  • A32PureFire control
  • A33PureFire control
  • A50PureFire control
  • #W00PureFire control
  • #W01PureFire control
  • #W02PureFire control
  • #W03PureFire control
  • #W04PureFire control

Manuals

Official documents

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Frequently asked questions

Is the Peerless PureFire available in Canada?

No official statement of Canadian sales or distribution was found in the official pages and manuals reviewed on September 9, 2026 (US-site data only), so Boilers.ca records canadianStatus 'unknown'. Confirm supply through a licensed distributor before purchase.

Why are the PF-300 and PF-399 rated differently from the other PureFire models?

The PF-300 and PF-399 rows on the residential cut sheet print gross output and thermal efficiency (96.5% and 95.2%) rather than AFUE, and the PF-300 is not ENERGY STAR certified per the product page — the cut sheet's commercial section shares the same document.

Does the PureFire need a chimney?

No — it is a direct-vent, sealed-combustion appliance that can be vented horizontally or vertically with 3" or 4" approved piping (PVC, CPVC, AL29-4C stainless or polypropylene) up to 200 equivalent feet; it is not connected to a conventional chimney.

Talk to a boiler technician

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate