NTI group fault codes (1 01–7 99) explained

Published September 8, 2026 · Updated September 8, 2026 · Boilers.ca editorial

Short answer

NTI Trinity FTVN, TRX and Compass controls print grouped fault codes: a leading group number and a member number, such as 1 01 for an over-temperature condition, with the P-lettered rows and the NOAVL, EMERG and CONFL text codes reserved for warnings and cascade communication. The leading digit sorts the fault into a family, so a code that shares a group with another is likely to share a diagnosis path, but only the manual table for the exact series and control generation names the member precisely.

The anatomy of a grouped code

The FTVN, TRX and Compass controls documented on this site print most faults as two-part codes in which a leading digit and a following number are separated by a space, so the display reads 1 01, 2 09 or 6 03 rather than a single number. The leading digit is a family label: on the FTVN and TRX tables the group 1 members concern central-heating temperature and flow conditions, group 2 members concern domestic hot water and storage, group 3 members concern the PCB, display and internal electronics, group 4 members concern room sensors, the communication bus and cascade boilers, group 5 members concern ignition and flame, and group 6 members concern exhaust temperature, the blower, and the condensate path.

The member number then names the specific condition inside that family. Code 1 01 is documented as an outlet temperature exceeding 210°F or a failed temperature sensor safety test, while 1 08 is documented as water pressure too low, and both sit in the same group 1 family of central-heating conditions with very different remedies. Reading only the first digit tells you the neighbourhood; reading the pair against the table tells you the fault.

The family table, from the codes documented on this site

The rows below are drawn from the code tables this site documents for the FTVN, TRX and Compass scopes, with two example codes per family so the pattern is visible. The blocking class matters as much as the code itself: the tables record blocking codes with manual or automatic reset behaviour, warnings that clear or self-limit, and a few purely informational rows such as 6 19, power limiting mode, which is documented as normal operation on a new start-up that clears on its own after the burner has run for about five minutes.

The P-lettered rows are warnings, not blocking faults. Code 3 P9 is documented as a scheduled maintenance reminder telling the owner the service interval has elapsed, 5 P1 as a first ignition attempt that failed, which can be momentary normal operation, and 1 P1, 1 P2 and 1 P3 as temperature-rate and spread warnings that can appear for a few minutes in systems with high- and low-temperature zones. A warning that repeats, though, points at the same underlying plumbing or combustion problems the blocking codes describe.

The documented NTI grouped-code families, with example codes from the FTVN/TRX tables on this site
GroupFamily the manual tables coverExample codes and meanings
1Central heating temperature, flow and system water1 01 outlet over 210°F; 1 08 water pressure too low
2Domestic hot water and storage2 01 damaged or shorted DHW probe; 2 09 storage over 175°F
3PCB, display and internal electronics3 02 communication error GP-GIU; 3 04 more than 5 resets in 15 minutes
4Room sensors, bus wiring and cascade4 11 room sensor open/short, zone 1; 4 41 follower boiler missing from bus
5Ignition and flame5 01 no flame detected three times; 5 02 flame out of sequence
6Exhaust, blower and condensate6 02 exhaust over 204°F; 6 03 blocked condensate switch open

The text codes: NOAVL, EMERG and CONFL

A few conditions on the FTVN, TRX and Compass controls are printed as words rather than numbers, and they all concern the cascade communication bus. NOAVL is documented as a problem with the boiler address settings or EBUS wiring, EMERG as a cascade boiler that has lost communication and is operating in emergency central-heating mode at the emergency setpoint, and CONFL as two or more cascade boilers sharing a common address. Each is tied to the orange EBUS connector and to the boiler address menu, where a unit must be set as a single boiler, the master, or a uniquely numbered follower.

These text codes are informative for owners because they explain themselves in the display: a boiler printing EMERG is not failing to burn, it is telling you the cascade link is down and it is holding the building warm on a fallback setpoint until the wiring or addressing is corrected. None of the three is a homeowner repair. The checks belong to a licensed technician who can verify the bus wiring, the address settings across the plant and the state of the master boiler.

How the other NTI controls print their codes

The grouped format is not universal across NTI's line. The FTVN Series II and TRX Series II controls documented on this site add rows to the Series I tables, such as 1 02, pressure sensor not connected, and 3 11, temperature sensor safety test failed, so the series generation must be matched before a code is read. The TFTN wall-hung models use the HMI control, whose tables print the same fault families in longer forms: 101 1 is documented on the TFTN as overheat, where the FTVN prints 1 01, and the TFTN tables also carry plain three-digit codes such as 113 for a low-water-cutoff fault and 730 for a buffer tank high probe error, plus the text prompts Unconfigured and Conflict for cascade configuration problems.

The floor-standing and commercial lines go their own way again. The Trinity Lx tables document plain numeric codes across a wide range, and the FTG commercial fire-tube manual tables are recorded with their hold, lockout and alert classes separated. Whatever the control, the discipline is identical to the grouped codes: identify the series and generation from the rating plate, then read the code in that control's own table, which is exactly how the code pages on this site are organized, one scope per series and manual.

What to do when a grouped code appears

Write the code down exactly as displayed, including the space in a two-part code, and note what the boiler was doing when it appeared. If the code is in a warning class, such as 3 P9, the boiler may simply be asking for service; if it is blocking, the boiler has stopped and the manual table's reset class tells you whether it will clear on its own. Do not press reset repeatedly: code 3 04 itself is documented as appearing when the reset button has been pushed more than five times in fifteen minutes, so resetting can manufacture its own fault.

Gas smell and carbon-monoxide alarms override every other step: leave the building and call 911 from outside. Otherwise, leave a locked-out boiler locked out and call ROMA Heating & Cooling at 778-909-5731 with the code and the circumstances. The repair and diagnostics services check the code against the manufacturer's procedure for the exact series and control generation, test the sensors, wiring and combustion the code implicates, and only then clear the fault for good.

  • Copy the code exactly as shown, including the space in two-part codes like 1 01
  • Identify the series and control generation before using any table
  • Separate blocking codes from warnings: P-lettered rows and 6 19 are not lockouts
  • NOAVL, EMERG and CONFL are cascade bus messages, not burner faults
  • Do not reset repeatedly; 3 04 documents the consequence of doing exactly that

Models referenced in this guide

CurrentSold in Canada
Input
19.9–199 MBH
Output (max)
—
AFUE
95 %

The NTI Trinity FTVN199 is the largest heating-only FTVN: 19.9 to 199 MBH input at 95% AFUE in a 139.5 lb wall-hung boiler. Its 2" venting terms follow NTI technical bulletin 2022-10-26, so most installations run 3" to the 150 ft limit.

Natural gasPropaneHeating-only
CurrentSold in Canada
Input
19.7–197 MBH
Output (max)
—
AFUE
95 %

The NTI Trinity TRX199 is the largest heating-only TRX: 19.7 to 197 MBH input on natural gas (19.2 to 192 MBH on LP) at 95% AFUE, weighing 130 lb with 1 1/4" NPT CH connections and 3" venting to 150 ft per side.

Natural gasPropaneHeating-only
CurrentSold in Canada
Input
19.9–199 MBH
Output (max)
—
AFUE
95 %

The NTI Trinity TFTN199 is the 95% AFUE wall-hung TFTN at the classic 199 MBH mark: 19.9 to 199 MBH input, 140 lb with water, still on 1 1/4" NPT CH connections with 2" venting to 100 ft or 3" to 150 ft.

Natural gasPropaneHeating-only
CurrentSold in Canada
Input
25–150 MBH
Output (max)
—
AFUE
93.5 %

The NTI Trinity Lx150 is the entry size of the Lx fire-tube line: 25 to 150 MBH input on natural gas (145 MBH maximum on LP) at 93.5% AFUE, in a 100 lb floor-standing unit that can also use the wall-hung kits NTI includes for the Lx200–400.

Natural gasPropaneHeating-only

Frequently asked questions

What does the first number in an NTI code like 1 08 mean?

The leading digit places the fault in a family, such as group 1 for central-heating temperature and flow conditions. The member number after it names the specific condition, so the pair is read against the table for the exact series and control generation.

My NTI boiler says EMERG. What does it mean?

EMERG is documented as a cascade boiler that lost communication and is operating in emergency central-heating mode at the emergency setpoint. It points at the EBUS wiring or cascade configuration, not at the burner, and the repair belongs to a licensed technician.

Do NTI codes mean the same thing on every model?

No. The FTVN and TRX Series II tables add rows such as 1 02 and 3 11 over the Series I tables, and the TFTN HMI control prints longer forms such as 101 1 for the same overheat family the FTVN prints as 1 01. Match the code to its own series and manual.

Get a ballpark estimate in two minutes

Answer a few questions for a CAD range before you share any contact details.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Guides

Sources and verification

Facts checked September 8, 2026. Last updated September 8, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate