Ideal Gallant Wall 250
The Ideal Gallant Wall 250 is the smallest Gallant model: 53.6 to 240 MBH input at 95% AFUE, 5.5:1 turndown and a 140 lb wall-hung cabinet with 3-inch venting and an integrated six-boiler cascade function.
Key figures
- Max input
- 240 MBH
- Max CSA output
- —
- AFUE
- 95 %
- Min input
- 53.6 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Ideal Gallant Wall 250 in practice
The Gallant Wall 250 is the entry model of the Gallant line, modulating from 53.6 to 240 MBH input at 95% AFUE with a 5.5:1 turndown, a 192 MBH AHRI net rating and a 222 MBH DOE heating capacity. It is ASME certified and ENERGY STAR listed, with a stainless steel fire-tube heat exchanger and full modulation.
At 140 lb it is the lightest Gallant, measuring 19.75 x 36.5625 x 17.3125 inches with 4.5 gallons of water volume, 3/4-inch gas, 1-1/4-inch supply/return and 3-inch vent/air connections. The CTRLMax control configures in 60 seconds or less for standard installations and offers four fully configurable circulator outputs, two reset curves and set points, and quiet operation. An integrated cascade function joins up to six boilers.
The 250 suits larger homes and light-commercial loads that want a wall-hung boiler; it is also the boiler used in the CPS500 and CPS600 Gallant Cascade kits (two boilers, total input up to 598 MBH). Natural-gas (IDGA250) and propane (IDGA250LP) versions are published, with published natural-gas input figures. No explicit Canadian sales statement was found on the official pages checked on 2026-09-09; the Exalt and Gallant submittals list ANSI Z21.13 and CSA 4.9 compliance, so Boilers.ca records canadianStatus as unknown.
Best suited to
- Larger homes and light-commercial loads that fit within 240 MBH
- Projects wanting the lightest Gallant chassis with 3-inch venting
- Plants planning a Gallant Cascade CPS500 or CPS600 rack
Applicability and support
- Model number
- IDGA250 (NG) / IDGA250LP (LP)
- Canadian availability
- unknown
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Series terms
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Ideal Heating. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Input modulation, minimum (NG & LP) | 53.6 MBH | Per the official model table. |
| Input modulation, maximum (NG & LP) | 240 MBH | Per the official model table. |
| Output | ||
| AHRI net rating | 192 MBH | Per the official model table. |
| DOE heating capacity | 222 MBH | Per the official model table. |
| Efficiency | ||
| Efficiency | 95 % | 95% AFUE per the official model table. |
| Domestic hot water | ||
| Domestic hot water | Heating-only; pair with a separate DHW source | |
| Venting and air | ||
| Vent / air diameter | 3 in | |
| Physical and connections | ||
| Weight | 140 lb | |
| Width | 19.75 in | |
| Height | 36.563 in | |
| Depth | 17.313 in | |
| Operating limits and other | ||
| Turndown ratio | 5.5:1 | Per the official model table. |
| Gas connection | 3/4 in | |
| Supply / return connections | 1-1/4 in | |
| Water volume | 4.5 gal | Per the official model table. |
Manuals
Frequently asked questions
What is the input range of the Gallant Wall 250?
53.6 to 240 MBH with a 5.5:1 turndown, a 192 MBH AHRI net rating and a 222 MBH DOE heating capacity, at 95% AFUE.
What connections does the Gallant Wall 250 use?
3/4-inch gas, 1-1/4-inch supply/return and 3-inch vent/air, per the official model table.
Which cascade kits use the Gallant 250?
The CPS500 (two 250s, 43.6–480 MBH total input) and CPS600 (two boilers, 72.5–598 MBH) rack configurations, per the Gallant Cascade page.
Questions about the Ideal Gallant Wall 250?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Sources and verification
- Ideal Heating NA — Gallant Wall product page and model table · accessed September 9, 2026
- Ideal Heating NA — Gallant 250 engineering submittal (2023-27) · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.