Skip to content
Boilers.caby ROMA Heating & Cooling

Patterson-Kelley · P-K MODU-FIRE FD

P-K MODU-FIRE FD N1500

The P-K MODU-FIRE FD N1500 is a forced-draft non-condensing commercial boiler rated 1500 MBH input and 1275 MBH output in Patterson-Kelley's published submittal, with 5:1 turndown and a 985 lb operating weight.

CurrentCanadian status unknown

Key figures

Max input
1,500 MBH
Max CSA output
1,275 MBH
AFUE
Min input
Natural gasHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

P-K MODU-FIRE FD N1500 in practice

Patterson-Kelley's submittal prints the N1500MFD at 1,500 BTU/hr input and 1,275 BTU/hr output and 5:1 turndown. Design data: 160 psig max pressure, 250°F max allowable temperature, 220°F max setpoint, 38 boiler HP, 206 sq. ft. heated wet surface and 127.5 GPM flow at 20°F ΔT.

Connections are a 1 1/4" NPT-F main gas, 2 1/2" NPT (supply F / return M) supply/return, a 8" dia. stub combustion-air inlet and a 8" (6" with adapter) exhaust vent. Shipping dimensions are 54" × 32" × 68" (L×W×H); operating weight is 985 lb, shipping weight 960 lb and water content 7.3 gallons. The submittal lists ASME CSD-1, FM Global 6-4 and GE GAP (IRI) compliance and an integrated NURO-series control.

P-K describes the MODU-FIRE FD as a full-modulation forced-draft design that 'changes both fuel and air at a constant ratio to match boiler output to actual heat demand' with smooth 5:1 turndown tracking down to 20% of rated capacity and up to 88% efficiency. No official Canadian-sales statement was found, so canadianStatus stays unknown.

Best suited to

  • Commercial plants documenting an installed MODU-FIRE FD N1500 against P-K's submittal
  • Hydronic systems in the 1500 MBH input class
  • Retrofit projects that need a small-footprint forced-draft boiler

Applicability and support

Model number
N1500MFD
Canadian availability
unknown
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Patterson-Kelley. Units are shown with every value; notes flag conflicting sources or missing figures.

P-K MODU-FIRE FD N1500 specifications
SpecificationValueNote
Input
Input1,500 MBHInput (BTU/hr) as printed on the model submittal.
Output
Output1,275 MBHOutput (BTU/hr) as printed on the model submittal.
Efficiency
Efficiency (page)88 %'Up to 88% efficiency' as printed on the P-K MODU-FIRE FD product page; the submittals do not print a per-model efficiency row.
Venting and air
Combustion air inlet8" dia. stubAs printed on the model submittal.
Exhaust vent8" (6" with adapter)As printed on the model submittal; MODU-FIRE FD requires Category II (condensing-negative pressure) or Category IV (condensing-positive pressure) venting.
Physical and connections
Main gas connection1 1/4" NPT-FAs printed on the model submittal.
Boiler supply / return2 1/2" NPT (supply F / return M)As printed on the model submittal.
Operating weight985 lbAs printed on the model submittal.
Shipping weight960 lbAs printed on the model submittal.
Boiler water content7.3 galAs printed on the model submittal.
Shipping length54 inShipping dimensions printed as 54" × 32" × 68" (L×W×H) on the submittal; listed here as depth × width × height.
Shipping width32 inSecond dimension of the submittal's L×W×H shipping box.
Shipping height68 inThird dimension of the submittal's L×W×H shipping box.
Heated wet surface area206 sq. ft.As printed on the model submittal.
Electrical
Power supply208–240 V, 1 ph, w/neutral, 60 HzAs listed on the submittal; operating current under 6 A (N750/N1000) or under 10 A (N1500/N2000) / under 15 A (N2500/N3000).
Operating limits and other
Turndown ratio5:1The N1500/N2000 submittal prints input, output and design data but no minimum-input row; the 5:1 turndown is the series figure printed on the product page.
Boiler HP38As printed on the model submittal.
Flow rate @ 20°F ΔT127.5 GPMAs printed on the model submittal.
Max. pressure160 psigASME Section IV design data on the submittal.
Max. allowable temperature250 °FASME Section IV design data on the submittal.
Maximum setpoint220 °FASME Section IV design data on the submittal.
ControlIntegrated NURO-series boiler controlListed on the submittal's boiler-controls panel.
ListingsASME CSD-1 standard; FM Global 6-4 Section 1.0; GE GAP (IRI) GAP.4.1.0 / GAP.4.1.3As listed on the submittals.

Manuals

Alerts documented for this model

Services

Frequently asked questions

What are the MODU-FIRE FD N1500 ratings?

P-K's submittal prints 1,500 BTU/hr input and 1,275 BTU/hr output, 5:1 turndown, a 985 lb operating weight and a 960 lb shipping weight.

What venting does the MODU-FIRE FD N1500 require?

P-K's submittal requires Category II (condensing-negative pressure) or Category IV (condensing-positive pressure) venting, with a 8" (6" with adapter) exhaust connection.

Is the MODU-FIRE FD condensing?

No. P-K lists MODU-FIRE FD under its non-condensing boilers; it is a forced-draft design with up to 88% efficiency and full modulation.

Questions about the P-K MODU-FIRE FD N1500?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate