Patterson-Kelley · P-K MODU-FIRE FD

P-K MODU-FIRE FD N2500

The P-K MODU-FIRE FD N2500 is a forced-draft non-condensing commercial boiler rated 2500 MBH input and 2123 MBH output in Patterson-Kelley's published submittal, with 5:1 turndown, a 500 MBH minimum input and a 1185 lb operating weight.

CurrentCanadian status unknown

Key figures

Max input
2,500 MBH
Max CSA output
2,123 MBH
AFUE
Min input
500 MBH
Natural gasHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

P-K MODU-FIRE FD N2500 in practice

Patterson-Kelley's submittal prints the N2500MFD at 2,500 BTU/hr input and 2,123 BTU/hr output, with a 500 BTU/hr minimum input and 5:1 turndown. Design data: 160 psig max pressure, 250°F max allowable temperature, 220°F max setpoint, 65.7 boiler HP, 357 sq. ft. heated wet surface and 212.3 GPM flow at 20°F ΔT.

Connections are a 2" NPT-F main gas, 3"-150# ANSI flange (supply F / return M) supply/return, a 8" dia. stub (10" with optional air-intake adapter) combustion-air inlet and a 10" exhaust vent. Shipping dimensions are 54" × 32" × 68" (L×W×H); operating weight is 1185 lb, shipping weight 1220 lb and water content 12.6 gallons. The submittal lists ASME CSD-1, FM Global 6-4 and GE GAP (IRI) compliance and an integrated NURO-series control.

P-K describes the MODU-FIRE FD as a full-modulation forced-draft design that 'changes both fuel and air at a constant ratio to match boiler output to actual heat demand' with smooth 5:1 turndown tracking down to 20% of rated capacity and up to 88% efficiency. No official Canadian-sales statement was found, so canadianStatus stays unknown.

Best suited to

  • Commercial plants documenting an installed MODU-FIRE FD N2500 against P-K's submittal
  • Hydronic systems in the 2500 MBH input class
  • Retrofit projects that need a small-footprint forced-draft boiler

Applicability and support

Model number
N2500MFD
Canadian availability
unknown
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Patterson-Kelley. Units are shown with every value; notes flag conflicting sources or missing figures.

P-K MODU-FIRE FD N2500 specifications
SpecificationValueNote
Input
Input2,500 MBHInput (BTU/hr) as printed on the model submittal.
Minimum input500 MBHMin input (BTU/hr) as printed on the model submittal.
Output
Output2,123 MBHOutput (BTU/hr) as printed on the model submittal.
Efficiency
Efficiency (page)88 %'Up to 88% efficiency' as printed on the P-K MODU-FIRE FD product page; the submittals do not print a per-model efficiency row.
Venting and air
Combustion air inlet8" dia. stub (10" with optional air-intake adapter)As printed on the model submittal.
Exhaust vent10"As printed on the model submittal; MODU-FIRE FD requires Category II (condensing-negative pressure) or Category IV (condensing-positive pressure) venting.
Physical and connections
Main gas connection2" NPT-FAs printed on the model submittal.
Boiler supply / return3"-150# ANSI flange (supply F / return M)As printed on the model submittal.
Operating weight1,185 lbAs printed on the model submittal.
Shipping weight1,220 lbAs printed on the model submittal.
Boiler water content12.6 galAs printed on the model submittal.
Shipping length54 inShipping dimensions printed as 54" × 32" × 68" (L×W×H) on the submittal; listed here as depth × width × height.
Shipping width32 inSecond dimension of the submittal's L×W×H shipping box.
Shipping height68 inThird dimension of the submittal's L×W×H shipping box.
Heated wet surface area357 sq. ft.As printed on the model submittal.
Electrical
Power supply208–240 V, 1 ph, w/neutral, 60 HzAs listed on the submittal; operating current under 6 A (N750/N1000) or under 10 A (N1500/N2000) / under 15 A (N2500/N3000).
Operating limits and other
Turndown ratio5:1As printed on the model submittal.
Boiler HP65.7As printed on the model submittal.
Flow rate @ 20°F ΔT212.3 GPMAs printed on the model submittal.
Max. pressure160 psigASME Section IV design data on the submittal.
Max. allowable temperature250 °FASME Section IV design data on the submittal.
Maximum setpoint220 °FASME Section IV design data on the submittal.
ControlIntegrated NURO-series boiler controlListed on the submittal's boiler-controls panel.
ListingsASME CSD-1 standard; FM Global 6-4 Section 1.0; GE GAP (IRI) GAP.4.1.0 / GAP.4.1.3As listed on the submittals.

Manuals

Alerts documented for this model

Services

Frequently asked questions

What are the MODU-FIRE FD N2500 ratings?

P-K's submittal prints 2,500 BTU/hr input and 2,123 BTU/hr output with a 500 BTU/hr minimum input, 5:1 turndown, a 1185 lb operating weight and a 1220 lb shipping weight.

What venting does the MODU-FIRE FD N2500 require?

P-K's submittal requires Category II (condensing-negative pressure) or Category IV (condensing-positive pressure) venting, with a 10" exhaust connection.

Is the MODU-FIRE FD condensing?

No. P-K lists MODU-FIRE FD under its non-condensing boilers; it is a forced-draft design with up to 88% efficiency and full modulation.

Questions about the P-K MODU-FIRE FD N2500?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate