Slant/Fin · CHS Series (CHS-85 to CHS-399)
Slant/Fin CHS-154
The Slant/Fin CHS-154 is a size in the line of the CHS high-efficiency fire-tube condensing gas boiler series: 15.4–154 MBH input, 141 MBH heating capacity, a 123 MBH AHRI net rating and 95% AFUE. The CHS hub sits in Slant/Fin's active 'Boilers' library section and also hosts the official 2018 recall notices.
Key figures
- Max input
- 154 MBH
- Max CSA output
- —
- AFUE
- 95 %
- Min input
- 15.4 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Slant/Fin CHS-154 in practice
The CHS-154 is a size in the line of Slant/Fin's CHS Series, a high-efficiency fire-tube condensing gas boiler line held in the official library's active 'Boilers' section ('Boilers > CHS Series'). The official submittal ratings table (720) prints 15.4–154 MBH input for this size (a single min–max range is printed), 141 MBH heating capacity, a 123 MBH AHRI net rating and 95% AFUE.
It is a condensing fire-tube design with direct spark ignition, a modulating burner, outdoor reset and DHW priority, and lead-lag capability up to 8 boilers. Water connections are 1" NPT, gas is ½" NPT and the vent/air connection is 3". The boiler is wall-standard with a floor kit option, carries MAWP of 30 psi (80 psi on CHS-175 and up), and the line's weights run 110–250 lb with water per the official submittal data.
Slant/Fin prints no 'current' or 'discontinued' sentence; the hub's active 'Boilers' placement is the only official status signal, so Boilers.ca describes the series as current library / documents available on slantfin.com without asserting current production. IMPORTANT: the CHS hub also hosts the official 2018 recall documents — a CPSC notice plus contractor and homeowner notifications — and owners should confirm whether their unit's date range is affected. No official Canadian-sales statement was found, so canadianStatus stays 'unknown'; gas, venting and combustion work belongs with a licensed contractor.
Best suited to
- Residential hydronic systems whose heat-loss calculation fits 141 MBH of heating capacity
- Wall-hung installs (floor kit available) needing a modulating condensing boiler
- Owners of an installed CHS checking ratings and the official 2018 recall notices
Applicability and support
- Model number
- CHS-154
- Canadian availability
- unknown
- Production status
- unknown
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Not verified
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Slant/Fin. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Input, minimum | 15.4 MBH | Minimum input in MBH as printed in the official submittal ratings table (a single min–max range is printed for this size). |
| Input, maximum | 154 MBH | Maximum input in MBH as printed in the official submittal ratings table (a single min–max range is printed for this size). |
| Output | ||
| Heating capacity | 141 MBH | Heating capacity in MBH as printed in the official submittal ratings table. |
| Net AHRI rating | 123 MBH | AHRI net rating in MBH as printed in the official submittal ratings table. |
| Efficiency | ||
| AFUE | 95 % | 95.0% AFUE as printed in the official submittal ratings table. |
| Domestic hot water | ||
| Domestic hot water | Heating-only boiler — DHW priority control; domestic hot water comes from a separate indirect tank | The CHS is a heating boiler; the submittal data prints DHW priority in the control features. |
| Venting and air | ||
| Vent / air connection | 3" | Vent/air connection size as printed in the official submittal data (3" on CHS-85 through CHS-285; 4" on CHS-340/399). |
| Physical and connections | ||
| Weight with water | 110–250 lb (line range) | The official submittal data prints the line range (110–250 lb with water) rather than per-size weights. |
| Mounting | Wall standard; floor kit available | Per the official submittal data. |
| Maximum allowable working pressure | 30 psi (80 psi on CHS-175 and up) | MAWP as printed in the official submittal data. |
| Operating limits and other | ||
| Water connections | 1" NPT | Water connection size as printed in the official submittal data (1" on CHS-85/110/154; 1¼" on CHS-175/201/285; 1½" on CHS-340/399). |
| Gas connection | ½" NPT | Gas connection size as printed in the official submittal data (½" NPT on CHS-85 through CHS-201; ¾" on CHS-285 through CHS-399). |
| Ignition / burner | Direct spark ignition with a modulating burner | Outdoor reset, DHW priority and lead-lag up to 8 boilers are printed in the official submittal data. |
Manuals
Alerts documented for this model
- Lockout 2
- Lockout 9
- Hold 27
- Hold 61
- Hold 62
- Hold 63
- Hold 65
- Hold 66
- Hold 67
- Lockout or Hold 79
- Lockout or Hold 81
- Lockout 82
- Lockout 85
- Lockout or Hold 88
- Hold 91
- Hold 92
- Hold 95
- Lockout 109 or Hold 110
- Lockout 113
- Lockout 122
- Alert 128
- Hold 137
- Lockout 138
- Lockout 173
- Lockout 174
- Alert 206
- Alert 233
- Alert 248
- Alert 448
- Alert 449
Frequently asked questions
What are the CHS-154's ratings?
15.4–154 MBH input, 141 MBH heating capacity, a 123 MBH AHRI net rating and 95% AFUE, per the official CHS submittal sheet.
Is the CHS-154 a condensing boiler?
Yes — the CHS Series is a high-efficiency fire-tube condensing gas boiler line, with 3" vent/air connections on CHS-85 through CHS-285 and 4" on CHS-340/399.
Was the CHS recalled?
The official CHS hub hosts 2018 recall documents — a CPSC notice plus contractor and homeowner official notifications. Owners should open the current notices on slantfin.com and act on any that apply to their unit's date range.
Questions about the Slant/Fin CHS-154?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Compare and explore
- Slant/Fin CHS-110 vs CHS-154Comparison
- Slant/Fin CHS-154 vs CHS-175Comparison
- Slant/Fin CHS-85Same series
- Slant/Fin CHS-110Same series
- Slant/Fin CHS-175Same series
- Slant/Fin CHS-201Same series
- Slant/Fin CHS-285Same series
- Slant/Fin CHS-340Same series
- Slant/Fin CHS-399Same series
- CHS Series (CHS-85 to CHS-399) series hub
- Buying guide
Sources and verification
- Slant/Fin — library: CHS Series (Boilers section; manuals and 2018 recall notices) · accessed September 9, 2026
- CHS-85 through CHS-399 Installation and Operation Manual, Pub. CHS-40 (V.2018-07-11) · accessed September 9, 2026
- CHS Submittal Sheet 720 · accessed September 9, 2026
Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.