Viessmann Vitocrossal 200 F.891 — System in a Fault State

F.891

Needs attentionVitocrossal 200 CI2 commercial condensing boilers (fault codes, SI 6175 797 - 23)

System in a fault state. O2 probe malfunction: probe not ready for operation in pre/post purge. Check the electric connection to the O2 probe (cable and connectors at the probe) and for loose connectors on the BCU and probe or damaged or broken pins and wires. Check the probe tip for damage or contamination and the probe heater by measuring the heating coil resistance (about 2 to 3 ohm between pins 3 and 5 on the all-black sensor, or pins 2 and 3 on the black-yellow sensor). Compare the O2 value measured by the probe with a flue gas analyzer during operation (after air calibration the difference should be less than 0.5% O2); if the difference is greater than 1% O2, try another probe and then another burner control unit. Check for internal and external flue gas recirculation, contaminated intake air, blocked venting, condensate blockage and dirty combustion air filters. If the fault is intermittent or only in the error history, repeat the checks while the burner is operating.

Applies to

This venting or air-supply fault code is displayed by the CI2 control (F-codes) on CI2 models (CI2-399 through CI2-2000), as documented in Vitocrossal 200 CI2 Service Instructions, doc 6175 797 - 23 (04/2026) (6175 797 - 23). Codes can differ between controller generations, so always check the manual that matches your unit.

Controller: CI2 control (F-codes). Source manual: 6175 797 - 23 (2026-04).

Why a code is not a diagnosis

A venting or air-supply code points at the combustion-air path: a blocked terminal, a restricted flue, a failed fan, or a condensate restriction. It does not say which, and running an appliance with a blocked flue is unsafe.

Safe things to observe

  • If a carbon-monoxide alarm sounds anywhere in the building, leave immediately and call 911 from outside.
  • From a safe distance, check that the vent terminal and combustion-air inlet are not blocked.
  • Do not run the appliance while a blockage is suspected.

Do not

  • Do not put anything into the vent or air-intake openings.
  • Do not remove or modify vent pipe.

How professional service helps

  1. A technician inspects the full vent and combustion-air path, clears blockages and checks the fan.
  2. Combustion and safety devices are verified with an analyser and the manufacturer's procedure after any repair.

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Parts and service

Parts commonly involved

These parts appear in the documented text for this alert. A code reports a condition, not a failed part — a technician confirms the cause by testing before anything is replaced.

Service for this alert

  • Gas Boiler Repair

    Licensed gas technicians from ROMA Heating & Cooling diagnose and repair residential and light-commercial gas boilers across…

Every boiler part explained — what it does, how it fails and what a technician checks.

Documented for Viessmann Vitocrossal 200 (CI2).

Frequently asked questions

Is this code a carbon-monoxide danger?

The code relates to combustion or venting, so treat any CO alarm as an emergency and call 911 from outside. The appliance itself should be checked by a technician before it runs again.

Can I clear this code myself?

Clearing a code without fixing its cause usually just brings it back. Note the code, check the safe items on this page, then call a licensed technician. If your appliance manual describes a user reset for this exact code and it stays away, no call may be needed.

Boiler locked out? Call with the alert text ready.

The brand, model and this alert are passed along when you request service online, so the technician arrives prepared.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.