Skip to content
Boilers.caby ROMA Heating & Cooling

Viessmann · Vitodens 200-W (legacy B2HA / B2HB)

Viessmann Vitodens 200-W WB2B-105

The Vitodens 200-W WB2B-105 is the largest WB2B boiler: 104 to 370 MBH NG/LPG input at 96.1% AFUE with a printed 94.5% thermal efficiency (ANSI Z21.13/CSA 4.9).

DiscontinuedHistorically in Canada

Key figures

Max input
370 MBH
Max CSA output
AFUE
96.1 %
Min input
104 MBH
Natural gasPropaneHeating-onlyresidentialcommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Viessmann Vitodens 200-W WB2B-105 in practice

The WB2B-105 tops the WB2B range at 104-370 MBH (30-108 kW) input and 98-350 MBH (29-103 kW) output with a 304 MBH Net I=B=R rating at 96.1% AFUE. It is the only WB2B size with a printed CSA thermal efficiency row: 94.5% per ANSI Z21.13/CSA 4.9.

It shares the 225 lb (102 kg), 3.4 USG, 60 psig large chassis with the WB2B-80, and the technical data manual notes a high-altitude derate for this model — 14% at 5,000 ft and 28% at 10,000 ft, averaging 2.8% per 1,000 ft. Multi-boiler installations with the Vitocontrol-S control are documented for the 80 and 105 models.

Best suited to

  • Owners of existing WB2B-105 units looking up printed ratings
  • The largest WB2B loads at up to 370 MBH input
  • Documentation for the top WB2B size and its altitude derate

Applicability and support

Model number
WB2B-105
Canadian availability
historical
Production status
discontinued
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Viessmann. Units are shown with every value; notes flag conflicting sources or missing figures.

Viessmann Vitodens 200-W WB2B-105 specifications
SpecificationValueNote
Input
CSA input, minimum (NG/LPG)104 MBH30 kW, per the technical data manual
CSA input, maximum (NG/LPG)370 MBH108 kW, per the technical data manual
Output
CSA output / DOE heating capacity98-350 MBH29-103 kW, based on 140°F / 120°F supply/return
Net I=B=R rating304 MBHBased on piping and pick-up allowance of 1.15.
Efficiency
Efficiency (AFUE)96.1 %96.1% AFUE per the technical data manual.
CSA thermal efficiency (ANSI Z21.13/CSA 4.9)94.5 %Printed only for the WB2B-105.
Physical and connections
Weight225 lb102 kg
Width19 in480 mm
Depth21 in530 mm
Height33.5 in850 mm
Operating limits and other
FuelNatural gas or liquid propane gasNG minimum supply pressure 4 in. w.c.; LPG 10 in. w.c.
Boiler water content3.4 USG
Maximum operating pressure60 psigAt 210°F (99°C).
Boiler heating supply / return1¼ in. NPTMGas valve connection 1 in. NPTF; pressure relief and drain valves ¾ in.

Frequently asked questions

What is the WB2B-105 rated at?

104-370 MBH (30-108 kW) NG/LPG input, 98-350 MBH (29-103 kW) output, a 304 MBH Net I=B=R rating and 96.1% AFUE, with a printed 94.5% CSA thermal efficiency (ANSI Z21.13/CSA 4.9).

Does the WB2B-105 derate at altitude?

Yes — the technical data manual prints an altitude derate for the WB2B-105 of 14% at 5,000 ft and 28% at 10,000 ft (average 2.8% per 1,000 ft).

What replaced the WB2B generation?

The later B2HB generation and then the current B2HE series. The WB2B documentation remains in Viessmann Canada's historic manuals for existing installations.

Questions about the Viessmann Vitodens 200-W WB2B-105?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate