Skip to content
Boilers.caby ROMA Heating & Cooling

Viessmann · Vitodens 200-W (legacy B2HA / B2HB)

Viessmann Vitodens 200-W WB2B-35

The Vitodens 200-W WB2B-35 is the largest WB2B model on the compact chassis: 31 to 125 MBH NG/LPG input at 96.1% AFUE in a 102 lb (46 kg) cabinet.

DiscontinuedHistorically in Canada

Key figures

Max input
125 MBH
Max CSA output
—
AFUE
96.1 %
Min input
31 MBH
Natural gasPropaneHeating-onlyresidentialcommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Viessmann Vitodens 200-W WB2B-35 in practice

The WB2B-35 tops the WB2B compact group at 31-125 MBH (9-37 kW) input, 28-114 MBH (8-33 kW) output and a 99 MBH Net I=B=R rating at 96.1% AFUE. Weight, water content, pressure rating and dimensions are shared with the WB2B-19 and WB2B-26.

Like the smaller models it is heating-only and runs on natural gas or propane. The WB2B-45, -60, -80 and -105 step up to the larger chassis groups with 1¼ in. supply and return connections and, for the 60 to 105 sizes, support for multi-boiler cascade installations with the Vitocontrol-S control.

Best suited to

  • Owners of existing WB2B-35 units looking up printed ratings
  • Residential loads between the WB2B-26 and the larger-chassis WB2B-45
  • Documentation for the last compact-chassis WB2B size

Applicability and support

Model number
WB2B-35
Canadian availability
historical
Production status
discontinued
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Viessmann. Units are shown with every value; notes flag conflicting sources or missing figures.

Viessmann Vitodens 200-W WB2B-35 specifications
SpecificationValueNote
Input
CSA input, minimum (NG/LPG)31 MBH9 kW, per the technical data manual
CSA input, maximum (NG/LPG)125 MBH37 kW, per the technical data manual
Output
CSA output / DOE heating capacity28-114 MBH8-33 kW, based on 140°F / 120°F supply/return
Net I=B=R rating99 MBHBased on piping and pick-up allowance of 1.15.
Efficiency
Efficiency (AFUE)96.1 %96.1% AFUE per the technical data manual.
Physical and connections
Weight102 lb46 kg
Width17.75 in450 mm
Depth14 in360 mm
Height33.5 in850 mm
Operating limits and other
FuelNatural gas or liquid propane gasNG minimum supply pressure 4 in. w.c.; LPG 10 in. w.c.
Boiler water content0.87 USG
Maximum operating pressure45 psigAt 210°F (99°C).
Boiler heating supply / return¾ in. NPTMGas valve connection ¾ in. NPTF; pressure relief and drain valves ¾ in.

Frequently asked questions

What is the WB2B-35 rated at?

31-125 MBH (9-37 kW) NG/LPG input, 28-114 MBH (8-33 kW) output, a 99 MBH Net I=B=R rating and 96.1% AFUE.

What changes when stepping to the WB2B-45?

The chassis grows to 155 lb (70 kg) with 1.9 USG water and a 60 psig rating, connections move to 1¼ in. supply/return and 1 in. gas, and the firing range starts at 60 MBH.

Can WB2B-35 boilers be cascaded?

The technical data manual's multi-boiler documentation covers the WB2B 45, 60, 80 and 105 models; the 19, 26 and 35 share single-boiler installation and service instructions.

Questions about the Viessmann Vitodens 200-W WB2B-35?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate