Skip to content
Boilers.caby ROMA Heating & Cooling

Viessmann · Vitodens 200-W (legacy B2HA / B2HB)

Viessmann Vitodens 200-W WB2B-80

The Vitodens 200-W WB2B-80 opens the WB2B large chassis: 104 to 285 MBH NG/LPG input at 96.1% AFUE in a 225 lb (102 kg) wall-hung boiler.

DiscontinuedHistorically in Canada

Key figures

Max input
285 MBH
Max CSA output
AFUE
96.1 %
Min input
104 MBH
Natural gasPropaneHeating-onlyresidentialcommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Viessmann Vitodens 200-W WB2B-80 in practice

The WB2B-80 is the first WB2B model on the large chassis: 104-285 MBH (30-83 kW) input, 95-260 MBH (28-76 kW) output and a 226 MBH Net I=B=R rating at 96.1% AFUE. It weighs 225 lb (102 kg) with 3.4 USG of boiler water and a 60 psig maximum operating pressure.

Dimensions are 19 x 21 x 33½ in (480 x 530 x 850 mm), with 1¼ in. supply and return and 1 in. gas connections. The 80 and 105 models share installation and service instructions and support multi-boiler installations with the Vitocontrol-S cascade control, documented up to four boilers.

Best suited to

  • Owners of existing WB2B-80 units looking up printed ratings
  • Large residential and light-commercial loads from 104 MBH
  • Documentation for the first large-chassis WB2B size

Applicability and support

Model number
WB2B-80
Canadian availability
historical
Production status
discontinued
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Viessmann. Units are shown with every value; notes flag conflicting sources or missing figures.

Viessmann Vitodens 200-W WB2B-80 specifications
SpecificationValueNote
Input
CSA input, minimum (NG/LPG)104 MBH30 kW, per the technical data manual
CSA input, maximum (NG/LPG)285 MBH83 kW, per the technical data manual
Output
CSA output / DOE heating capacity95-260 MBH28-76 kW, based on 140°F / 120°F supply/return
Net I=B=R rating226 MBHBased on piping and pick-up allowance of 1.15.
Efficiency
Efficiency (AFUE)96.1 %96.1% AFUE per the technical data manual.
Physical and connections
Weight225 lb102 kg
Width19 in480 mm
Depth21 in530 mm
Height33.5 in850 mm
Operating limits and other
FuelNatural gas or liquid propane gasNG minimum supply pressure 4 in. w.c.; LPG 10 in. w.c.
Boiler water content3.4 USG
Maximum operating pressure60 psigAt 210°F (99°C).
Boiler heating supply / return1¼ in. NPTMGas valve connection 1 in. NPTF; pressure relief and drain valves ¾ in.

Frequently asked questions

What is the WB2B-80 rated at?

104-285 MBH (30-83 kW) NG/LPG input, 95-260 MBH (28-76 kW) output, a 226 MBH Net I=B=R rating and 96.1% AFUE.

How heavy is the WB2B-80?

225 lb (102 kg) with 3.4 USG of boiler water, in the 19 x 21 x 33½ in large chassis shared with the WB2B-105.

Can WB2B-80 boilers be combined?

Yes — the technical data manual documents multi-boiler installations of the WB2B 80 and 105 models with the Vitocontrol-S, WB2B cascade control; the manual's system guide describes combinations up to four boilers.

Questions about the Viessmann Vitodens 200-W WB2B-80?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate