Burnham Alpine ALP399C
The Burnham Alpine ALP399C is the entry commercial Alpine: 80 to 399 MBH input printing 375 MBH gross output, a 326 MBH net AHRI water rating and 94.1% thermal efficiency (not an AFUE), floor-standing with 4" venting and a 10,100 ft altitude rating.
Key figures
- Max input
- 399 MBH
- Max CSA output
- —
- AFUE
- —
- Min input
- 80 MBH
Input is gas energy consumed; output is heat delivered. Never size from input alone.
Burnham Alpine ALP399C in practice
The ALP399C is the commercial side of the Alpine family, documented in the Alpine Commercial I&O (Doc 106307-03, 11/22) alongside the ALP500C–ALP800C sizes. It fires 80–399 MBH input for 375 MBH gross output and a 326 MBH net AHRI water rating, with the table printing 94.1% thermal efficiency rather than an AFUE — a condensing stainless steel unit on the same Sage control scheme as the residential Alpines.
It is floor-standing, ships at 316 lb, connects on 3/4" FPT gas and 1-1/2" FPT supply/return, ships with a 50 psi relief valve (160 psi MAWP) and holds 3.4 gal of water. Venting is 4" PVC intake with 4" CPVC/polypropylene/stainless vent to 100 ft maximum equivalent each, and the unit is rated to 10,100 ft elevation per the Commercial manual's high-altitude appendix. Boilers.ca links the residential Alpine I&O (103448-12) for the ALP080B–ALP285B models; the 399C's own manual is the Alpine Commercial I&O (106307-03).
Best suited to
- Light-commercial hydronic plants whose load approaches 399 MBH of input
- Projects wanting an Alpine-class condensing boiler above the residential 285B ceiling
- High-altitude sites up to 10,100 ft within the 399C's rating
Applicability and support
- Model number
- ALP399C
- Canadian availability
- unknown
- Production status
- current
- ROMA supplies
- Confirmed at consultation
- ROMA services
- Confirmed at consultation
- Warranty
- Series terms
Where ROMA provides on-site service
On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.
Specifications
Published specifications
Values as published by Burnham. Units are shown with every value; notes flag conflicting sources or missing figures.
| Specification | Value | Note |
|---|---|---|
| Input | ||
| Input, minimum | 80 MBH | Minimum input per the Alpine Commercial ratings table; min/max inputs give 5:1 modulation. |
| Input, maximum | 399 MBH | Maximum input per the Alpine Commercial ratings table (Doc 106307-03, 11/22). |
| Output | ||
| DOE heating capacity (gross) | 375 MBH | The Alpine Commercial ratings table prints 375 MBH gross output for the ALP399C. |
| Net AHRI water rating | 326 MBH | Net AHRI water rating per the Alpine Commercial ratings table. |
| Efficiency | ||
| Thermal efficiency | 94.1 % | The commercial ratings table prints 94.1% thermal efficiency for the ALP399C rather than an AFUE. |
| Domestic hot water | ||
| Domestic hot water | Heating-only boiler — domestic hot water comes from a separate indirect tank or water heater | |
| Venting and air | ||
| Vent connection | 4" PVC intake + 4" CPVC/PP/SS vent | 4" PVC intake with 4" CPVC, polypropylene or stainless steel vent, 100 ft max equivalent each, per the Alpine submittal. |
| Physical and connections | ||
| Shipping weight | 316 lb | Shipping weight per the Alpine Commercial ratings table. |
| Gas connection | 3/4" FPT | Female NPT per the Alpine Commercial manual specifications. |
| Supply/return connections | 1-1/2" FPT | Female NPT per the Alpine Commercial manual specifications. |
| Width | 31-3/16" | Jacket width 31-3/16" per the Alpine submittal dimensions (floor unit). |
| Boiler water content | 3.4 gal | 3.4 gal water content per the Alpine Commercial specifications. |
| Operating limits and other | ||
| Altitude rating | 10,100 ft | The ALP399C is rated to 10,100 ft per the Alpine Commercial high-altitude instructions (Appendix A). |
| Safety relief valve | 50 psig | The ALP399C ships with a 50 psi relief valve (MAWP 160 psi). |
| Fuel | Natural gas or propane | Inputs identical on NG and LP; boiler ships configured for natural gas with a field LP-conversion kit. |
Frequently asked questions
What is the ALP399C's efficiency rating?
The Alpine Commercial ratings table prints 94.1% thermal efficiency for the ALP399C; it is not given an AFUE figure like the residential ALP080B–ALP285B models (95.0% AFUE).
Is the ALP399C residential or commercial?
It is the entry of the Alpine Commercial size range (ALP399C–ALP800C), documented in the Alpine Commercial I&O manual (Doc 106307-03, 11/22).
What venting does the ALP399C use?
A 4" PVC intake with a 4" CPVC, polypropylene or stainless steel vent, 100 ft maximum equivalent each, per the Alpine submittal.
Questions about the Burnham Alpine ALP399C?
Describe what the boiler is doing and get a straight answer about the next step.
On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.
Sources and verification
- U.S. Boiler Company — Alpine product page · accessed September 8, 2026
- U.S. Boiler Company — Technical Literature (Alpine/ES2 I&O manual listings) · accessed September 8, 2026
Facts checked September 8, 2026. Last updated September 8, 2026. Technical reviewer: not yet assigned.