Camus DynaFlame DFH 1100 (Non-Condensing Heating)

The Camus DynaFlame DFH 1100 is the non-condensing hydronic-heating size of Camus' stainless-steel watertube line: 1100 MBTU/hr input, 935 MBTU/hr output, up to 85% thermal efficiency and 3:1 turndown.

CurrentSold in Canada

Key figures

Max input
1,100 MBTU/hr
Max CSA output
935 MBTU/hr
AFUE
Min input
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Camus DynaFlame DFH 1100 (Non-Condensing Heating) in practice

Per the official DynaFlame spec sheet (99-0143 Rev 01), the DFH 1100 is rated 1100 MBTU/hr input and 935 MBTU/hr output with a 640 lb approximate shipping weight. It connects through the range's vertical cylindrical watertube heat exchanger — 439 stainless steel, 6-pass, 160 psig working pressure — and vents in category i or iii non-condensing configuration.

The model is a non-condensing appliance: the spec sheet prints up to 85% thermal efficiency with a 3:1 turndown ratio (minimum 35% firing rate) and light-off at no more than 50% input. Electrical draw is 7 A at 115 V single-phase, and the vent-diameter table prints Cat. I 10", Cat. III up to 50 ft 6", Cat. III up to 100 ft 8" and outdoor 6".

As a hydronic heating boiler the DFH 1100 is design certified to ANSI Z21.13 / CSA 4.9. Camus is a Mississauga, Ontario manufacturer, and Boilers.ca reproduces the manufacturer's printed figures here; sizing a boiler plant remains a heat-loss and load calculation by a licensed contractor.

Best suited to

  • Hydronic heating plants whose design load lands near 1100 MBTU/hr input (935 MBTU/hr output)
  • Projects wanting a non-condensing Camus watertube boiler with a Canadian-built stainless heat exchanger
  • Multiple-boiler plants: the SOLA control documented for the DynaFlame line cascades up to eight units

Applicability and support

Model number
DF(N,P)H 1100
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Camus Hydronics. Units are shown with every value; notes flag conflicting sources or missing figures.

Camus DynaFlame DFH 1100 (Non-Condensing Heating) specifications
SpecificationValueNote
Input
Input, maximum1,100 MBTU/hrAs printed in the official DynaFlame spec sheet (99-0143 Rev 01).
Output
Output, maximum935 MBTU/hrHydronic-heating output as printed in the spec sheet.
Efficiency
Thermal efficiency85 %Up to 85% thermal efficiency as printed in the spec sheet (non-condensing).
Venting and air
VentingCat. I 10" · Cat. III up to 50 ft 6" · Cat. III up to 100 ft 8" · outdoor 6"Category I or III non-condensing.
Physical and connections
Shipping weight640 lbApproximate shipping weight as printed in the spec sheet.
Heat exchanger439 stainless steel welded 6-pass vertical cylindrical watertube
Electrical
Electrical7 A at 115 V single-phase
Operating limits and other
Turndown ratio3:1Proportional modulating with a minimum 35% firing rate; light-off at no more than 50% input.
Max. working pressure160 psig1100 kPa; ASME Section IV heat-exchanger testing.
FuelNatural gas or propane (optional dual-fuel operation listed)
CertificationCSA International design certified; ANSI Z21.13 / CSA 4.9
ApplicationHydronic heating

Frequently asked questions

Is the DynaFlame DFH 1100 condensing?

It is the non-condensing generation: the official spec sheet prints up to 85% thermal efficiency and category i or iii non-condensing venting.

How big is the DFH 1100?

The spec sheet prints 1100 MBTU/hr input and 935 MBTU/hr output, a 640 lb approximate shipping weight, and 7 A at 115 V single-phase.

What fuel does the DFH 1100 use?

The spec sheets list natural gas, propane and optional dual-fuel operation; the captured sheets print natural-gas ratings and the gas train description. Fuel selection and conversion are licensed trade work.

Questions about the Camus DynaFlame DFH 1100 (Non-Condensing Heating)?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.