Camus Hydronics · DynaFlame Series

Camus DynaFlame DFW 3002 (Condensing DHW)

The Camus DynaFlame DFW 3002 is the condensing domestic-hot-water size of Camus' stainless-steel watertube line: 3000 MBTU/hr input, 2850 MBTU/hr output, up to 95% thermal efficiency and 5:1 turndown.

CurrentSold in Canada

Key figures

Max input
3,000 MBTU/hr
Max CSA output
2,850 MBTU/hr
AFUE
Min input
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Camus DynaFlame DFW 3002 (Condensing DHW) in practice

Per the official DynaFlame spec sheet (99-0144 Rev 01), the DFW 3002 is rated 3000 MBTU/hr input and 2850 MBTU/hr output with a 1120 lb approximate shipping weight. It connects through the range's vertical cylindrical watertube heat exchanger — 439 stainless steel, 6-pass, 160 psig working pressure — and vents in category ii or iv condensing configuration.

The model is a condensing appliance: the spec sheet prints up to 95% thermal efficiency with a 5:1 turndown ratio (minimum 20% firing rate) and light-off at no more than 50% input. Electrical draw is 14 A at 230 V single-phase, and the vent-diameter table prints Cat. I 10", Cat. III up to 50 ft 8", Cat. III up to 100 ft 12" and outdoor 8".

As a domestic-hot-water appliance the DFW 3002 is rated for recovery capacity of 3415 GPH at a 100°F rise, 4269 GPH at 80°F, 5692 GPH at 60°F; it is design certified to ANSI Z21.10 / CSA 4.3. Camus is a Mississauga, Ontario manufacturer, and Boilers.ca reproduces the manufacturer's printed figures here; sizing a boiler plant or DHW system remains a load calculation by a licensed contractor.

Best suited to

  • Domestic hot-water plants whose design load lands near 3000 MBTU/hr input (2850 MBTU/hr output)
  • Projects wanting a condensing Camus watertube boiler with a Canadian-built stainless heat exchanger
  • Multiple-boiler plants: the SOLA control documented for the DynaFlame line cascades up to eight units

Applicability and support

Model number
DF(N,P)W 3002
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Camus Hydronics. Units are shown with every value; notes flag conflicting sources or missing figures.

Camus DynaFlame DFW 3002 (Condensing DHW) specifications
SpecificationValueNote
Input
Input, maximum3,000 MBTU/hrAs printed in the official DynaFlame spec sheet (99-0144 Rev 01).
Output
Output, maximum2,850 MBTU/hrRecovery output as printed in the spec sheet.
Efficiency
Thermal efficiency95 %Up to 95% thermal efficiency as printed in the spec sheet (condensing).
Domestic hot water
Recovery at 100°F rise3,415 GPH
Recovery at 80°F rise4,269 GPH
Recovery at 60°F rise5,692 GPH
Venting and air
VentingCat. I 10" · Cat. III up to 50 ft 8" · Cat. III up to 100 ft 12" · outdoor 8"Category II or IV condensing.
Physical and connections
Shipping weight1,120 lbApproximate shipping weight as printed in the spec sheet.
Heat exchanger439 stainless steel welded 6-pass vertical cylindrical watertube
Electrical
Electrical14 A at 230 V single-phase
Operating limits and other
Turndown ratio5:1Proportional modulating with a minimum 20% firing rate; light-off at no more than 50% input.
Max. working pressure160 psig1100 kPa; ASME Section IV heat-exchanger testing.
FuelNatural gas or propane (optional dual-fuel operation listed)
CertificationCSA International design certified; ANSI Z21.10 / CSA 4.3
ApplicationDomestic hot water supply

Frequently asked questions

Is the DynaFlame DFW 3002 condensing?

It is the condensing generation: the official spec sheet prints up to 95% thermal efficiency and category ii or iv condensing venting.

How big is the DFW 3002?

The spec sheet prints 3000 MBTU/hr input and 2850 MBTU/hr output, a 1120 lb approximate shipping weight, and 14 A at 230 V single-phase.

What fuel does the DFW 3002 use?

The spec sheets list natural gas, propane and optional dual-fuel operation; the captured sheets print natural-gas ratings and the gas train description. Fuel selection and conversion are licensed trade work.

Questions about the Camus DynaFlame DFW 3002 (Condensing DHW)?