Skip to content
Boilers.caby ROMA Heating & Cooling

Camus Hydronics · DynaFlame Series

Camus DynaFlame DFH 5001 (Near-Condensing Heating)

The Camus DynaFlame DFH 5001 is the near-condensing hydronic-heating size of Camus' stainless-steel watertube line: 4999 MBTU/hr input, 4399 MBTU/hr output, up to 88% thermal efficiency and 5:1 turndown.

CurrentSold in Canada

Key figures

Max input
4,999 MBTU/hr
Max CSA output
4,399 MBTU/hr
AFUE
Min input
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Camus DynaFlame DFH 5001 (Near-Condensing Heating) in practice

Per the official DynaFlame spec sheet (99-0148 Rev 01), the DFH 5001 is rated 4999 MBTU/hr input and 4399 MBTU/hr output with a 1627 lb approximate shipping weight. It connects through the range's vertical cylindrical watertube heat exchanger — 439 stainless steel, 6-pass, 160 psig working pressure — and vents in category ii or iv near-condensing configuration.

The model is a near-condensing appliance: the spec sheet prints up to 88% thermal efficiency with a 5:1 turndown ratio (minimum 20% firing rate) and light-off at no more than 50% input. Electrical draw is 18 A at 230 V three-phase, and the vent-diameter table prints Cat. I 12", Cat. III up to 50 ft 10", Cat. III up to 100 ft 14" and outdoor 10".

As a hydronic heating boiler the DFH 5001 is design certified to ANSI Z21.13 / CSA 4.9. Camus is a Mississauga, Ontario manufacturer, and Boilers.ca reproduces the manufacturer's printed figures here; sizing a boiler plant remains a heat-loss and load calculation by a licensed contractor.

Best suited to

  • Hydronic heating plants whose design load lands near 4999 MBTU/hr input (4399 MBTU/hr output)
  • Projects wanting a near-condensing Camus watertube boiler with a Canadian-built stainless heat exchanger
  • Multiple-boiler plants: the SOLA control documented for the DynaFlame line cascades up to eight units

Applicability and support

Model number
DF(N,P)H 5001
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Camus Hydronics. Units are shown with every value; notes flag conflicting sources or missing figures.

Camus DynaFlame DFH 5001 (Near-Condensing Heating) specifications
SpecificationValueNote
Input
Input, maximum4,999 MBTU/hrAs printed in the official DynaFlame spec sheet (99-0148 Rev 01).
Output
Output, maximum4,399 MBTU/hrHydronic-heating output as printed in the spec sheet.
Efficiency
Thermal efficiency88 %Up to 88% thermal efficiency as printed in the spec sheet (near-condensing).
Venting and air
VentingCat. I 12" · Cat. III up to 50 ft 10" · Cat. III up to 100 ft 14" · outdoor 10"Category II or IV near-condensing.
Physical and connections
Shipping weight1,627 lbApproximate shipping weight as printed in the spec sheet.
Heat exchanger439 stainless steel welded 6-pass vertical cylindrical watertube
Electrical
Electrical18 A at 230 V three-phase
Operating limits and other
Turndown ratio5:1Proportional modulating with a minimum 20% firing rate; light-off at no more than 50% input.
Max. working pressure160 psig1100 kPa; ASME Section IV heat-exchanger testing.
FuelNatural gas or propane (optional dual-fuel operation listed)
CertificationCSA International design certified; ANSI Z21.13 / CSA 4.9
ApplicationHydronic heating

Frequently asked questions

Is the DynaFlame DFH 5001 condensing?

It is the near-condensing generation: the official spec sheet prints up to 88% thermal efficiency and category ii or iv near-condensing venting.

How big is the DFH 5001?

The spec sheet prints 4999 MBTU/hr input and 4399 MBTU/hr output, a 1627 lb approximate shipping weight, and 18 A at 230 V three-phase.

What fuel does the DFH 5001 use?

The spec sheets list natural gas, propane and optional dual-fuel operation; the captured sheets print natural-gas ratings and the gas train description. Fuel selection and conversion are licensed trade work.

Questions about the Camus DynaFlame DFH 5001 (Near-Condensing Heating)?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Compare and explore

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.