Camus DynaFlame DFW 1202 (Condensing Heating)

The Camus DynaFlame DFW 1202 is the condensing hydronic-heating size of Camus' stainless-steel watertube line: 1200 MBTU/hr input, 1140 MBTU/hr output, up to 95% thermal efficiency and 5:1 turndown.

CurrentSold in Canada

Key figures

Max input
1,200 MBTU/hr
Max CSA output
1,140 MBTU/hr
AFUE
Min input
Natural gasPropaneHeating-onlycommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Camus DynaFlame DFW 1202 (Condensing Heating) in practice

Per the official DynaFlame spec sheet (99-0145 Rev 01), the DFW 1202 is rated 1200 MBTU/hr input and 1140 MBTU/hr output with a 770 lb approximate shipping weight. It connects through the range's vertical cylindrical watertube heat exchanger — 439 stainless steel, 6-pass, 160 psig working pressure — and vents in category ii or iv configuration.

The model is a condensing appliance: the spec sheet prints up to 95% thermal efficiency with a 5:1 turndown ratio (minimum 20% firing rate) and light-off at no more than 50% input. Electrical draw is 7 A at 115 V single-phase, and the vent-diameter table prints Cat. I 7", Cat. III up to 50 ft 6", Cat. III up to 100 ft 8" and outdoor 6".

As a hydronic heating boiler the DFW 1202 is design certified to ANSI Z21.13 / CSA 4.9. Camus is a Mississauga, Ontario manufacturer, and Boilers.ca reproduces the manufacturer's printed figures here; sizing a boiler plant remains a heat-loss and load calculation by a licensed contractor.

Best suited to

  • Hydronic heating plants whose design load lands near 1200 MBTU/hr input (1140 MBTU/hr output)
  • Projects wanting a condensing Camus watertube boiler with a Canadian-built stainless heat exchanger
  • Multiple-boiler plants: the SOLA control documented for the DynaFlame line cascades up to eight units

Applicability and support

Model number
DF(N,P)W 1202
Canadian availability
available
Production status
current
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Not verified

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Camus Hydronics. Units are shown with every value; notes flag conflicting sources or missing figures.

Camus DynaFlame DFW 1202 (Condensing Heating) specifications
SpecificationValueNote
Input
Input, maximum1,200 MBTU/hrAs printed in the official DynaFlame spec sheet (99-0145 Rev 01).
Output
Output, maximum1,140 MBTU/hrHydronic-heating output as printed in the spec sheet.
Efficiency
Thermal efficiency95 %Up to 95% thermal efficiency as printed in the spec sheet (condensing).
Venting and air
VentingCat. I 7" · Cat. III up to 50 ft 6" · Cat. III up to 100 ft 8" · outdoor 6"Category II or IV.
Physical and connections
Shipping weight770 lbApproximate shipping weight as printed in the spec sheet.
Heat exchanger439 stainless steel welded 6-pass vertical cylindrical watertube
Electrical
Electrical7 A at 115 V single-phase
Operating limits and other
Turndown ratio5:1Proportional modulating with a minimum 20% firing rate; light-off at no more than 50% input.
Max. working pressure160 psig1100 kPa; ASME Section IV heat-exchanger testing.
FuelNatural gas or propane (optional dual-fuel operation listed)
CertificationCSA International design certified; ANSI Z21.13 / CSA 4.9
ApplicationHydronic heating

Frequently asked questions

Is the DynaFlame DFW 1202 condensing?

It is the condensing generation: the official spec sheet prints up to 95% thermal efficiency and category ii or iv venting.

How big is the DFW 1202?

The spec sheet prints 1200 MBTU/hr input and 1140 MBTU/hr output, a 770 lb approximate shipping weight, and 7 A at 115 V single-phase.

What fuel does the DFW 1202 use?

The spec sheets list natural gas, propane and optional dual-fuel operation; the captured sheets print natural-gas ratings and the gas train description. Fuel selection and conversion are licensed trade work.

Questions about the Camus DynaFlame DFW 1202 (Condensing Heating)?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Compare and explore

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate