Weil-McLain EG-30

The EG-30 is the smallest EG cast iron boiler: 75 MBH input, 64/62 MBH water/steam DOE heating capacity, 196 sq ft of steam coverage and 84%/82% water/steam AFUE — discontinued in Canada, still sold in the US as EG Series 6 and Series 7.

DiscontinuedHistorically in Canada

Key figures

Max input
75 MBH
Max CSA output
AFUE
Min input
Natural gasPropaneHeating-onlyresidentialcommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Weil-McLain EG-30 in practice

The EG-30 opens the eight-size EG range at 75 MBH CSA input, with 64 MBH of DOE water heating capacity and 62 MBH in steam, and net AHRI ratings of 56 MBH water and 47 MBH steam covering 196 sq ft. Like every EG size it is rated 84% AFUE in water and 82% in steam, and it ships at approximately 430 lb.

It is an atmospheric cast iron boiler with Category I, B-vent venting — vertical only, natural draft through a draft hood with an automatic vent damper and a 5" I.D. chimney collar. The manual lists a 3" supply tapping, 2-1/2" return, 1/2" gas connection and 3/4" relief tapping, with 12.3 gal of water content and 8.4 gal to the steam waterline. The EG is discontinued in Canada, where the weil-mclain.ca page sits in the Discontinued menu, while the US continues the line as Series 6 and Series 7.

Best suited to

  • Small water or steam loads near 75 MBH with a chimney
  • Replacing a compact atmospheric cast iron boiler
  • Documenting an EG generation that Canada discontinued

Applicability and support

Model number
EG-30
Canadian availability
historical
Production status
discontinued
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Series terms

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Weil-McLain. Units are shown with every value; notes flag conflicting sources or missing figures.

Weil-McLain EG-30 specifications
SpecificationValueNote
Input
Input, maximum75 MBHCSA input per the US EG Series 6/7 spec tables and the EG Series 7 manual ratings table (Table 20).
Output
DOE heating capacity, water64 MBHWater heating capacity per manual Table 20; matches the CA discontinued page's output figure.
DOE heating capacity, steam62 MBHSteam heating capacity per manual Table 20.
Net AHRI rating, water56 MBHNet AHRI water rating based on a 1.15 piping and pick-up allowance per the manual ratings notes.
Net AHRI rating, steam47 MBHNet AHRI steam rating based on a 1.333 pick-up allowance per the manual ratings notes.
Net AHRI steam rating, area196 sq ftSteam square-foot rating per manual Table 20; the CA discontinued page's published range ends at 750 sq ft, which does not match the EG-75's 733 sq ft.
Efficiency
AFUE, water84 %84.0% AFUE in water per manual Table 21 and the US spec tables.
AFUE, steam82 %82.0% AFUE in steam per manual Table 21 and the US spec tables.
Venting and air
VentingCategory I, B-vent — vertical vent only, natural draft with draft hood and automatic vent damper; 5" I.D. chimney x 20 ftPer the US spec tables (chimney size) and the CA discontinued page (Cat. 1, B-vent, vertical vent only).
Physical and connections
Supply connection3"Supply tapping O is 1 x 3" on every EG/PEG size per the Series 7 manual connections section.
Return connection2-1/2"Return tapping P is 1 x 2-1/2" on every EG/PEG size per the Series 7 manual connections section.
Gas connection1/2"Gas connection F is 1/2" on EG/PEG-30 through -55 per the Series 7 manual.
Relief valve3/4" tappingWater boilers use a 3/4" tapping on the side with a 30 psi relief valve; steam boilers use a 15 psi relief valve on a top tapping per the Series 7 manual.
Weight430 lbApproximate shipping weight per the US spec tables and manual Table 20.
Operating limits and other
Boiler water content12.3 galWater content per manual Table 20.
Steam-to-waterline content8.4 galSteam-to-waterline water content per manual Table 20.

Frequently asked questions

What are the EG-30's ratings?

75 MBH CSA input, 64 MBH DOE water heating capacity, 62 MBH steam, 56 MBH net AHRI water, 47 MBH net AHRI steam (196 sq ft), and 84% water / 82% steam AFUE per the US spec tables and manual.

Is the EG-30 still sold in Canada?

No. Weil-McLain Canada's EG / EG Steam page is in the Discontinued menu; the US still sells the EG as Series 6 and Series 7, so literature should match the unit's generation.

How does the EG-30 vent?

Category I, B-vent with vertical venting only: natural draft through a draft hood with an automatic vent damper and a 5" I.D. chimney collar.

Questions about the Weil-McLain EG-30?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.