Weil-McLain EG DHW VOLTAGE HIGH — DHW / Thermostat2 Input Excessive Voltage

DHW VOLTAGE HIGH

Needs attentionWeil-McLain EG Series cast-iron boilers (display faults, manual 550-100-225)

DHW / Thermostat2 input excessive voltage. Unplug the control P3 connector. Measure the voltage between the control connector's Pins 4 & 6. Is the measured voltage in excess of 24 Vac nominal? If no, inspect the harness for a short. If yes, measure the voltage of the 24 Vac transformer output connector P1 between P1 pins 6 & 7 without unplugging it from the control; if in excess of 24 Vac nominal, replace the transformer; if not, inspect 120 Vac supply power. The table classifies it as voltage.

Applies to

This domestic hot water fault code is displayed by the EG water control (display faults) on EG models (EG-30 through EG-75), as documented in EG Series 7 Boiler Manual, doc 550-100-225/0425 (Table 17 water-control faults; steam uses charts + limit/LWCO) (550-100-225/0425). Codes can differ between controller generations, so always check the manual that matches your unit.

Controller: EG water control (display faults). Source manual: 550-100-225/0425 (2025-04).

Why a code is not a diagnosis

A DHW code involves the hot-water side: sensors, flow, the mixing/bypass valve or the DHW heat exchanger. It does not say whether the fix is a sensor, a valve or a flush.

Safe things to observe

  • Note the code and whether the problem follows a hot-water draw or appears at all times.

Do not

  • Do not open the appliance to test DHW components yourself.

How professional service helps

  1. A technician tests the DHW sensors, flow switch and valve circuits, and cleans the DHW path where the manual directs.
  2. Combustion and safety devices are verified with an analyser and the manufacturer's procedure after any repair.

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Parts and service

Parts commonly involved

These parts appear in the documented text for this alert. A code reports a condition, not a failed part — a technician confirms the cause by testing before anything is replaced.

Service for this alert

  • Gas Boiler Repair

    Licensed gas technicians from ROMA Heating & Cooling diagnose and repair residential and light-commercial gas boilers across…

Every boiler part explained — what it does, how it fails and what a technician checks.

Documented for Weil-McLain EG / EG Steam.

Frequently asked questions

Can I clear this code myself?

Clearing a code without fixing its cause usually just brings it back. Note the code, check the safe items on this page, then call a licensed technician. If your appliance manual describes a user reset for this exact code and it stays away, no call may be needed.

Boiler locked out? Call with the alert text ready.

The brand, model and this alert are passed along when you request service online, so the technician arrives prepared.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.