Weil-McLain EG-50

The EG-50 moves the EG range to 175 MBH input with 148/145 MBH water/steam DOE heating capacity, 454 sq ft of steam coverage, 84%/82% AFUE and a 7" I.D. chimney; discontinued in Canada, current in the US.

DiscontinuedHistorically in Canada

Key figures

Max input
175 MBH
Max CSA output
AFUE
Min input
Natural gasPropaneHeating-onlyresidentialcommercial

Input is gas energy consumed; output is heat delivered. Never size from input alone.

Weil-McLain EG-50 in practice

The EG-50 is rated 175 MBH CSA input and produces 148 MBH of DOE water heating capacity and 145 MBH in steam, with net AHRI ratings of 129 MBH water and 109 MBH steam covering 454 sq ft. It carries the range's 84% water / 82% steam AFUE and ships at approximately 585 lb.

It is built as an atmospheric cast iron boiler with Category I, B-vent vertical venting, a draft hood, an automatic vent damper and a 7" I.D. chimney collar. Manual data lists a 3" supply tapping, 2-1/2" return, 1/2" gas connection and 3/4" relief tapping, with 17.3 gal of water content and 11.2 gal to the steam waterline. Canada lists the EG as discontinued; the US still sells the model within EG Series 6 and Series 7.

Best suited to

  • Light-commercial or large residential loads near 175 MBH
  • Steam systems needing about 454 sq ft of radiation
  • Replacement planning where a 7" chimney is available

Applicability and support

Model number
EG-50
Canadian availability
historical
Production status
discontinued
ROMA supplies
Confirmed at consultation
ROMA services
Confirmed at consultation
Warranty
Series terms

Where ROMA provides on-site service

On-site service is currently offered in Greater Vancouver, BC, including Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Port Coquitlam, Port Moody, Delta, Langley, Maple Ridge, Abbotsford, Chilliwack, White Rock, Pitt Meadows, Tsawwassen, Anmore, Lions Bay, Belcarra, Bowen Island, Mission. Everything else on this site is reference information you can use anywhere in Canada.

See all service areas

Specifications

Published specifications

Values as published by Weil-McLain. Units are shown with every value; notes flag conflicting sources or missing figures.

Weil-McLain EG-50 specifications
SpecificationValueNote
Input
Input, maximum175 MBHCSA input per the US EG Series 6/7 spec tables and the EG Series 7 manual ratings table (Table 20).
Output
DOE heating capacity, water148 MBHWater heating capacity per manual Table 20; matches the CA discontinued page's output figure.
DOE heating capacity, steam145 MBHSteam heating capacity per manual Table 20.
Net AHRI rating, water129 MBHNet AHRI water rating based on a 1.15 piping and pick-up allowance per the manual ratings notes.
Net AHRI rating, steam109 MBHNet AHRI steam rating based on a 1.333 pick-up allowance per the manual ratings notes.
Net AHRI steam rating, area454 sq ftSteam square-foot rating per manual Table 20; the CA discontinued page's published range ends at 750 sq ft, which does not match the EG-75's 733 sq ft.
Efficiency
AFUE, water84 %84.0% AFUE in water per manual Table 21 and the US spec tables.
AFUE, steam82 %82.0% AFUE in steam per manual Table 21 and the US spec tables.
Venting and air
VentingCategory I, B-vent — vertical vent only, natural draft with draft hood and automatic vent damper; 7" I.D. chimney x 20 ftPer the US spec tables (chimney size) and the CA discontinued page (Cat. 1, B-vent, vertical vent only).
Physical and connections
Supply connection3"Supply tapping O is 1 x 3" on every EG/PEG size per the Series 7 manual connections section.
Return connection2-1/2"Return tapping P is 1 x 2-1/2" on every EG/PEG size per the Series 7 manual connections section.
Gas connection1/2"Gas connection F is 1/2" on EG/PEG-30 through -55 per the Series 7 manual.
Relief valve3/4" tappingWater boilers use a 3/4" tapping on the side with a 30 psi relief valve; steam boilers use a 15 psi relief valve on a top tapping per the Series 7 manual.
Weight585 lbApproximate shipping weight per the US spec tables and manual Table 20.
Operating limits and other
Boiler water content17.3 galWater content per manual Table 20.
Steam-to-waterline content11.2 galSteam-to-waterline water content per manual Table 20.

Frequently asked questions

What are the EG-50's ratings?

175 MBH CSA input, 148 MBH DOE water heating capacity, 145 MBH steam, 129 MBH net AHRI water, 109 MBH net AHRI steam (454 sq ft), and 84% water / 82% steam AFUE per the US spec tables and manual.

Does the EG-50 have a low water cut-off?

The steam version includes a probe-type low water cut-off and gauge glass per the manual; water boilers use a Unity-CI ignition module with a temperature/LWCO sensor.

Is the EG-50 sold in Canada?

No. Weil-McLain Canada's EG / EG Steam page is in the Discontinued menu; US sales continue as EG Series 6 and Series 7.

Questions about the Weil-McLain EG-50?

Describe what the boiler is doing and get a straight answer about the next step.

On-site service in Greater Vancouver, BC. ROMA lists “Open 7 days” on its site; call to confirm same-day availability.

Sources and verification

Facts checked September 9, 2026. Last updated September 9, 2026. Technical reviewer: not yet assigned.

CallEmailEstimate